On Daikin FTK/FTX AX wall-mount systems, L3 means electrical box temperature rise. With the compressor off, the outdoor unit's radiation fin got hotter than its limit. DAMA-SM-21-001 (p.81) blames the outdoor fan motor first, then a short, the radiation fin thermistor, a loose connector or the outdoor PCB. Its chart checks the fin temperature and the outdoor fan, then fin dirt and the installation. If the fan check fails, replace the outdoor fan motor. On RK/RX 09 and 12 sizes the manual rates that motor DC, 41 W, 8 poles, and 4017514 is a listing with the same rating. The manual gives no part number, so match the number on your old motor. The 18 and 24 sizes use a 128 W motor that this listing does not match.
When does L3 trip and clear?
The manual (p.81) gives three temperatures for the radiation fin, all read with the compressor off:
- A: above this, L3 is set.
- B: below this, the error clears and the outdoor fan stops.
- C: above this, the outdoor fan starts to cool the electrical components.
| Size | A | B | C |
|---|---|---|---|
| 09 | 82.0°C (179.6°F) | 65.0°C (149.0°F) | 70°C (158.0°F) |
| 12 | 82.0°C (179.6°F) | 65.0°C (149.0°F) | 70.0°C (158.0°F) |
| 18 | 90.0°C (194.0°F) | 64.0°C (147.2°F) | 81.0°C (177.8°F) |
| 24 | 90.0°C (194.0°F) | 64.0°C (147.2°F) | 81.0°C (177.8°F) |
So the outdoor fan can run with the compressor off. That is normal cooling of the electrical box, not a fault. L3 is the stage after that, when the fin still gets too hot.
What does the manual list as causes?
- Defective outdoor fan motor
- Short circuit
- Defective radiation fin thermistor
- Disconnection of connector
- Defective outdoor unit PCB
How do you troubleshoot L3 step by step?
Turn off the power switch before you plug or unplug any connector. The chart on p.81 runs in this order:
- Turn the power off, then on, to restart the system.
- If the error comes back or the outdoor fan runs, check the radiation fin temperature. If it is not above A, replace the outdoor unit PCB (main PCB). Our reading: the error was set without a real overheat, so the chart treats the board side as suspect.
- If the fin is above A, or the error did not return, do Check No. 19, the outdoor fan check (p.92). It asks whether the outdoor fan is running. If it is not, and the fan motor lead wire connector is not disconnected, go to Check No. 16. If it is disconnected, reconnect it.
- If the fan check is NG, the chart lists: replace the outdoor fan motor, correct the connectors and fan motor lead wire, and replace the outdoor unit PCB (main PCB).
- If the fan check is OK, look at the radiation fin. If it is dirty, clean it. If it is clean, check the installation with Check No. 17 (p.91).
How do you test the outdoor fan motor (Check No. 16)?
Check No. 16 (p.90) is the rotation pulse check at connector S70 or S71 on the outdoor PCB. It applies to FTK(X)09/12/18/24.
- Set operation off and power off. Disconnect S70 or S71.
- Check 320 VDC between pins 4 and 7. If NG, the PCB is defective: replace the outdoor unit PCB (main PCB).
- Check the 15 VDC control voltage between pins 3 and 4.
- Check the rotation command voltage between pins 2 and 4: 0 to 6.5 VDC. If NG, the Hall IC is defective: replace the outdoor fan motor.
- Keep operation and power off and reconnect the connector.
- Turn the fan one full turn by hand and check for 4 rotation pulses (0 to 15 VDC) on pins 1 and 4.
The manual adds: if steps 2 and 4 are both OK, replace the outdoor unit PCB (main PCB). When the fuse has melted, check the outdoor fan motor for proper function.
What does Check No. 17 look at?
Check No. 17 (p.91) is the installation check. It looks for clearance problems at the air suction and discharge, discharged air short-circuiting back into the unit, a very dirty outdoor heat exchanger, and obstacles or wind blowing against the airflow. It also says the outdoor temperature should be within the operation range. Field practice, not from the manual: an outdoor unit in direct afternoon sun with little clearance can run its electrical box hot even with a good fan.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Outdoor fan motor | Replace when Check No. 19 or Check No. 16 fails at the motor. DAMA-SM-21-001 lists the RK/RX 09 and 12 outdoor fan motors as DC, 41 W output, 8 poles (specifications, pp.16, 18 and 19) and gives no part number. This listing reads DC 280 V, 41 W, 8 poles: a spec match, not a confirmed fit. The 18 and 24 sizes use a 128 W motor, so it does not fit them. Confirm the number on your old motor. | Daikin Applied 4017514 — Dc280v 41w 8p Motor |
| Outdoor unit PCB (main PCB) | Replace when the radiation fin temperature is not above A, when Check No. 16 fails at the 320 VDC step, or when both steps pass. The manual also replaces the PCB for a P4 radiation fin thermistor fault (p.79). The listing title does not say indoor or outdoor or name a model, so match your old board's number. | Daikin Applied 6025170 — Printed Circuit Assy (Main) |
If the fin overheats while the compressor runs, the code is L4 instead. See Daikin L4 and P4 Errors. If the fan motor locks, see Daikin A6 and E7 Errors. More parts: Daikin Parts for VRV Units.
Which units this applies to
- Cooling only: FTK09/12/18/24AXVJU with RK09/12/18/24AXVJU
- Heat pump: FTX09/12/18/24AXVJU with RX09/12/18/24AXVJU
Scope: All values come from DAMA-SM-21-001 and apply only to the models listed. Other Daikin families use L3 differently or not at all. Our listings do not name these models.
Before you order
Write down the indoor and outdoor model and serial numbers, the results of Check No. 16 and No. 19, and the part number on the old motor or board. Contact us or email help@totalhvacparts.com and we will match it.
Frequently Asked Questions
What does L3 mean on a Daikin mini split?
On FTK/FTX AX wall-mount systems it is electrical box temperature rise. The radiation fin went above its limit with the compressor off: 82.0°C (179.6°F) on 09/12 sizes and 90.0°C (194.0°F) on 18/24 sizes (DAMA-SM-21-001, p.81).
Why does my Daikin outdoor fan run when the compressor is off?
The manual says the outdoor fan starts to cool the electrical components when the radiation fin rises above a set temperature (70°C on 09/12, 81°C on 18/24) and stops when it falls below 65°C or 64°C.
Is L3 usually the fan motor?
The manual lists the defective outdoor fan motor first. Its chart checks the fin temperature and the outdoor fan (Check No. 19) before fin dirt and the installation.
How do I test a Daikin outdoor DC fan motor?
Check No. 16 measures 320 VDC, 15 VDC and 0 to 6.5 VDC at S70 or S71, then counts 4 pulses per turn of the fan by hand. NG at the 0 to 6.5 VDC step means a defective Hall IC and a new fan motor.
Sources
- Daikin DAMA-SM-21-001, Service Manual, Inverter Split Wall Mounted Type FTK(X) Series — pp.13, 16, 18, 19, 79, 81, 90, 91, 92
- Live product titles and listed specs for the listings above, read from our catalog
Inverter outdoor units carry line voltage and a charged DC bus. Service should be performed only by qualified personnel, following Daikin's service manual and your site's lockout/tagout procedures.