On a Daikin Enfinity water source heat pump with the MicroTech III unit controller, "Room Temp Sensor Fail" shows as Yellow Flash, Green Flash, Red ON and only applies when the unit is set for room sensor control. Daikin Applied's OM 931-7 lists the LED pattern and the board terminals, and IM 930-13 lists the wall sensors by part number, including the 4-button digitally adjustable display sensor 910152147. Check the jumper setting, the return air sensor and the sensor wiring first; replace the wall sensor if a known good sensor clears the fault.
What does the LED pattern mean?
| Fault (OM 931-7) | LED pattern (Table 5, p. 12) | Priority (Table 4, p. 12) |
|---|---|---|
| Room Temp Sensor Fail (Room Sensor Control Only) | Yellow Flash, Green Flash, Red ON | Level 7 |
OM 931-7 Table 3 (p. 11) marks "All Sensor Failures" as No for Auto Recovery, No for Tenant Override Button Reset and Yes for Network Reset. For the full LED table, see our article on Daikin WSHP MicroTech III LED codes.
Is the unit set for a room sensor or a thermostat?
The fault only applies under room sensor control, and that is set by a jumper on the main board (OM 931-7, p. 6):
| Jumper | Open | Shorted |
|---|---|---|
| JP6 | Thermostat control | Room sensor control |
| JP5 (setpoint adjust range) | Short range: -3 to +3 ºF (-1.67 to +1.67 ºC) | Long range: 55 to 95 ºF (12.78 to 35 ºC) |
If the job uses a thermostat but JP6 is shorted, the board looks for a room sensor that is not there. JP5 sets the room sensor setpoint potentiometer range, so check it matches how your sensor is meant to adjust the setpoint (our reading, not a manual instruction).
Where does the sensor connect?
| Terminal (OM 931-7, p. 4) | Function |
|---|---|
| H9-1 | Room Temp Sensor & Tenant Override – Signal |
| H9-2 | Room Temp Sensor & Tenant Override – Common |
| TB1-1 | Room Sensor – Status LED Output |
| TB1-2 | Room Sensor – Fan Mode & Unit Mode Switches |
| TB1-3 | Room Sensor – Setpoint Adjust Potentiometer |
| TB1-4 | Room Sensor – Room Temp Sensor & Tenant Override |
| TB1-5 | Room Sensor – DC Signal Common |
How do you check a Room Temp Sensor Fail?
- Confirm the LED pattern is Yellow Flash, Green Flash, Red ON.
- Check JP6. Shorted means room sensor control. If the unit should be on a thermostat, the jumper is wrong.
- Check for a return air sensor. OM 931-7 (p. 19) and IM 930-13 (p. 33) warn that the return air temperature (RAT) sensor must not be installed when a wall-mounted room sensor is connected: "A wall-mounted room temperature sensor and the return air temperature sensor must not be connected simultaneously or the unit will not operate properly."
- Field practice, not from the manual: check the wiring. Follow the sensor cable to TB1 and confirm TB1-4 (sensor) and TB1-5 (common) are tight and not shorted to each other or to ground.
- Field practice, not from the manual: isolate the sensor. If the cable checks good, swap in a known good sensor of the same type. If the fault clears, replace the wall sensor.
- Field practice, not from the manual: board last. If a known good sensor and good wiring still give the fault, suspect the main board.
Which wall sensors does Daikin list?
IM 930-13 (Enfinity vertical VFC/VFW 009-070) shows these room sensor accessories, among others (Figs. 39-41, p. 32):
| IM 930-13 description | Part number | Connection shown |
|---|---|---|
| Digitally Adjustable Display Sensor (4-button), Fig. 40 | 910152147 | MicroTech III controller terminals TB1, TB2 and TB3 |
| Digitally Adjustable Display Sensor (6-button), Fig. 39 | 910121754 | TB1, TB2 and TB3 |
| Cool/Warm Adjustable Sensor | 910171464 | MicroTech III controller terminals TB1 |
Parts that fix it
| Component | Role | Link |
|---|---|---|
| 4-button digitally adjustable display sensor | Listed by part number in IM 930-13. | Daikin Applied 910152147 — Sensor 24V W/Override Reset 55-95F |
| 6-button digitally adjustable display sensor | Listed by part number in IM 930-13. | Daikin Applied 910121754 — Tstat,room Digital Adj Temp & H |
| Cool/warm adjustable sensor | Listed by part number in IM 930-13. | Daikin Applied 910171464 — Room Sensor, Microtech Iii |
| MicroTech III WSHP main board | Only after a known good sensor and wiring still show the fault. The listing title does not name a model; match the part number on your old part or your unit's parts list. | Daikin Applied 668105601 — Control Board Microtech Iii Wshp Main |
Which units this applies to
- LED pattern, jumpers and terminals: Daikin Enfinity CCH/CCW, VFC/VFW, MHC/MHW and LVC/LVW with the MicroTech III unit controller (OM 931-7).
- Sensor part numbers: Enfinity vertical VFC/VFW 009-070 (IM 930-13).
Scope: The sensor part numbers come from IM 930-13 for VFC/VFW units. Other Enfinity models have their own IM manuals; check the accessory list there before ordering.
Before you order
Note the unit model and serial number, the part number on the back of the old wall sensor, and the JP5 and JP6 settings. Contact us or email help@totalhvacparts.com and we will help confirm the sensor.
Frequently Asked Questions
What does Yellow Flash, Green Flash, Red ON mean on a Daikin Enfinity heat pump?
OM 931-7 Table 5 lists it as Room Temp Sensor Fail, which applies under room sensor control only.
Why does my Enfinity unit show a room sensor fault with a thermostat installed?
Check JP6. OM 931-7 says JP6 open is thermostat control and shorted is room sensor control.
Can I use a return air sensor and a wall sensor together?
No. OM 931-7 and IM 930-13 warn that the return air sensor must not be installed when a wall-mounted room sensor is connected.
Which wall sensor is 910152147?
IM 930-13 (Fig. 40) shows 910152147 as the Digitally Adjustable Display Sensor (4-button) for Enfinity VFC/VFW units; Fig. 39 shows 910121754 as the 6-button version.
Sources
- Daikin Applied OM 931-7 (August 2019), MicroTech III Unit Controller for Water Source Heat Pump Units (pp. 4, 6, 11-12, 19)
- Daikin Applied IM 930-13 (January 2021), Enfinity Vertical Water Source Heat Pumps VFC/VFW 009-070, Installation and Maintenance Manual (pp. 32-33)
- Live product titles for the listings above, read from our catalog
Water source heat pumps carry line voltage, pressurized refrigerant and moving fans. Service should be performed only by qualified personnel, following the Daikin Applied manuals for your unit and your site's lockout/tagout procedures.