Daikin L4 means the inverter's radiation fin got too hot; P4 means the radiation fin thermistor itself reads open or shorted. Daikin's SM-TS3 list gives L4 as "Malfunction of inverter radiation fin temperature rise" (fin temperature rise due to short circuit, defective fin thermistor) and P4 as "Malfunction of radiation fin temperature sensor". On RZR-TA/RZQ-TA units, service manual SiUS281811EA checks airflow and the thermistor connector for L4, measures the fin thermistor for P4, and ends at the outdoor main PCB (A1P), the compressor or the fan motor.
What do L4 and P4 mean?
| Code | SM-TS3 name | SM-TS3 supposed causes |
|---|---|---|
| L4 | "Malfunction of inverter radiation fin temperature rise" | "Fin temperature rise due to short circuit"; "Defective fin thermistor" |
| P4 | "Malfunction of radiation fin temperature sensor" | "Defective radiation fin temperature thermistor"; "Defective inverter PCB"; "Defective INV. compressor"; "Defective fan motor" |
The radiation fin is the heat sink for the inverter power module. L4 says the fin really is hot (or reads hot). P4 says the sensor signal is not believable.
What does the service manual check for L4?
SiUS281811EA, "Radiation fin temperature rise abnormality" (p. 268), applies to all outdoor units in the manual. The fin temperature is measured by the radiation fin thermistor; the list of inverter-related error codes (CHECK 9, p. 299) gives the condition as the radiation fin temperature reaching 87°C (188°F) or more while in operation. The listed causes on p. 268 are activation of the radiation fin thermistor, a defective outdoor main PCB and a defective radiation fin thermistor; the flowchart adds defective radiation (heat dissipation) from the power unit.
- Check heat dissipation. Is the fin temperature above the designed temperature? If so, the chart points to defective radiation from the power unit: a blocked air suction port, a stained radiation fin or a high outdoor air temperature.
- Check the connector. Confirm the fin thermistor connector X111A is correctly connected to the outdoor unit PCB, then power on.
- Check for P4. If the remote controller shows P4, go to the P4 procedure below.
- Run and watch. If L4 comes back when the unit starts, the manual's end box is to replace the outdoor main PCB (A1P). If not, keep operating.
What does the service manual check for P4?
"Radiation fin thermistor abnormality" (p. 274) is detected by measuring the resistance of the fin thermistor and the PCB circuit thermistor while the compressor is not running. The decision is a resistance equal to an open or short circuit, and the manual notes the error is not decided while operation continues. Listed causes are a defective fin thermistor, a defective PCB, a defective inverter compressor and a defective fan motor.
- Measure the thermistor. Disconnect X111A and measure the radiation fin thermistor resistance (CHECK 11). Compare it with the table below at the fin temperature.
- Abnormal resistance. Replace the outdoor main PCB (A1P), per the manual for this family.
- Compressor insulation. If the compressor's insulation resistance is below 100 kΩ, replace the compressor (M1C).
- Fan motor insulation. If the fan motor's insulation resistance is below 1 MΩ, replace the fan motor.
- Restart. If P4 returns at power-on, replace the outdoor main PCB; otherwise continue operation.
What should the fin thermistor read?
CHECK 11 (pp. 301-303) lists two thermistor types: R10T (Type K) on RZR/RZQ18 and 24TAVJU, and FINTH (Type F) on RZR/RZQ30 to 48TAVJU. The manual marks these values as data for reference only.
| Temperature | Type K (kΩ) | Type F (kΩ) |
|---|---|---|
| -30°C | 350.6 | 354.1 |
| 0°C | 63.80 | 64.10 |
| 25°C | 19.40 | 19.41 |
| 50°C | 6.962 | 6.954 |
| 100°C | 1.305 | 1.304 |
| 120°C | 0.7420 | 0.7450 |
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Fin thermistor | SM-TS3 lists a defective fin thermistor for L4 and P4. In SiUS281811EA the P4 chart's end action for an abnormal reading is the outdoor main PCB, so check your unit's parts list for whether the fin thermistor is sold separately. The listing title does not name a model; match the part number on your old part or your unit's parts list. | Daikin Applied 1885374 — Fin Thermistor |
| Inverter / control board | Defective inverter PCB is a P4 cause in SM-TS3. The listing title does not name a model; match the part number on your old part or your unit's parts list. | Daikin Applied 2198390 — Inverter Assembly/control Board |
| Inverter assembly | Alternate inverter listing. The listing title does not name a model; match the part number on your old part or your unit's parts list. | Daikin Applied 2007595 — Inverter Assembly |
| Compressors and fan motors | When the insulation tests in P4 point to them | Daikin Parts for VRV Units |
Which units this applies to
- L4 and P4 meanings: units covered by Daikin's SM-TS3 list.
- Checks, X111A, 87°C (188°F) and CHECK 11 values: RZR18-48TAVJU(A) cooling-only and RZQ18-48TAVJU(A) heat pump outdoor units, with the FCQ-TA, FHQ-P, FHQ-M, FAQ-TA, FBQ-P and FTQ-TA indoor units the manual covers.
Scope: The procedures and values above come from SiUS281811EA and apply only to RZR-TA and RZQ-TA outdoor units. Other families may use different values. Listings are shown by live title and are not a fit confirmation.
Before you order
Note the outdoor model, serial number and the part number on the board or thermistor you plan to replace. Contact us or email help@totalhvacparts.com and we will help confirm the part.
Frequently Asked Questions
What does Daikin L4 mean?
SM-TS3 defines L4 as "Malfunction of inverter radiation fin temperature rise". On RZR-TA/RZQ-TA units the manual's table gives 87°C (188°F) or more during operation.
What does Daikin P4 mean?
P4 is "Malfunction of radiation fin temperature sensor": the fin thermistor reads like an open or short circuit.
Is L4 always a bad board?
No. Check heat dissipation first: blocked suction air, dirty fins and high outdoor temperature are on the manual's list. Then check connector X111A and look for P4. Replace the outdoor main PCB if L4 returns at startup after those checks.
What should a Daikin fin thermistor read at 25°C?
In SiUS281811EA CHECK 11, 19.40 kΩ for Type K and 19.41 kΩ for Type F, marked as reference data.
Sources
- Daikin, Simple Self-Diagnosis by Malfunction Code, SM-TS3 (error code list, pages 1-6)
- Daikin Service Manual, Cooling Only 60 Hz / Heat Pump 60 Hz, RZR-TA, RZQ-TA Series, SiUS281811EA (L4 p. 268; P4 p. 274; CHECK 9 p. 299; CHECK 11 pp. 301-303)
- Live product titles for the listings above, read from our catalog
Daikin inverter systems carry line voltage, high-voltage DC on the inverter circuit, pressurized refrigerant and rotating fans. Service should be performed only by qualified personnel, following the Daikin service manual for your model and your site's lockout/tagout procedures.