"Evaporator – Transducer Or Leaving Liquid Probe" on a York YK means the control center no longer believes its evaporator pressure transducer and its leaving chilled liquid temperature sensor at the same time. York form 160.54-O1 (YK through Style G OptiView operation guide) says the panel compares the two, and shuts the chiller down if they disagree for 10 minutes. It is a safety shutdown, so you reset it at the panel. The parts to check are the evaporator pressure transducer (025-28678-112 on YK Mod E, F and G) and the leaving chilled liquid sensor.
How does the York YK decide the transducer or probe is bad?
Form 160.54-O1 explains the test. The control center converts evaporator pressure into a saturated temperature. It then subtracts that from the leaving chilled liquid temperature. In a healthy chiller the leaving water is a little warmer than the refrigerant boiling in the shell.
| Item | Value (160.54-O1) |
|---|---|
| Allowed difference (leaving chilled liquid minus evaporator saturation) | -2.5°F to +25.0°F |
| Time outside that band before shutdown | 10 continuous minutes |
| Steam turbine drives | Check bypassed for the first 20 minutes of operation |
| Type | Safety shutdown |
| Reset | Move the Compressor Switch to Stop-Reset (O), then start |
A negative difference larger than 2.5°F means the water reads colder than the refrigerant can be. A difference above 25°F means the refrigerant reads far colder than the water. Either way, the panel treats one of the two signals as suspect. That reading is our explanation of the rule, not York wording, so prove it with gauges and a thermometer before you buy a sensor.
What other YK messages point at the same parts?
- Warning – Condenser or Evaporator XDCR Error: the evaporator pressure transducer reads higher than the condenser pressure transducer. That cannot happen with a healthy pair, so one of them is wrong.
- XX.X on the display: the manual says a value the panel cannot calculate is shown with Xs. For example, oil pressure shows XX.X if either transducer used to calculate it is out of range.
- < or > beside a value: the reading is at the minimum or maximum of its input range.
Table 1 of form 160.54-O1 lists the input ranges:
| Input | Display range (160.54-O1, Table 1) |
|---|---|
| Leaving chilled liquid temperature | 0.0 to 82.0°F (-17.7 to 27.7°C) |
| Evaporator pressure, R-134a, R-513A, R-1234ze | 5.5 to 77.4 psig (37.9 to 533.7 kPag) |
| Evaporator pressure, R-22 (water) | 49.4 to 128.8 psig (340.6 to 888.2 kPag) |
| Condenser pressure (R-22, R-134a, R-513A, R-1234ze) | 0.0 to 315.0 psig (low value 7.5 psig with Flash Memory Card C.MLM.01.04 and later) |
How do you find which sensor is wrong?
- Write down the readings. From the Evaporator screen, record evaporator pressure, evaporator saturation temperature, and return and leaving chilled liquid temperature.
- Check the water side. Compare the leaving chilled liquid reading with a calibrated thermometer or gauge in the leaving water line.
- Check the refrigerant side. Put a calibrated gauge on the evaporator and compare with the panel's evaporator pressure.
- Look for range symbols. A value pinned at the end of its Table 1 range, or shown with < or >, points to an open or shorted sensor or wiring.
- Check the XDCR warning. If "Condenser or Evaporator XDCR Error" is also logged, compare both transducers against gauges.
- Inspect plugs and wiring at the transducer and sensor before you replace anything.
- Replace the part that disagrees with your instrument, then reset with the Compressor Switch at Stop-Reset (O).
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Evaporator pressure transducer | Evaporator pressure for the saturation calculation. Listed for YK Mod E, F and G, YD Mod A–C, YKEP Mod A, YR, YS Style E and YST. | York 025-28678-112 Transducer, Pressure, Evaporator | OEM Chiller Part |
| Pressure transducer | Listed for YK Mod A through G and YS Style A–D. Check whether your evaporator or condenser transducer carries this number. | York 025-28678-001 Transducer, Pressure | OEM Chiller Part |
| Evaporator temperature sensor | Listed for YK Mod G, YD Mod A–C, YKEP Mod A and YMC2. Confirm it matches the leaving chilled liquid sensor on your unit. | York 025-41904-000 Sensor, Temperature (Evaporator) | OEM Chiller Part |
| Evaporator pressure transducer, Mod H | Listed for YK Mod H, CYK Style G and YMC2. Mod H is outside 160.54-O1. | York 025-28678-115 Transducer, Pressure (Evaporator) | OEM Chiller Part |
| All sensors | Temperature sensors and transducers | York Chiller Sensors, Thermistors & Transducers |
If the chiller is actually tripping on low evaporator pressure rather than this message, see York YK 'Evaporator - Low Pressure' Shutdown: Causes and Checks.
Which units this applies to
- YK Mod E, YK Mod F and YK Mod G: message from 160.54-O1; 025-28678-112 listed.
- YK Mod C and YK Mod D: message from 160.54-O1; 025-28678-001 is the transducer listed for these Mods.
- YK Mod H: 025-28678-115 listed; check the manual for your panel.
Scope: The detection rule, ranges and reset are from York form 160.54-O1, YK Mod C through Mod G with OptiView. Part roles and fits are from the product listings, which cite York renewal parts manuals. Transducer ranges differ by refrigerant and position, so always match the part number printed on the old part.
Before you order
Note the chiller model, Mod letter, serial number and refrigerant, and read the part number off the transducer or sensor you are replacing. To confirm fit, contact us or email help@totalhvacparts.com.
Frequently Asked Questions
What does Evaporator – Transducer Or Leaving Liquid Probe mean on a York YK?
The leaving chilled liquid temperature minus evaporator saturation temperature stayed outside -2.5°F to +25.0°F for 10 continuous minutes, so the panel suspects the evaporator pressure transducer or the leaving liquid sensor (160.54-O1).
How do you reset Evaporator – Transducer Or Leaving Liquid Probe?
It is a safety shutdown. Fix the cause, then move the Compressor Switch to Stop-Reset (O) before restarting.
What is Condenser or Evaporator XDCR Error on a York YK?
A warning that the evaporator pressure transducer reads higher than the condenser pressure transducer, which means one of them is faulty.
Which evaporator transducer fits a York YK Mod G?
York renewal parts data lists 025-28678-112 for YK Mod E, F and G. Match the part number on your old transducer.