On a Daikin Enfinity water source heat pump with the MicroTech III controller, Yellow Flash, Green OFF, Red OFF is "Compressor #1 Low Suction Temp (LT1) Fault". The suction line got too cold: below 28°F on standard equipment, or 6.5°F on geothermal. Yellow Flash, Green Flash, Red ON is a different fault: the LT1 sensor itself has failed. Daikin's OM 931-7 and the IM 930-13 troubleshooting table start with water flow, airflow and the loop fluid jumper. The part to replace for a failed sensor is a suction line temperature sensor such as 910121228.
What do the LEDs mean?
| Fault (OM 931-7, Table 5, p.12) | Yellow | Green | Red | Priority (Table 4) |
|---|---|---|---|---|
| Compressor #1 Low Suction Temp (LT1) Fault | Flash | OFF | OFF | 6 |
| Compressor #1 Low Suction Temp (LT1) Sensor Fail Fault | Flash | Flash | ON | 5 |
| Room Temp Sensor Fail (room sensor control only) | Flash | Flash | ON | 7 |
Note that the LT1 sensor fail and the room sensor fail share the same LED pattern in Table 5. On a unit under room sensor control, check both sensors before you order. Our full LED list is in Daikin WSHP MicroTech III LED codes, and the room sensor fault has its own article: Enfinity Room Temp Sensor Fail.
What trips the Low Suction Temp fault?
OM 931-7 (p.7) describes the Suction Line Temperature Sensor (SLTS, labelled LT1 in Tables 1 and 5) as a "temperature sensor on the suction line which provides low temperature protection". Per p.10, the fault trips when "the suction line temperature falls below 28°F on standard equipment (6.5°F on Geothermal)". What the unit does depends on the mode:
| Mode | Action (OM 931-7, p.10) | Recovery |
|---|---|---|
| Heating | Reversing valve de-energizes. Compressor and fan run in cooling for 60 seconds to defrost the water-to-refrigerant coil. | At 36°F (14.5°F on glycol-protected loops); subject to Intelligent Reset |
| Cooling | Compressor stops; fan runs 60 seconds | At 36°F; subject to Intelligent Reset |
| Dehumidification | Compressor stops; fan runs 60 seconds | Clears automatically |
| Fan only | Fan stops | Depends on the previous mode |
Intelligent Reset (p.11) "clears faults the first two times they occur within a 24-hour period". The third time, the unit locks out. The count goes back to zero every 24 hours. Table 3 (p.11) marks heating and cooling Low Suction Temp as auto-recovering (subject to Intelligent Reset), and resettable by the tenant override button or the network. "All Sensor Failures" do not auto-recover, cannot be reset by the tenant override button, and can be reset over the network.
Is the loop fluid jumper set right?
JP3 on the main board sets the loop fluid (OM 931-7, Table 2, p.6):
| JP3 | Setting |
|---|---|
| Open | Water Loop Fluid (water freeze protection - factory default setting) |
| Shorted | Glycol Loop Fluid (Systems with anti-freeze protection) |
The manual warns that a fresh water system must keep JP3 open, or "unit damage and fluid leaks" can occur. The p.10 text names the 6.5°F trip "Geothermal" and the 14.5°F recovery "glycol protected". Linking those values to JP3 is our reading; the manual does not say it in one sentence. If the loop has no antifreeze, JP3 should be open.
How do you troubleshoot Low Suction Temp?
- Read the LEDs. Yellow Flash only is the low temperature fault. Yellow Flash, Green Flash, Red ON is a sensor fail.
- Check JP3 against the loop fluid (above).
- In heating, check water flow. IM 930-13's troubleshooting table for this fault (Table 19) lists "Check water flow (heating operation)" for this fault.
- In cooling, check airflow. The same table lists "Check airflow (cooling operation)". Look at the filter, blower and coil.
- Check operating limits. IM 930-13: "Entering water and air temperatures should be within the operating limits."
- Field practice, not from the manual: check the sensor. LT1 lands on H6-2 (common) and H6-3 (signal) on the main board (OM 931-7, Table 1, p.4). Make sure the sensor is tight on the suction line and insulated, and that the wires are not chafed or shorted. Compare its reading with a contact thermometer on the same spot.
- Field practice, not from the manual: replace the sensor if it reads wrong or gives the sensor fail pattern with good wiring. Suspect the main board only after a known good sensor and good wiring still fault.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Suction line temperature sensor (LT1) | Replace when the sensor reads wrong or shows the sensor fail pattern. The listing title does not name an Enfinity model; match the part number on your old sensor or your unit's parts list. | Daikin Applied 910121228 — Suction Line Temp Sensor |
| MicroTech III WSHP main board | Last step, after a good sensor and good wiring still fault. The listing does not name a model; match the number on your board. | Daikin Applied 668105601 — Control Board Microtech Iii Wshp Main |
More Daikin Applied parts: Daikin Parts for Daikin Applied.
Which units this applies to
- Daikin Enfinity CCH/CCW, VFC/VFW, MHC/MHW and LVC/LVW water source heat pumps with the MicroTech III unit controller (OM 931-7)
- Troubleshooting table quoted from IM 930-13 (Enfinity vertical VFC/VFW 009-070)
Scope: Older McQuay units with the Mark IV board use different LEDs; see McQuay Mark IV LEDs. Each Enfinity model has its own IM manual; check yours for limits.
Before you order
Note the unit model and serial number, the LED pattern, the JP3 setting and the part number on the old sensor. Contact us or email help@totalhvacparts.com to match the sensor.
Frequently Asked Questions
What does Yellow Flash, Green OFF, Red OFF mean on a Daikin Enfinity?
OM 931-7 Table 5 lists it as Compressor #1 Low Suction Temp (LT1) Fault. The suction line went below 28°F on standard equipment, or 6.5°F on geothermal.
Why does my Enfinity lock out after the third freeze fault?
Intelligent Reset clears the first two occurrences in 24 hours. On the third, the unit locks out until it is reset; OM 931-7 Table 3 marks this fault as resettable by the tenant override button or the network.
What sets the geothermal or glycol freeze point?
JP3: open is water loop fluid (factory default), shorted is glycol loop fluid. Systems without antifreeze must keep JP3 open.
Where does the suction temperature sensor connect?
OM 931-7 Table 1 lists LT1 at H6-2 (common) and H6-3 (signal) on the MicroTech III main board.
Sources
- Daikin Applied OM 931-7 (August 2019), MicroTech III Unit Controller for Water Source Heat Pump Units (pp.4, 6-7, 10-12)
- Daikin Applied IM 930-13 (January 2021), Enfinity Vertical Water Source Heat Pumps VFC/VFW 009-070, troubleshooting tables
- Live product titles for the listings above, read from our catalog
Water source heat pumps carry line voltage and pressurized refrigerant. Service should be performed only by qualified personnel, following the Daikin Applied manuals for your unit and your site's lockout/tagout procedures.