On a Daikin water source heat pump with the MicroTech III controller, a Base Board Communication Failure on the I/O expansion board means the expansion board has lost its link to the main board. Daikin's manuals point to the 12-wire cable between the two boards, the jumper settings and, last, the I/O expansion board itself. On Enfinity units (OM 931-7) the expansion board shows this as yellow off, green flashing, red flashing. The part that fixes a failed board is the MicroTech III WSHP I/O expansion board, 668105711.

What does the I/O expansion board do?

OM 931-7 (p.15) calls the I/O Expansion Module "a field-installed option" and "an extension of the main board". It is the standard control for two-stage equipment and adds outputs for secondary electric heat and multi-speed fans. It also has its own LED annunciator for operational fault conditions. On dual-compressor units it reads circuit 2's high pressure switch, low pressure switch and suction line temperature sensor (Table 11, p.18). The OM 1149-5 manual for SmartSource and vertical stack units lists more jobs (p.9), such as variable speed fan control, waterside economizer control, hot gas reheat and hydronic heat.

Our reading: when the board stops talking, the main board can lose the second compressor, the extra heat stages or fan speeds, depending on how the unit is built.

What do the I/O board LEDs mean on an Enfinity unit?

The expansion board has its own yellow, green and red LEDs. These are OM 931-7 Table 10 (p.17), in priority order. The manual says fault LEDs take precedence over the service test indication.

Mode / fault Yellow Green Red Thermostat output "A"
Invalid jumper configuration Flash Flash Off De-energized
Base board communication failure Off Flash Flash N/A
High pressure #2 fault Off Off Flash De-energized
Low pressure #2 fault Off Off On De-energized
Low suction temp #2 fault Flash Off Off De-energized
Sensor failures (LT2; EWT with boilerless electric heat only) Flash Flash On De-energized
Service test mode enabled Flash Flash Flash Energized
Unoccupied mode On On Off Energized
Occupied, bypass, standby or tenant override Off On Off Energized

Read these LEDs on the expansion board, not the main board. The main board's own table (Table 5) uses some of the same patterns for different faults.

Is it different on SmartSource and vertical stack units?

Yes. OM 1149-5 covers the MicroTech III SmartSource controller with I/O expansion module (GC, GS, GT and VH). It names two separate faults and gives different LED patterns:

Fault (OM 1149-5) Yellow Green Red Page
IO Expansion Communication Fail ON Flash Flash Table 10, p.16
Baseboard Communication Fail Flash OFF Flash p.18

The troubleshooting page (p.17) prints the I/O Expansion Communication Fail with the red LED OFF, not flashing, so the two pages disagree. Confirm on the unit before you rely on either pattern. Table 9 (p.16) gives I/O Expansion Communication Fail priority 1, and Table 7 (p.15) shows it recovers automatically but cannot be reset by the tenant override button or the network.

How do you troubleshoot a communication failure?

OM 931-7 lists the fault but gives no check steps for it. OM 1149-5 does (pp.17-18), and the steps are about the cable, the jumpers and the board:

  1. Check the 12-wire cable. Verify the cable between H5 on the main board and H1 on the I/O expansion board is fully engaged at both ends. The main board's H5 is labeled "Connections to I/O Expansion Board" (p.4).
  2. Check main board jumper JP8. In OM 1149-5, JP8 on the main board is "Shorted when I/O expansion module is required" (Table 5, p.7). For Baseboard Communication Fail the manual says to verify it is shorted.
  3. Check the run jumper on the I/O board. For I/O Expansion Communication Fail (p.17), verify the run/program jumper is in the run position, then try a spare jumper.
  4. Check the jumper settings on both boards. For an Invalid Configuration fault, the manual says to verify the jumper selection on both the main board and the I/O expansion board, and that the main board and I/O expansion board software must be compatible.
  5. Replace the I/O expansion board if the cable, jumpers and run jumper check out.

Field practice, not from the manual: cycle unit power after any cable or jumper change and watch both boards' LEDs through start-up before you order a board.

Which jumpers does the Enfinity expansion board use?

OM 931-7 Table 7 (p.16) sets the Enfinity board's options with jumpers. A wrong jumper gives the Invalid Configuration pattern, not a communication failure, but check them while the cover is off:

Jumper Open Shorted
JP1 compressor options Single compressor (factory default) Dual compressor
JP2 dehumidification None Hot gas / water reheat
JP3 / JP4 secondary heat Both open: none JP3 shorted: supplemental electric; JP4 shorted: boilerless electric
JP5 / JP6 fan speed Both open: single speed (PSC) JP5 shorted: two speed (ECM); JP6 shorted: three speed
JP8 lead compressor Compressor 1 leads Compressor 2 leads (dual compressor only)

What about the circuit 2 faults?

OM 931-7 (pp.17-18) says the expansion board handles circuit 2 high pressure, low pressure and low suction temperature the same way the main board handles circuit 1: "HP, LP, SLTS fault for either circuit one or circuit two, will lockout the individual compressor." The lag compressor runs after the interstage timer, default 300 seconds. Circuit 2 wiring on the board (Table 11, p.18): high pressure switch on HP6, suction line temperature sensor and low pressure switch on H7, entering water temperature sensor on H4.

Parts that fix it

Component Role Link
I/O expansion board Replace when the cable and jumper checks pass and the communication fault stays. The listing's description names Enfinity WSHP with MicroTech III. Daikin Applied 668105711 — Control Board Microtech Iii Wshp I/O Exp Board-Gold
Main board Holds the H5 connector and JP8. Suspect it if a known-good expansion board still cannot communicate. Daikin Applied 668105601 — Control Board Microtech Iii Wshp Main
Suction line temperature sensor The circuit 2 sensor on H7. The title does not name a unit, so match the number on your old sensor. Daikin Applied 910121228 — Suction Line Temp Sensor

For the main board's own LEDs, see Daikin Water Source Heat Pump MicroTech III LED Codes. For a circuit 1 low suction temperature trip, see Daikin Enfinity Low Suction Temp Fault. More parts: Daikin Parts for Daikin Applied.

Which units this applies to

  • Daikin Enfinity water source heat pumps with the MicroTech III unit controller and I/O expansion module (OM 931-7)
  • Daikin SmartSource and vertical stacked water source heat pumps GC, GS, GT and VH with the MicroTech III SmartSource controller and I/O expansion module (OM 1149-5)

Scope: LED patterns and steps come from OM 931-7 (August 2019) and OM 1149-5 (April 2020) and differ between them, so use the manual for your unit. Neither manual gives a part number for the expansion board or the 12-wire cable. The 668105711 listing names Enfinity; for SmartSource units, match the number on your old board.

Before you order

Write down the unit model and serial number, which LEDs are on or flashing on each board, and the part number printed on the old expansion board. Contact us or email help@totalhvacparts.com and we will match it.

Frequently Asked Questions

What does green and red flashing mean on a Daikin heat pump I/O board?

On an Enfinity unit's I/O expansion board, yellow off with green and red flashing is a Base Board Communication Failure (OM 931-7, Table 10). The expansion board has lost its link to the main board.

What causes a MicroTech III I/O expansion communication failure?

OM 1149-5 points to the 12-wire cable between H5 on the main board and H1 on the I/O board, main board jumper JP8, and the run jumper on the I/O board. If those are good, replace the I/O expansion board.

Does an I/O expansion communication fault clear itself?

On SmartSource units, OM 1149-5 Table 7 shows I/O Expansion Communication Fail with auto recovery yes, tenant override reset no and network reset no.

Which faults does the I/O expansion board handle?

On Enfinity units it handles circuit 2 high pressure, low pressure and low suction temperature, entering water temperature with boilerless electric heat, and invalid jumper settings (OM 931-7, Table 10).

Sources

Water source heat pumps carry line voltage, 24 VAC controls and pressurized refrigerant. Service should be performed only by qualified personnel, following Daikin's manual and your site's lockout/tagout procedures.