On Daikin FTK/FTX AXVJU wall-mount units, A5 is freeze-up protection control. In cooling, the indoor coil went below 0°C (32°F). On heat pumps in heating, the same coil sensor read above 61°C (141.8°F). Daikin's DAMA-SM-21-001 service manual (p.60) puts airflow first: blocked or short-circuited air, a dirty filter and a dusty coil. Only after those does it check the indoor heat exchanger thermistor, and then the indoor PCB. If the sensor fails its resistance check, an indoor coil sensor such as 4010117 is the part.
What triggers A5?
| Mode | Condition (DAMA-SM-21-001, p.60) | What the unit does |
|---|---|---|
| Cooling | Indoor heat exchanger temperature below 0°C (32°F) | Freeze-up protection control (operation halt) |
| Heating (heat pump models only) | Indoor heat exchanger thermistor above 61°C (141.8°F) | High pressure control (stop, outdoor fan stop, etc.) |
A5 is the last stage of a control that starts earlier. Section 3.7 (p.41) limits compressor frequency by indoor coil temperature in cooling. Its figure shows five bands, from warmest to coldest: reset, up, keep, dropping and stop. They are separated by lines at 13°C (55.4°F), A, B, C and 0°C:
| Line | °C | °F |
|---|---|---|
| A | 7.0 | 44.6 |
| B | 5.0 | 41.0 |
| C | 3.0 | 37.4 |
| Zone | Control (p.41) |
|---|---|
| Reset | The upper limit of frequency is cancelled |
| Up | The upper limit of frequency increases |
| Keep | The upper limit of frequency is kept |
| Dropping | The upper limit of frequency decreases |
| Stop | "When indoor coil temperature <0°C for >80s, compressor is stopped" |
The figure draws separate rising and falling paths between the lines, so read the exact band edges from the figure. In short, the unit slows the compressor before it stops it. Field practice, not from the manual: a unit that cools poorly and then shows A5 often has an airflow problem rather than a sensor problem.
What does the manual list as causes?
- Indoor short-circuited air
- Clogged air filter of the indoor unit
- Dust accumulation on the indoor heat exchanger
- Defective indoor heat exchanger thermistor
- Defective indoor unit PCB
How do you troubleshoot A5 step by step?
Turn off the power switch before you plug or unplug any connector. The chart on p.60 runs in this order:
- Check the air passage. If the supply air is short-circuiting back to the return, provide a proper air passage.
- Check the air filter. If it is dirty, clean it.
- Check the indoor heat exchanger for dust. If it is dirty, clean it.
- Check No. 01, the indoor heat exchanger thermistor (p.87). If it does not match the thermistor chart, replace it. The manual says: "When replacing the defective thermistor(s), replace the thermistor as ASSY."
- If the thermistor is good, replace the indoor unit PCB (control PCB).
What should the indoor coil thermistor read?
DAMA-SM-21-001 Check No. 01 (p.87) lists the indoor heat exchanger thermistor as resistance type B, 10 kΩ at 25°C (77°F), tolerance ±2%. Unplug the thermistor assembly from the PCB and measure across its pins. Values from the 10 kΩ column of the table:
| Temperature | Resistance |
|---|---|
| −5°C (23°F) | 35.3 kΩ |
| 0°C (32°F) | 28.2 kΩ |
| 10°C (50°F) | 18.3 kΩ |
| 25°C (77°F) | 10.0 kΩ |
| 40°C (104°F) | 5.8 kΩ |
| 50°C (122°F) | 4.1 kΩ |
Both resistance columns on the printed page are headed "Room temperature thermistor". Our reading, not Daikin's wording: the column that reads 10.0 kΩ at 25°C is the type B curve, which the type table on the same page gives to both the room and the indoor heat exchanger thermistors.
Field practice, not from the manual: a sensor that has slipped off its tube, or reads low, can trip A5 when the coil is not actually freezing. Compare the reading with a contact thermometer on the same spot before you buy a board.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Indoor coil sensor | Replace when Check No. 01 fails. The listing does not name a model, so match the part number on your old sensor. | Daikin Applied 4010117 — Indoor Coil Sensor |
| Thermistor | The listing title names FTXB09/FTXB12, a different wall-mount series from the AX models in this manual. Use it only if that is your unit or your old part carries this number. | Daikin Applied 4009585 — Thermistor for FTXB09/FTXB12 |
More sensors: Daikin Parts for VRV Units. If the unit shows C4 (an open or shorted indoor coil thermistor) rather than A5, see Daikin C4, C9, J3, J5, J6, H9 error codes. If the indoor fan is the problem (A6), see Daikin A6 and E7 errors.
Which units this applies to
- Cooling only: FTK09/12/18/24AXVJU with RK09/12/18/24AXVJU
- Heat pump: FTX09/12/18/24AXVJU with RX09/12/18/24AXVJU (the 61°C heating limit applies to heat pump models only)
Scope: All values come from DAMA-SM-21-001 and apply only to the models listed. Other Daikin families have their own code lists (the SkyAir RZR/RZQ manual SiUS281811EA, for example, does not list A5), so check the service manual for your unit.
Before you order
Clean the filter and coil first. If the sensor fails, write down the indoor model and serial number and the part number on the old thermistor. Contact us or email help@totalhvacparts.com and we will match it.
Frequently Asked Questions
What does A5 mean on a Daikin mini split?
On FTK/FTX AXVJU wall-mount units, DAMA-SM-21-001 lists A5 as freeze-up protection control. In cooling the indoor coil was below 0°C (32°F); on heat pumps in heating it was above 61°C (141.8°F).
Is A5 a bad sensor?
Not usually first. The manual checks the air passage, the filter and coil dust before the indoor heat exchanger thermistor, and the indoor PCB last.
What should a Daikin indoor coil thermistor read?
DAMA-SM-21-001 lists it as type B, 10 kΩ at 25°C (77°F), ±2%. It reads 28.2 kΩ at 0°C (32°F) and 18.3 kΩ at 10°C (50°F).
How long does the coil have to be below freezing?
Section 3.7 says the compressor is stopped when the indoor coil temperature is below 0°C for more than 80 seconds.
Sources
- Daikin DAMA-SM-21-001, Service Manual, Inverter Split Wall Mounted Type FTK(X) Series (pp.13, 41, 57, 60, 87)
- Live product titles for the listings above, read from our catalog
Wall-mount units carry line voltage and pressurized refrigerant. Service should be performed only by qualified personnel, following Daikin's service manual and your site's lockout/tagout procedures.