Daikin ductless and SkyAir systems show a two-character error code (A3, E5, U4…) on the remote controller when a fault stops or limits the unit. This table gives each code's meaning in Daikin's own words, what Daikin lists to check first, the parts commonly involved, and our detailed guide where we have one. Meanings come from Daikin service manuals SiUS281811EA (RZR/RZQ-TA SkyAir with FCQ, FHQ, FAQ, FBQ and FTQ indoor units) and DAMA-SM-21-001 (FTK/FTX09-24AXVJU wall-mount with RK/RX outdoor units), with Daikin's general SM-TS3 list for cross-reference.

60 codes. 42 have a detailed guide. Jump to a code: A0 A1 A3 A5 A6 A7 A8 A9 AF AJ C1 C4 C5 C6 C9 CA CE CJ E1 E3 E4 E5 E6 E7 E8 E9 EA F3 F6 H0 H6 H9 J3 J5 J6 J7 J9 JA JC L1 L3 L4 L5 L8 L9 LC P1 P4 U0 U2 U3 U4 U5 U8 U9 UA UC UE UF UH

How to read a Daikin code

  • Letter = area. In SiUS281811EA, A and C codes are indoor unit faults, E, F, H, J, L and P are outdoor unit faults, and U codes are system faults (power, transmission, settings). CJ is the remote controller's own thermistor.
  • Blinking vs steady lamp. A blinking operation lamp means the unit stopped on the fault. For A7, AF, CA, CE, CJ, P4, U0 and UC the lamp stays ON and the system keeps running, but the manual says to check and repair.
  • Sub-codes. On a BRC1E-series navigation remote, a code can carry a sub-code (for example AJ-01 or AJ-02) that narrows the fault (SiUS281811EA section 4.2).
  • Wired remote. On the BRC1E73 a blinking operation lamp means the system has stopped. Press Menu/OK to see the code.
  • Wireless remote. ARC452A-type remotes use the TIMER CANCEL method in Daikin SM-TS3 pp. 7-8. See How to Read a Daikin Error Code with an ARC452A Remote.
  • Outdoor board. RZR/RZQ-TA outdoor PCBs can also show the code on LEDs H1P-H7P in monitor mode (SiUS281811EA section 4.3).
  • Same code, different model. Some codes mean different things on different families (E5, F6, L5, U2 below). Read the meaning for your model.

Daikin error code table

"SkyAir" = SiUS281811EA wording. "Wall-mount AX" = DAMA-SM-21-001 wording. "First checks" condenses the supposed causes Daikin lists for that code. Parts are commonly involved — confirm by diagnosis: a listing appears only where the manual names that component for the code. Match the part number on your unit before ordering.

Code Meaning (Daikin wording) Unit side First checks (from the manual) Parts commonly involved — confirm by diagnosis Our detailed guide
A0 SkyAir: External protection device abnormality Indoor External protection device tripped; field setting; indoor unit PCB. — —
A1 SkyAir: Indoor unit PCB abnormality
Wall-mount AX: Indoor unit PCB abnormality
Indoor External factor such as electrical noise; then the indoor unit PCB. Daikin Applied 6025170 — Printed Circuit Assy (Main)
Daikin Applied 2371986 — Main Pcb Board
Our reading: PCB titles do not say indoor or outdoor; match the number on your board.
Daikin A1 or E1 Error: Indoor or Outdoor PCB, and What to Check First
A3 SkyAir: Drain level control system (S1L) abnormality Indoor Drain pump, drain piping work or clogging, float switch, PCB short-circuit connector. Daikin Applied 2013437 — Condensate Drain Pump
Daikin Applied 5011011 — Drain Pump Assembly
Daikin Applied 139502J — Float Switch
Daikin A3 Error: Drain Pump, Float Switch or Clogged Drain?
A5 Wall-mount AX: Freeze-up protection control Indoor Short-circuited air, clogged filter, dusty indoor coil, coil thermistor, indoor PCB. Daikin Applied 4010117 — Indoor Coil Sensor
Our reading: Listing title says indoor coil sensor; it does not name AX-series models.
Daikin A5 Error on Wall-Mount Units: Freeze-Up or Coil Sensor?
A6 SkyAir: Indoor fan motor (M1F) lock, overload; Indoor fan motor abnormality (plus three FTQ-TA-only A6 rows)
Wall-mount AX: Indoor fan motor (DC motor) or related abnormality
Indoor Foreign matter at the fan, motor harness and connectors, fan motor, indoor PCB. —
Our reading: Our fan motor titles do not say indoor or outdoor; see the guide for listings.
Daikin A6 and E7 Errors: Indoor or Outdoor Fan Motor Fault?
A7 SkyAir: Swing flap motor abnormality
Operation lamp ON: unit keeps running, but check and repair.
Indoor Swing motor, its cable and limit switch, micro-switch, indoor main PCB. — —
A8 SkyAir: Power supply voltage abnormality (FTQ-TA: blower motor stops for over/under voltage) Indoor Supply voltage, signal-line connection, wiring, instantaneous power failure. — —
A9 SkyAir: Electronic expansion valve coil abnormality, Dust clogging Indoor Indoor EEV coil, indoor unit main PCB, relay cables. Daikin Applied 2433473 — Coil/el. Expansion Valve
Daikin Applied 2430474 — Coil/ Electronic Txv
Daikin Applied 142054J — Electronic Expansion Valve
Daikin A9 Error: Indoor Expansion Valve Coil or Valve Body?
AF SkyAir: Drain level above limit
Operation lamp ON: unit keeps running, but check and repair.
Indoor Drain pipe installation, float switch, indoor PCB, connector, drain pump. Daikin Applied 139502J — Float Switch
Daikin Applied 2013437 — Condensate Drain Pump
Daikin A3 Error: Drain Pump, Float Switch or Clogged Drain?
AJ SkyAir: Defective capacity setting Indoor Was a spare PCB fitted? Was the capacity setting adaptor installed? Daikin Applied 065336J — Capacity Setting Adaptor
Daikin Applied 065331J — Capacity Setting Adaptor
Daikin Applied 066965J — Capacity Setting Adaptor
Our reading: Adaptor titles do not state capacity class; match by part number.
Daikin AJ Error: Capacity Setting Adaptor and Defective Capacity Setting
C1 SkyAir: Transmission abnormality (between indoor unit PCB and fan PCB) Indoor A1P-to-A2P connector, indoor main PCB, fan PCB, power interruption. — —
C4 SkyAir: Heat exchanger liquid pipe thermistor abnormality
Wall-mount AX: Indoor heat exchanger thermistor or related abnormality
Indoor Thermistor, connector, broken or disconnected wire, indoor unit PCB. Daikin Applied 2433125 — Thermistor Assy. (Liq)
Daikin Applied 063151J — Thermistor (For Liquid Line)
Daikin C4, C9, J3, J5, J6, H9 Error Codes: Which Thermistor Failed?
C5 SkyAir: Heat exchanger gas pipe thermistor abnormality Indoor Thermistor, connector, broken or disconnected wire, indoor unit PCB. — —
C6 SkyAir: Combination abnormality (between indoor unit PCB and fan PCB) Indoor Fan PCB, capacity setting adaptor connection, setting error. —
Our reading: The AJ guide covers C6-01 as a related entry, not as its main topic.
Daikin AJ Error: Capacity Setting Adaptor and Defective Capacity Setting
C9 SkyAir: Suction air thermistor (R1T) abnormality; Remote sensor abnormality
Wall-mount AX: Room temperature thermistor or related abnormality
Indoor Thermistor, connector, broken or disconnected wire, indoor unit PCB. Daikin Applied 2258261 — Thermistor (Suction Air)
Daikin Applied 2258247 — Thermistor Suction Air
Daikin C4, C9, J3, J5, J6, H9 Error Codes: Which Thermistor Failed?
CA SkyAir: Discharge air thermistor abnormality
Operation lamp ON: unit keeps running, but check and repair.
Indoor Thermistor, connector, broken or disconnected wire, indoor unit PCB. — —
CE SkyAir: Infrared presence/floor sensor error
Operation lamp ON: unit keeps running, but check and repair.
Indoor Presence sensor connector (CE-01) or floor sensor faults (CE-02 to CE-04). — —
CJ SkyAir: Remote controller thermistor abnormality
Operation lamp ON: unit keeps running, but check and repair.
Remote controller (in the indoor list) Remote controller thermistor, remote controller PCB, electrical noise. Daikin Applied BRC1H71W — Madoka Remote Controller
Our reading: The manual names BRC1E73/BRC2A71 remotes; we list the Madoka only.
Daikin CJ Error: Remote Controller Thermistor or Field Setting?
E1 SkyAir: Outdoor main PCB abnormality
Wall-mount AX: Outdoor unit PCB abnormality
Outdoor Inside/outside relay wires, outdoor main PCB; DAMA adds noise and voltage dips. Daikin Applied 6025170 — Printed Circuit Assy (Main)
Daikin Applied 2371986 — Main Pcb Board
Our reading: PCB titles do not say indoor or outdoor; match the number on your board.
Daikin A1 or E1 Error: Indoor or Outdoor PCB, and What to Check First
E3 SkyAir: Activation of high pressure switch Outdoor HP switch tripped, HP switch, outdoor main PCB, power failure, HP sensor. Daikin Applied 151107J — High Pressure Switch
Daikin Applied 2534983 — High Pressure Switch
Daikin E3 and E4 Errors: High Pressure vs Low Pressure
E4 SkyAir: Activation of low pressure sensor Outdoor Stop valve not opened, low pressure drop, LP sensor, outdoor main PCB. Daikin Applied 6023719 — Low Pressure Sensor Daikin E3 and E4 Errors: High Pressure vs Low Pressure
E5 SkyAir: Inverter compressor motor lock
Wall-mount AX: OL activation (compressor overload)
Outdoor SkyAir: stop valve, UVW wiring, high differential pressure, PCB. Wall-mount: OL and discharge thermistor. Daikin Applied 150638J — Scroll Compressor
Daikin Applied 1703496 — Swing Compressor
Daikin Applied 2198390 — Inverter Assembly/control Board
Our reading: Compressor titles give type only, not model.
Daikin E5 Error: Inverter Compressor Lock or Bad Outdoor PCB?
E6 Wall-mount AX: Compressor lock Outdoor Closed stop valve, locked compressor, disconnected compressor harness. Daikin Applied 6025170 — Printed Circuit Assy (Main)
Daikin Applied 4005672 — Swing Compressor
Our reading: 4005672 matches the manual's swing compressor type only.
Daikin E6, H6 or H0 Error: Compressor Won't Start or Bad Board?
E7 SkyAir: Outdoor fan motor abnormality
Wall-mount AX: DC fan lock
Outdoor Foreign matter at the fan, motor-to-PCB harness, fan motor, outdoor PCB. Daikin Applied 4015250 — Condenser Fan Motor
Daikin Applied 4016596 — Condenser Fan Motor 220v
Daikin Applied 4017514 — Dc280v 41w 8p Motor
Our reading: 4017514 matches the 41 W DC fan motor spec of RK/RX09-12 only.
Daikin A6 and E7 Errors: Indoor or Outdoor Fan Motor Fault?
E8 Wall-mount AX: Input overcurrent detection Outdoor Outdoor temperature out of range, compressor, power module, outdoor PCB, short circuit. — —
E9 SkyAir: Electronic expansion valve coil abnormality Outdoor EEV connectors, EEV coil, outdoor main PCB. Daikin Applied 2254074 — Coil/elec Exp Valve
Daikin Applied 2254067 — Coil/elec Exp Valve
Daikin L5 and E9 Errors: Inverter Board, Compressor or EEV Coil?
EA Wall-mount AX: Four way valve abnormality Outdoor Connector contact, thermistor, four-way valve coil or harness, the valve, low charge, PCB. Daikin Applied 4009532 — Coil, Four-Way Valve
Daikin Applied 4005910 — Coil, Four-Way Valve
Daikin Applied 1946976 — Four Way Reversing Valve Body
Our reading: Titles name no FTX/RX model; match the old part number.
Daikin EA Error: Four-Way Valve Coil, Thermistor or Stuck Valve?
F3 SkyAir: Discharge pipe temperature abnormality
Wall-mount AX: Discharge pipe temperature control
Outdoor Discharge pipe thermistor and its connection, outdoor PCB; DAMA adds EEV, charge, stop valve. Daikin Applied 2425775 — Thermistor
Daikin Applied 2254074 — Coil/elec Exp Valve
Daikin F3 Error: Discharge Pipe Thermistor, EEV Coil or Low Charge?
F6 SkyAir: Refrigerant overcharged
Wall-mount AX: High pressure control in cooling
Outdoor SkyAir: overcharge, outdoor thermistors. Wall-mount: clearance, dirty coil, fan motor. Daikin Applied 063151J — Thermistor (For Liquid Line)
Daikin Applied 6018704 — Thermistor (Air)
Daikin F6 Error: Refrigerant Overcharge or High Pressure Control?
H0 Wall-mount AX: Compressor sensor system abnormality Outdoor Broken or disconnected harness, outdoor unit PCB. Daikin Applied 6025170 — Printed Circuit Assy (Main) Daikin E6, H6 or H0 Error: Compressor Won't Start or Bad Board?
H6 Wall-mount AX: Position sensor abnormality Outdoor Supply voltage, compressor harness, closed stop valve, compressor, outdoor PCB. Daikin Applied 6025170 — Printed Circuit Assy (Main)
Daikin Applied 4005672 — Swing Compressor
Our reading: 4005672 matches the manual's swing compressor type only.
Daikin E6, H6 or H0 Error: Compressor Won't Start or Bad Board?
H9 SkyAir: Outdoor air thermistor abnormality
Wall-mount AX: Outdoor temperature thermistor or related abnormality
Outdoor Thermistor and its connection, outdoor main PCB. Daikin Applied 3P381576-1 — Ambient Air Temperature Sensor
Our reading: Listing is titled ambient air sensor; it does not say H9 sensor on your model.
Daikin C4, C9, J3, J5, J6, H9 Error Codes: Which Thermistor Failed?
J3 SkyAir: Discharge pipe thermistor abnormality
Wall-mount AX: Discharge pipe thermistor or related abnormality
Outdoor Thermistor and its connection, outdoor main PCB. Daikin Applied 6025111 — Thermistor (R1/2/3T)
Our reading: R1/2/3T title matches SkyAir symbols only; other families use them differently.
Daikin C4, C9, J3, J5, J6, H9 Error Codes: Which Thermistor Failed?
J5 SkyAir: Suction pipe thermistor abnormality Outdoor Thermistor and its connection, outdoor main PCB. Daikin Applied 6025111 — Thermistor (R1/2/3T)
Our reading: R1/2/3T title matches SkyAir symbols only; other families use them differently.
Daikin C4, C9, J3, J5, J6, H9 Error Codes: Which Thermistor Failed?
J6 SkyAir: Outdoor heat exchanger deicer thermistor abnormality
Wall-mount AX: Outdoor heat exchanger thermistor or related abnormality
Outdoor Thermistor and its connection, outdoor main PCB. — Daikin C4, C9, J3, J5, J6, H9 Error Codes: Which Thermistor Failed?
J7 SkyAir: Outdoor heat exchanger liquid pipe thermistor abnormality Outdoor Thermistor and its connection, outdoor main PCB. — —
J9 SkyAir: Subcooling heat exchanger gas pipe thermistor abnormality Outdoor Thermistor and its connection, outdoor main PCB. — —
JA SkyAir: High pressure sensor abnormality Outdoor HP sensor and its connection, LP sensor on wrong connector, outdoor main PCB. Daikin Applied 6023718 — High Pressure Sensor Daikin JA and JC Errors: High or Low Pressure Sensor Failed?
JC SkyAir: Low pressure sensor abnormality Outdoor LP sensor and its connection, HP sensor on wrong connector, outdoor main PCB. Daikin Applied 6023719 — Low Pressure Sensor Daikin JA and JC Errors: High or Low Pressure Sensor Failed?
L1 SkyAir: PCB (for inverter compressor) abnormality Outdoor IPM, current sensor or drive circuit failure. — Daikin A1 or E1 Error: Indoor or Outdoor PCB, and What to Check First
L3 Wall-mount AX: Electrical box temperature rise Outdoor Outdoor fan motor, short circuit, radiation fin thermistor, connector, outdoor PCB. Daikin Applied 4017514 — Dc280v 41w 8p Motor
Our reading: 4017514 matches the 41 W DC fan motor spec of RK/RX09-12 only.
Daikin L3 Error: Electrical Box Overheat, Fan Motor or PCB?
L4 SkyAir: Radiation fin temperature rise abnormality
Wall-mount AX: Radiation fin temperature rise
Outdoor Fin thermistor, outdoor PCB; DAMA adds fan motor and fin grease after PCB swap. Daikin Applied 1885374 — Fin Thermistor
Daikin Applied 2198390 — Inverter Assembly/control Board
Daikin L4 and P4 Errors: Radiation Fin Overheat or Fin Thermistor?
L5 SkyAir: Inverter compressor instantaneous overcurrent
Wall-mount AX: Output overcurrent detection
Outdoor Compressor coil, compressor mechanical lock, PCB. Daikin Applied 2198390 — Inverter Assembly/control Board
Daikin Applied 129040J — Inverter PCB Assembly
Daikin Applied 1703496 — Swing Compressor
Our reading: Board and compressor titles name no unit model.
Daikin L5 and E9 Errors: Inverter Board, Compressor or EEV Coil?
L8 SkyAir: Inverter compressor overcurrent Outdoor Compressor overload, broken wire in compressor, PCB, compressor disconnected. Daikin Applied 129040J — Inverter PCB Assembly
Daikin Applied 1703496 — Swing Compressor
Our reading: Board and compressor titles name no unit model.
Daikin L8 or L9 Error: Inverter Compressor or Outdoor PCB?
L9 SkyAir: Inverter compressor startup abnormality Outdoor Compressor, large pressure difference before start, PCB. Daikin Applied 129040J — Inverter PCB Assembly
Daikin Applied 1703496 — Swing Compressor
Our reading: Board and compressor titles name no unit model.
Daikin L8 or L9 Error: Inverter Compressor or Outdoor PCB?
LC SkyAir: Transmission error (between microcomputers on the outdoor main PCB) Outdoor Outdoor main PCB, noise filter, noise, inverter compressor, fan motor. — Daikin A1 or E1 Error: Indoor or Outdoor PCB, and What to Check First
P1 SkyAir: Inverter circuit capacitor high voltage Outdoor Main circuit capacitor and wiring, outdoor PCB, phase imbalance or missing phase. — —
P4 SkyAir: Radiation fin thermistor abnormality
Wall-mount AX: Radiation fin thermistor or related abnormality
Operation lamp ON: unit keeps running, but check and repair.
Outdoor Fin thermistor, PCB, inverter compressor, fan motor. Daikin Applied 1885374 — Fin Thermistor Daikin L4 and P4 Errors: Radiation Fin Overheat or Fin Thermistor?
U0 SkyAir: Refrigerant shortage
Operation lamp ON: unit keeps running, but check and repair.
System Shortage or clogging, suction pipe thermistor, pressure sensor, outdoor main PCB. — —
U2 SkyAir: Power supply insufficient or instantaneous abnormality
Wall-mount AX: Low-voltage detection or over-voltage detection
System Supply voltage, power failure, outdoor fan motor, outdoor PCB. — —
U3 SkyAir: Check operation not executed System Check operation has not been run. — —
U4 SkyAir: Transmission error between indoor units and outdoor units
Wall-mount AX: Signal transmission error (between indoor unit and outdoor unit)
System F1/F2 wiring, outdoor power, system address; then indoor or outdoor PCB. Daikin Applied 6025170 — Printed Circuit Assy (Main)
Daikin Applied 2371986 — Main Pcb Board
Our reading: PCB titles do not say indoor or outdoor; match the number on your board.
Daikin U4 Error: Indoor-to-Outdoor Transmission Fault
U5 SkyAir: Transmission error between remote controller and indoor unit System Two remotes both set as main, indoor PCB, remote PCB, noise. Daikin Applied BRC1H71W — Madoka Remote Controller
Daikin Applied 6025170 — Printed Circuit Assy (Main)
Daikin U5 or U8 Error: Remote Controller Setting, Wiring or Bad PCB?
U8 SkyAir: Transmission error between main and sub remote controllers System Sub remotes wired to each other; remote controller PCB. Daikin Applied BRC1H71W — Madoka Remote Controller Daikin U5 or U8 Error: Remote Controller Setting, Wiring or Bad PCB?
U9 SkyAir: Transmission error between indoor and outdoor units in the same system System Other system's indoor EEV or PCB; indoor-outdoor transmission wiring. — —
UA SkyAir: Improper combination of indoor and outdoor units, indoor units and remote controller
Wall-mount AX: Installation error (between indoor unit and outdoor unit)
System Too many indoor units, refrigerant mismatch, spare outdoor PCB not set. — Daikin U4 Error: Indoor-to-Outdoor Transmission Fault
UC SkyAir: Address duplication of centralized controller
Operation lamp ON: unit keeps running, but check and repair.
System Duplicate centralized controller address; indoor unit PCB. — —
UE SkyAir: Transmission error between centralized controller and indoor unit System Transmission wiring, group No. or address setting, controller PCB, indoor PCB. — —
UF SkyAir: System not set System Transmission wiring, check operation not run, stop valve, indoor PCB. — —
UH SkyAir: System abnormality, refrigerant system address undefined System Indoor-outdoor transmission wiring, indoor PCB, outdoor main PCB. — Daikin U4 Error: Indoor-to-Outdoor Transmission Fault

Scope

Code meanings and causes are quoted or condensed from SiUS281811EA (RZR18-48TAVJU(A) cooling only and RZQ18-48TAVJU(A) heat pump SkyAir) and DAMA-SM-21-001 (FTK/FTX09-24AXVJU with RK/RX09-24AXVJU). A code that appears in only one column is not in the other manual's code list. Other Daikin families, including VRV, may word or check a code differently. Lines marked "Our reading" are our interpretation, not Daikin's text. Listings are shown by live product title; they are not a fit confirmation for your unit.

Before you order

Write down the code and any sub-code, and the indoor and outdoor model numbers from the nameplates. Read the part number on the old part. To confirm fit, contact us or email help@totalhvacparts.com. Browse all Daikin Parts for VRV Units.

Frequently Asked Questions

What does a Daikin error code mean?

It is the controller's self-diagnosis result. The letter shows the area and the digit the fault. In service manual SiUS281811EA, A and C codes are indoor unit faults, E, F, H, J, L and P codes are outdoor unit faults, and U codes are system faults such as transmission errors. Each code has its own troubleshooting section with a list of supposed causes.

Does the same Daikin code mean the same thing on every model?

No. E5 is "Inverter compressor motor lock" in SiUS281811EA (RZR/RZQ-TA SkyAir) but "OL activation (compressor overload)" in DAMA-SM-21-001 (FTK/FTX AX wall-mount). F6 is "Refrigerant overcharged" in one and "High pressure control in cooling" in the other. Use the service manual for your model.

Which Daikin codes let the unit keep running?

SiUS281811EA shows the operation lamp ON, not blinking, for A7, AF, CA, CE, CJ, P4, U0 and UC. The manual says system operation continues for these codes, but they should still be checked and repaired. For CJ it notes the system may not continue, depending on conditions.

What does Daikin U4 mean?

On RZR/RZQ-TA SkyAir systems U4 is "Transmission error between indoor units and outdoor units". The listed causes are F1/F2 wiring faults, outdoor power OFF, a system address mismatch, and a defective indoor PCB or outdoor main PCB. Three of the five are not boards.

How do I read the error code on a Daikin wireless remote?

For ARC452A-type remotes, Daikin's SM-TS3 sheet (pp. 7-8) says to hold TIMER CANCEL for 5 seconds until "00" flashes, then press it repeatedly until the unit gives a long beep. The code showing at that beep is the error code.

Can the error code tell me which part to replace?

Not on its own. Each code has a list of supposed causes, and many are wiring, settings, airflow or refrigerant charge. The parts in this table are commonly involved. Confirm with the flowchart in the service manual before you order.

Why does a Daikin show AJ after the indoor board was replaced?

SiUS281811EA's AJ flowchart asks whether the indoor PCB was replaced with a spare and whether the capacity setting adaptor was installed. If the adaptor was not installed, the fix is to install one.

Does this table cover Daikin VRV systems?

Only in part. The meanings here come from SkyAir and wall-mount service manuals. Daikin's general SM-TS3 list covers RA, SkyAir, VRV and other lines with the same code letters, but a VRV system can word or check a code differently. Use your VRV service manual.

Sources

Daikin systems involve line voltage, high-voltage DC on inverter boards, pressurized refrigerant and rotating fans. Service should be performed only by qualified personnel, following the manufacturer's service manual for your model and lockout/tagout procedures.