When a York YK won't start and shows "Oil – Low Temperature" or "Oil – Low Temperature Differential", the oil in the sump is too cold, or not warm enough above condenser saturation temperature, for a safe start. York form 160.54-O1 (YK through Style G OptiView operation guide) gives the limits: 55°F for oil temperature, and 30°F or 40°F above condenser saturation depending on how long the chiller has been off. If the oil never warms up while the chiller sits, check the oil heater; our 1000 W immersion heater listing, 025-34523-000, cites York parts data for YK Mod A, B, C, F, G and H, so confirm it matches the part number on your old heater. If the reading looks wrong, check the oil temperature sensor, 025-28936-000.
What do the York YK oil temperature messages mean?
Section 3 (Display Messages) of form 160.54-O1 defines three oil temperature messages:
| Message | What trips it (160.54-O1) | Type and restart |
|---|---|---|
| Oil – Low Temperature | Oil temperature has dropped below 55°F. | Cycling shutdown. Restarts automatically when oil rises above 55.0°F and also meets the differential rule below. |
| Oil – Low Temperature Differential | Start is blocked if: the chiller has been off 30 minutes or less and oil temperature minus condenser saturation temperature is under 30°F; or it has been off more than 30 minutes and that difference is under 40°F; or power was just restored after a power failure and the difference is under 40°F. | Cycling. Restarts automatically when the conditions are met. |
| Oil – High Temperature | Oil temperature, as sensed by the Oil Temperature Transmitter, above 180.0°F (82.2°C). | Safety shutdown. Restart after oil falls below 180.0°F and the Compressor Switch is moved to Stop-Reset (O). |
Timing depends on software. In C.OPT.01.23.307 and later, the low temperature differential is checked only while the chiller is stopped. Earlier versions also check it during the first 10 seconds of prelube.
How does the oil heater fit in?
The oil heater is what lifts the sump temperature while the chiller is off, so it is the first part to suspect when the differential never clears. Form 160.54-O1 says the oil-to-condenser temperature differential shown on the Oil Sump screen "is used in the control of the oil heater". The Oil Sump screen also has an Oil Heater LED (variable speed oil pump units), which "Indicates whether the oil heater output is energized".
The manual's trending slots let you log the heater. Slot 1537 is "Oil: Sump Temperature", slot 1541 is "Oil Heater: Is Control Enabled" and slot 1542 is "Oil Heater: Is Heater On". Trend slot 1542 against slot 1537 over a few hours with the chiller off. If the heater is called on and the oil temperature does not move, the heater element or its circuit is the likely problem.
How do you check whether it's the heater or the sensor?
- Read the message. Low Temperature or Low Temperature Differential points at a cold sump. High Temperature is a safety shutdown and needs Stop-Reset.
- Compare oil and condenser saturation. On the Oil Sump screen, read the oil-to-condenser differential. Compare it with the 30°F and 40°F limits above.
- Trend the heater. Log slots 1541, 1542 and 1537. Heater on with no temperature rise means no heat is getting into the oil.
- Check the heater circuit. With the panel locked out, check the heater fuse and wiring per your wiring diagram, and check the element for continuity. The listed heater is 1000 W at 120 V.
- Sanity-check the sensor. Form 160.54-O1, Table 1, gives the oil temperature display range as 31.8 to 226.3°F (-0.1 to 107.9°C). Readings outside the range show with a < or > symbol. A reading pinned at either end, or one that disagrees with a contact thermometer on the sump, points at the sensor or its wiring.
- Replace the failed part. Match the part number on the old heater or sensor before you order.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Immersion heater, 1000 W, 120 V | Listed in York renewal parts data for YK Mod A, B, C, F, G and H (160.75-RP1, 160.73-RP2/RP4, 160.49-RP5, 160.76-RP1). Confirm it matches the heater on your sump by its part number. | York 025-34523-000 Heater, Immersion (1000 W, 120) | OEM Chiller Part |
| Oil temperature sensor | Reports oil temperature to the control center. Listed for YK Mod A through G, YD Mod A–B, YT Mod H–J and others. | York 025-28936-000 Sensor, Temperature (Discharge / Oil) | OEM Chiller Part |
| Heaters by chiller | Other York chiller heaters | York Chiller Heaters |
| YK parts | Browse parts by chiller line | York YK Centrifugal Chiller Parts |
If the chiller starts but trips on low oil pressure instead, see York Chiller Oil Low Differential Pressure Shutdown: What to Check.
Which units this applies to
- YK Mod C, YK Mod F and YK Mod G: messages from 160.54-O1; heater and oil sensor both listed.
- YK Mod D and YK Mod E: messages from 160.54-O1; the oil sensor is listed, the heater listing does not include these Mods.
- YK Mod H: heater listed; Mod H messages are outside 160.54-O1, so use your panel's manual.
Scope: Message definitions, limits and slot numbers are from York form 160.54-O1 for YK Mod C through Mod G with the OptiView panel. The manual does not publish the heater's on/off setpoints, so this article does not give any. Fits come from the product listings, which cite York renewal parts manuals.
Before you order
Send the chiller model, Mod letter and serial number, plus the part number and voltage on the old heater or sensor. To confirm fit, contact us or email help@totalhvacparts.com.
Frequently Asked Questions
Why won't my York YK start with Oil – Low Temperature Differential?
The oil is not warm enough above condenser saturation temperature. Form 160.54-O1 requires at least 30°F if the chiller has been off 30 minutes or less, and 40°F if it has been off longer or after a power failure.
Does Oil – Low Temperature lock out a York YK?
No. It is a cycling shutdown that restarts automatically once oil is above 55.0°F and the differential rule is met.
What temperature trips Oil – High Temperature on a York YK?
Above 180.0°F (82.2°C), as sensed by the Oil Temperature Transmitter. It is a safety shutdown; restart needs the Compressor Switch moved to Stop-Reset (O) after the oil cools below 180.0°F.
How can I tell if the York YK oil heater is working?
Watch the Oil Heater LED on the Oil Sump screen (variable speed oil pump units) or trend slots 1542 (Is Heater On) and 1537 (Sump Temperature). Heater on with no rise in oil temperature points to the heater or its circuit.
Sources
- York form 160.54-O1, YK through Style G OptiView Control Center operation guide (YK Mod C, D, E, F and G) (Section 3 Display Messages: Oil – Low Temperature, Oil – Low Temperature Differential, Oil – High Temperature; Oil Sump screen; Table 1 analog input ranges; Common Slots table)
- Live product titles and fit data for York 025-34523-000 and 025-28936-000, as shown on each product page
Chiller control panels carry line voltage and 24 VAC control power. Service should be performed only by qualified personnel, following York's manual for your unit and your facility's lockout/tagout procedures.