Daikin L8 or L9 Error: Inverter Compressor or Outdoor PCB?

On Daikin SkyAir RZR/RZQ TA outdoor units, L8 is inverter compressor overcurrent and L9 is inverter compressor startup abnormality. Both are detected from the power transistor current, and both charts end at the compressor or the outdoor main PCB (A1P), with a refrigerant check first for L9. Daikin's service manual SiUS281811EA (pp.270-271) checks the compressor lead wires, insulation and windings first, then the power transistors (CHECK 4). If the transistors fail, the outdoor main PCB is the part. If the compressor fails, the manual lists four swing compressor models for these units and no part numbers, so match the number on your old compressor.

What is the difference between L8 and L9?

Code Name (SiUS281811EA) Error decision Supposed causes
L8 (p.270) Inverter compressor overcurrent "Overload in the compressor is detected." Compressor overload; broken wire inside compressor; defective PCB; disconnection of compressor
L9 (p.271) Inverter compressor startup abnormality "Compressor overload during activation" Defective compressor; large pressure difference before starting the compressor; defective PCB

Our reading: L8 is a compressor overload in general, while L9 is an overload during activation (start-up). Both apply to all outdoor units in the manual. If the unit shows E5 (compressor motor lock) instead, see Daikin E5 Error: Inverter Compressor Lock or Bad Outdoor PCB?.

How do you troubleshoot L8?

Turn off the power switch before you plug or unplug any connector. The manual warns that parts may be damaged. The L8 chart (p.270) runs in this order:

  1. Check the compressor lead wires. If they are not normal, replace the compressor lead wires.
  2. Check the compressor insulation. If the insulation resistance of the compressor is 100 kΩ or below, replace the inverter compressor.
  3. Check the windings. If the compressor coils are disconnected (open), replace the inverter compressor.
  4. CHECK 4, power transistor check. If the power transistor is not normal, replace the outdoor main PCB (A1P).
  5. Reconnect the compressor lead wires and restart. If L8 does not come back, continue operation. If it does, the chart ends at "Inspection of the compressor."

How do you troubleshoot L9?

The L9 chart (p.271), as printed:

  1. Check the pressure difference at start. The first box asks: "When operation starts, is the high and low pressure difference greater than 0.2 MPa (29.0 psi)?" A NO leads to "Nonconforming pressure balance. Check the refrigerant system."
  2. On YES: "Disconnect the compressor from the inverter. Use power transistor to check codes based on maintenance codes."
  3. Check the inverter output. The box reads "Unbalanced inverter output voltage (±5 V is normal). After stabilizing the inverter, is the inverter output pressure measurable?" Our reading: it asks whether the inverter output voltage is balanced within ±5 V. On NO, replace the outdoor main PCB (A1P).
  4. Reconnect and power up. If L9 does not blink, reset and restart the unit. If it does, check the compressor for abnormal noise, vibration and operating conditions.

How do you do CHECK 4, the power transistor check?

CHECK 4 (p.295) is done with the power off and all wiring removed from the PCB that carries the power transistors. Measure 10 minutes after power-off. The manual recommends an analog meter but allows a digital meter with a diode check.

Meter + lead to – lead Judgment
Analog, ×1 kΩ range P2 to U, V, W 2 to 15 kΩ
Analog, ×1 kΩ range U, V, W to P2 15 kΩ and above (including ∞)
Analog, ×1 kΩ range N3 to U, V, W 15 kΩ and above (including ∞)
Analog, ×1 kΩ range U, V, W to N3 2 to 15 kΩ
Digital, diode check P2 to U, V, W 1.2 V and over
Digital, diode check U, V, W to P2 0.3 to 0.7 V
Digital, diode check N3 to U, V, W 0.3 to 0.7 V
Digital, diode check U, V, W to N3 1.2 V and over

The manual notes that the higher readings may take some time because of capacitor charge. A reading outside these ranges means the power transistor is not normal, which in both charts leads to the main PCB.

Field practice, not from the manual: test the compressor before you fit a new board. A shorted or grounded compressor can damage a new board as soon as it is powered.

Parts that fix it

Component Role Link
Inverter compressor Replace when the insulation is 100 kΩ or below or a winding is open. The manual lists four hermetically sealed swing compressor models for these units (2YC63ABXDD, 2YC63TXD#A, 2YC90GXD#D and 2YC90FXD#A, by size and TAVJU or TAVJUA version; e.g. pp.16-21) and gives no part numbers. This listing does not name a model, so use it only if it matches the number on your old compressor. Daikin Applied 1703496 — Swing Compressor
Inverter / main PCB Replace when CHECK 4 fails or the inverter output is unbalanced. The manual calls it the outdoor main PCB (A1P). These listings do not name an RZR/RZQ model, so match your old board's number. Daikin Applied 129040J — Inverter PCB Assembly
Daikin Applied 2198390 — Inverter Assembly/control Board

More parts: Daikin Parts for VRV Units. For radiation fin overheat (L4) or the fin thermistor (P4), see Daikin L4 and P4 Errors. For L5, see Daikin L5 and E9 Errors.

Which units this applies to

  • Daikin SkyAir cooling only RZR18/24/30/36/42/48TAVJU and TAVJUA
  • Daikin SkyAir heat pump RZQ18/24/30/36/42/48TAVJU and TAVJUA
  • Paired indoor units in the same manual (FCQ, FHQ, FAQ, FBQ, FTQ)

Scope: All values and steps come from SiUS281811EA. Other Daikin families (VRV, wall-mount FTX/RX) have their own charts and values. Our listings do not name these models.

Before you order

Write down the outdoor model and serial number, the error code and what each check showed, and the part number on the old compressor or board. Contact us or email help@totalhvacparts.com and we will match it.

Frequently Asked Questions

What does L8 mean on a Daikin SkyAir unit?

Inverter compressor overcurrent. SiUS281811EA says the error is detected by current flowing in the power transistor when overload in the compressor is detected (p.270).

What does L9 mean on a Daikin SkyAir unit?

Inverter compressor startup abnormality: compressor overload during activation. Causes are a defective compressor, a large pressure difference before start, or a defective PCB (p.271).

What insulation reading condemns the compressor on L8?

The L8 chart says to replace the inverter compressor if its insulation resistance is 100 kΩ or below, or if its coils are disconnected.

How do I know if it is the board and not the compressor?

Run CHECK 4 on the power transistors (p.295). If the readings fall outside the listed ranges, the charts point to the outdoor main PCB (A1P).

Sources

Inverter outdoor units hold a charge in their capacitors after power-off. Service should be performed only by qualified personnel, following Daikin's service manual and your site's lockout/tagout procedures.