York YK 'Vane Motor Switch Open' Won't Start: PRV Actuator Checks Before You Replace 375-49340-101

"Vane Motor Switch Open" on a York YK is a start inhibit: the chiller will not start because the pre-rotation vanes (PRV) are not fully closed. York form 160.54-O1 (YK through Style G OptiView operation guide) says exactly that. The vane motor switch (VMS) closes only when the vanes are shut. If the vanes are stuck open, or the actuator never drives them closed, or the switch never makes, the chiller sits there. When the actuator is at fault, the YK replacement is a PRV actuator kit, 375-49340-101 or 375-49340-103; match the part number on your old kit.

What does the vane motor switch do on a York YK?

Form 160.54-O1 describes the vanes and their drive:

  • The pre-rotation vanes sit at the entrance to the compressor impeller and match capacity to load, from wide open at full load to completely closed at minimum load.
  • An electric motor mounted outside the compressor housing drives them through a lever arm.
  • The vane motor switch closes when the vanes are fully closed. The panel uses it to confirm the vanes are shut before a start and during shutdown.

Common Slots table entry 1280, "Pre-Rotation Vanes: Is Motor Switch Closed", lets you trend the switch.

Which YK messages involve the vanes?

Message Meaning (160.54-O1)
Vane Motor Switch Open Start inhibit. The chiller is inhibited from starting because the pre-rotation vanes are not fully closed.
Vanes Closing Before Shutdown Status during a soft shutdown. The run signal is removed when the VMS closes or after 3.5 minutes, whichever comes first, then System Coastdown follows.
Warning – Vanes Uncalibrated – Fixed Speed The compressor motor VSD is running in fixed speed (full speed) mode because PRV calibration has not been done.
Warning – Vanes Uncalibrated Hot gas bypass is enabled, but the PRV calibration procedure has not been performed.
Warning – Condenser – High Pressure Limit / Evaporator – Low Pressure Limit While these conditions are in effect, the pre-rotation vanes are inhibited from further opening.

The soft shutdown note matters for diagnosis. If the vanes never close, the panel still stops the compressor after 3.5 minutes, but the next start will be blocked by Vane Motor Switch Open.

How do you check a stuck vane or bad actuator?

  1. Confirm the message. Check the status line and history. Trend slot 1280 to see whether the switch ever closes.
  2. Look at the vane position. The PRV Calibration screen has Pre-rotation Vanes Opening and Closing LEDs. In software C.OPT.01.23.307 and later it also shows Pre-rotation Vanes Voltage, the feedback from the PRV potentiometer when it connects directly to the 031-02430 microboard (VGD, VSD Modbus and hot gas bypass applications).
  3. Watch the linkage. With the chiller safe to observe, check that the actuator moves the lever arm and the vanes follow. A motor that runs while the vanes do not move points to the linkage.
  4. Check the switch. If the vanes are fully closed but slot 1280 still reads open, check the switch and its wiring.
  5. Replace the actuator kit if it fails. Match the kit to the compressor, then recalibrate.
  6. Recalibrate the vanes. PRV calibration needs a SERVICE login on the PRV Calibration screen (Start Calibration, then follow the Calibration Messages). On VSD chillers, the VSD Tuning screen will not accept Auto until the pre-rotation vanes calibration has been successfully performed, and on VGD units the PRV position reads XXX until calibration is done. Service details are in York form 160.54-M1.

Parts that fix it

Component Role Link
PRV actuator and wiring kit (-101) Replaces the vane actuator. Listed for YK Mod F, G and H, YKEP Mod A and YST. York 375-49340-101 ACTUATOR/WIRING, PRV Kit | OEM Chiller Part
PRV actuator and wiring kit (-103) Listed for YK Mod F, G and H, YD Mod A–D, CYK and YST. Match the part number on your old kit. York 375-49340-103 ACTUATOR/WIRING, PRV Kit | OEM Chiller Part
Actuator wiring (-105) Listed for YK Mod F, G and H, YD, CYK, YKEP Mod A and YST. York 375-49340-105 Wiring, Actuator | OEM Chiller Part
YK parts Browse parts by chiller line York YK Centrifugal Chiller Parts

Not sure which kit matches your compressor? See York YK PRV Actuator Kit: 375-49340-101, -103 or -105?

Which units this applies to

  • YK Mod F and YK Mod G: messages from 160.54-O1; all three kits listed.
  • YK Mod H: kits listed; Mod H messages are outside 160.54-O1.
  • YK Mod C, Mod D and Mod E: messages from 160.54-O1, but these kits are not listed for them. Read the part number on your actuator.

Scope: Messages, the 3.5-minute soft-shutdown limit and the calibration screen are from York form 160.54-O1, YK Mod C through Mod G with OptiView. Kit fits come from the product listings, which cite York renewal parts manuals. Calibration steps are in form 160.54-M1, which we did not use here.

Before you order

Note the chiller model, Mod letter and serial number, the compressor code, and the part number on the existing actuator. To confirm the right kit, contact us or email help@totalhvacparts.com.

Frequently Asked Questions

What does Vane Motor Switch Open mean on a York YK?

It is a start inhibit. Form 160.54-O1 says the chiller is inhibited from starting because the pre-rotation vanes are not fully closed.

How long does a York YK wait for the vanes to close on shutdown?

During a soft shutdown the run signal is removed when the vane motor switch closes or after 3.5 minutes, whichever comes first.

Do you have to calibrate the vanes after replacing the PRV actuator?

Plan on it. 160.54-O1 shows Vanes Uncalibrated warnings until the PRV calibration is done, and on VSD chillers the VSD Tuning screen will not accept Auto until calibration succeeds. The full procedure is in York form 160.54-M1.

Which PRV actuator kit fits a York YK Mod G?

Both 375-49340-101 and 375-49340-103 are listed for YK Mod G. The listings do not say which one your unit uses, so match the part number on your old actuator kit.

Sources

Chiller control panels carry line voltage and 24 VAC control power. Service should be performed only by qualified personnel, following York's manual for your unit and your facility's lockout/tagout procedures.