Rheem Furnace Code 57, Pressure Switch Stuck Open: Inducer Checks Before You Replace 70-101087-81

On Rheem downflow single-stage gas furnaces covered by installation instructions 92-24161-145-12, code 57 reads "PRESS SWITCH STUCK OPEN WHEN SHOULD BE CLOSED." The control started the induced draft blower (IDM), but the air-proving pressure switch never closed. Rheem's pressure switch section lists an inoperative induced draft blower, a loose or leaky hose, a blockage in the vent and severe downdrafts as reasons the switch will not close, and its diagnostic flowchart starts with "Does the IDM Energize?" If the inducer is the failed part and its label reads 70-101087-81, the fix is Rheem 70-101087-81 Blower Motor, Draft Inducer 115V — Replacement, our verified replacement for Rheem 70-101087-81.

What do codes 55, 57, 10 and 11 mean?

Code Rheem text (92-24161-145-12) What it tells you
55 PRESSURE SWITCH STUCK CLOSED WHEN SHOULD BE OPEN The switch was already closed before the inducer started. Look at the switch and its wiring, not the inducer.
57 PRESS SWITCH STUCK OPEN WHEN SHOULD BE CLOSED The inducer was energized but airflow was not proven. Check the IDM, hose and vent.
10 1 HOUR LOCKOUT Flame has not been detected after four ignition trials.
11 FAILED IGNITION Ignition attempt failed. This is downstream of the pressure switch.

How does the control use the inducer and pressure switch?

Per 92-24161-145-12, on each call on W the control first confirms the pressure switch is open, then starts the induced draft blower for pre-purge. The air-proving negative pressure switch(es) close. After a 30-second pre-purge, the gas valve opens for an 8-second ignition trial and the spark igniter lights the burners. The low pressure switch must close within 60 seconds of inducer operation at the start of a heat cycle. If it does not, the control enters a five-minute soft lockout that resets automatically. A furnace that keeps restarting every few minutes with code 57 is following that logic.

How do I work through code 57?

  1. Does the IDM energize? This is Rheem's first flowchart question. Call for heat and watch the inducer.
  2. If it does not run: follow Rheem's next steps, "Check line voltage at IDM" and "Check IDM wired correctly." Power present at the motor with no rotation, or a seized or dragging wheel, means the inducer has failed.
  3. If it runs: check the pressure switch hose. Rheem lists a loose or leaky hose as a cause. Make sure it is tight on both ends and not cracked.
  4. Check the vent. Rheem lists vent blockage and severe downdrafts. The start-up checklist calls for the "Vent pipe secured to induced draft blower housing," and the venting section requires horizontal runs to "Rise 1/4 inch per foot away from the furnace" without sags or dips.
  5. Check for intermittent pressure switch operation (Rheem flowchart). Work through the hose, vent and switch before you condemn the inducer.
  6. If the vent, hose and switch are good but the inducer is slow, noisy or cannot hold the switch closed, replace the inducer. Rheem's start-up checklist also calls for a "Proper negative pressure reading in the vent." Confirm it after the repair.

Parts that fix it

Component Role Link
Draft inducer (induced draft blower), 115 V Primary fix when the inducer has failed. Replaces Rheem 70-101087-81; the listing also covers 70-1010187-81, 70-2417581 and 702111559. Rheem 70-101087-81 Blower Motor, Draft Inducer 115V — Replacement
Draft inducer, 115 V (A066) Only if your old inducer reads 70-24175-81 or one of the numbers that listing covers (for example 70-22838-82, 70-24157-03 or 7062-4702). This is a different Rheem number. Rheem 70-24175-81 Blower Motor, Draft Inducer 115V A066 — Replacement

Which units this applies to

  • Codes, sequence and diagnostics: Rheem (-)801T, (-)801C, (-)80DSX and (-)80DSC single-stage gas furnaces covered by 92-24161-145-12.
  • Part: any furnace whose existing inducer or Rheem parts list shows 70-101087-81, 70-1010187-81, 70-2417581 or 702111559 (the numbers our listing replaces).

Scope: Code text, timings and flowchart steps are from Rheem 92-24161-145-12 and apply to the models it covers. Other Rheem and Ruud furnaces may use different codes or flash patterns, so check the label on your furnace. The instructions do not list inducer part numbers by model, so this article matches the part only by the number on the old inducer. Our part's rating (115 V) comes from its listing.

Before you order

Read the part number on the label of the part you are removing and have the unit's full model and serial number from the rating plate. If the number on your old part is not one of the numbers listed above, or anything about the unit looks different from what is described here, contact us or email help@totalhvacparts.com with the model, serial and old part number and we will check it before you order.

Frequently Asked Questions

What does code 57 mean on a Rheem furnace?

In 92-24161-145-12, code 57 is "PRESS SWITCH STUCK OPEN WHEN SHOULD BE CLOSED." The inducer was told to run, but the pressure switch did not prove airflow.

Why does my Rheem furnace restart every five minutes?

If the low pressure switch does not close within 60 seconds of inducer operation, the control enters a five-minute soft lockout and then tries again automatically.

Code 55 or code 57: which one is the inducer?

Code 57 (switch stuck open) can be the inducer, the hose or the vent. Code 55 (switch stuck closed when it should be open) points at the switch or its wiring, not the inducer.

Is 70-24175-81 the same as 70-101087-81?

They are different Rheem numbers on separate listings with different cross-reference lists. Order the one that matches the number on your old inducer.