WaterFurnace E82 ASB Sensor Problem on R-454B Units: Checking the 19P688-01 Refrigerant Sensor

On a WaterFurnace R-454B unit, E82 "ASB Sensor Problem" means the refrigerant gas sensor has lost communication with the ASB board or has an internal error. It is a sensor or wiring fault, not a leak. A leak sets E81 "ASB Leak Detected" instead. The 5 Series 500A11 O&M (OMW5-0016W) and the 7 Series 700A11 O&M (OMW7-0018W) both list the sensor as 19P688-01 — WaterFurnace Danfoss A2L Sensor.

What are E81 and E82 on a WaterFurnace R-454B unit?

These units carry a refrigerant detection sensor. The manuals describe the ASB board as monitoring the refrigerant sensor and reporting a leak to the ABC (Aurora Base Control) board. The two ASB codes in the Aurora fault table are:

Code Name Lockout Reset Description (OMW5-0016W, p.34)
E81 ASB Leak Detected Yes Auto "High refrigerant gas concentration detected by ASB and gas sensor."
E82 ASB Sensor Problem Yes Auto "Gas sensor has issued a fault, lost communication, internal error"

In the 5 Series table both codes are marked as lockouts with an automatic reset. The 7 Series manual (OMW7-0018W) describes them in its mitigation fault code section rather than in the main table. It says E82 "occurs when an ASB has a sensor that has lost communication, has a sensor health problem," or has an internal error.

What does the unit do on a leak alarm?

Both manuals describe the same mitigation. The sensor detects a leak when the refrigerant concentration exceeds 13% of the LFL (lower flammability limit). The ASB tells the ABC, and the ABC turns off the compressor, auxiliary heat and pump outputs. The blower comes on and keeps running until the ABC no longer reports the fault.

So a unit with the blower running and no heating or cooling may be in mitigation. Read the code before you touch the sensor. If it is E81, treat it as a refrigerant leak. Ventilate, find and repair the leak following the A2L procedures in the manual. Do not replace the sensor to clear an E81.

How do you read the ASB and sensor LEDs?

OMW5-0016W (p.31) gives the LED meanings for the ASB board and for the RDS (refrigeration detection sensor):

Board LED Pattern Meaning
ASB Green status Fast flash ABC loss communication
ASB Red fault Slow flash Alarm
ASB Red fault Fast flash Sensor loss communication
RDS Red fault Solid Alarm state
RDS Red fault Blinking Sensor fault
RDS Green status Solid Power up / self test
RDS Green status Blinking Normal operation

These LEDs split E82 into two paths. A blinking red LED on the sensor points at the sensor itself. A fast-flashing red LED on the ASB points at the link between the sensor and the board.

How do you check an E82?

  1. Confirm the code. Read the fault on the thermostat or the Aurora tools and write it down. E81 is a leak. E82 is a sensor or communication problem.
  2. Isolate power before opening the unit. Apply your lockout/tagout procedure. These units contain flammable refrigerant; follow the A2L warnings in your O&M.
  3. Read the sensor LEDs. Green blinking is normal operation. Red blinking is a sensor fault. Solid green right after power-up is the self test.
  4. Read the ASB LEDs. Red fast flash means the ASB has lost the sensor. Green fast flash means the ASB has lost the ABC, which is a communication problem on the board side, not the sensor.
  5. Check the sensor harness. On the 7 Series 700A11, the parts list names the RDS/ASB harness as 11P991-02. Our listing title for it reads "Harness-ASB P1-30in To Danfoss Sensor". Look for loose plugs, pinched or damaged wire, and seat both ends.
  6. Replace the sensor if it reports a fault. OMW5-0016W says the device is "capable of determining it's specified end-of-life". If the sensor shows a fault with a good harness and good connections, replace it. The manuals say refrigerant sensors "shall only be replaced" with sensors specified by the appliance manufacturer. Both parts lists specify 19P688-01.
  7. Confirm the result. After power-up the sensor should go from solid green (self test) to blinking green (normal). The OMW5-0016W table lists an automatic reset for E82, so it should clear once the sensor reports normally.

Field practice, not from the manual: if E82 comes back intermittently, note when it happens and check the harness routing for chafe points before ordering a second sensor.

Parts that fix it

Component Role Link
Refrigerant detection sensor Primary fix for an E82 sensor fault. Listed as 19P688-01 in OMW5-0016W ("ASB Sensor") and OMW7-0018W ("Refrigerant Detection Sensor"). The OMW5-0016W sensor drawing names Danfoss DST G54B. 19P688-01 — WaterFurnace Danfoss A2L Sensor
Sensor harness Fix for a sensor loss-of-communication path. Listed as the RDS/ASB harness in the 7 Series 700A11 parts list. 11P991-02 — WaterFurnace Harness-ASB P1-30in To Danfoss Sensor
Other WaterFurnace parts Boards, thermistors and harnesses by part number WaterFurnace Replacement Parts

The ASB board itself is 17P599-01 in both parts lists. It is not listed on our site at the moment, so contact us if the board is the suspect.

Which units this applies to

  • 5 Series 500A11, R-454B, 60 Hz (OMW5-0016W), sizes 018 through 072. The parts list shows the ASB sensor 19P688-01 for every size.
  • 7 Series 700A11, R-454B, 60 Hz (OMW7-0018W), sizes 024 through 060.
  • Other R-454B WaterFurnace lines may use the same ASB and sensor. Our listings for 19P688-01 and 11P991-02 also show a confirmed fit on unit V5AV060BS3AG1DTRBANW212SSS.

Scope: Codes, LEDs, mitigation and part numbers are from WaterFurnace OMW5-0016W and OMW7-0018W, the R-454B manuals. If your unit is on another refrigerant or another WaterFurnace line, use the manual for your model.

Before you order

Read the model and serial number off the nameplate, and the part number off the old sensor and harness. Note which LED pattern you saw on the sensor and the ASB. To confirm fit, contact us or email help@totalhvacparts.com. For other Aurora codes, see WaterFurnace Aurora Base Control fault codes and how to reset a WaterFurnace lockout.

Frequently Asked Questions

What does E82 mean on a WaterFurnace?

E82 is "ASB Sensor Problem". The refrigerant gas sensor has issued a fault, lost communication with the ASB board, or has an internal error (OMW5-0016W and OMW7-0018W).

Is E82 a refrigerant leak?

No. A leak sets E81, "ASB Leak Detected". E82 is a sensor or communication problem. Read the code before you act.

Why is my WaterFurnace blower running with no heat or cooling?

On R-454B units with a refrigerant sensor, a leak alarm turns off the compressor, auxiliary heat and pump outputs and runs the blower until the fault clears. Check for E81.

Can I use any A2L refrigerant sensor?

No. WaterFurnace says refrigerant sensors shall only be replaced with sensors specified by the appliance manufacturer. Both parts lists specify 19P688-01.

What part number is the WaterFurnace ASB sensor?

19P688-01 in the 5 Series 500A11 and 7 Series 700A11 R-454B parts lists. The ASB board is 17P599-01.

Sources

WaterFurnace heat pumps involve line voltage, 24 V control circuits, pressurized flammable (A2L) refrigerant on R-454B units, and rotating equipment. Service should be performed only by qualified personnel, following the manufacturer's manual for your unit and your facility's lockout/tagout procedures.