Daikin JA and JC Errors: High or Low Pressure Sensor Failed?

Daikin JA is a high pressure sensor fault and JC is a low pressure sensor fault. Daikin's SM-TS3 list names them "Malfunction of high pressure sensor" and "Malfunction of low pressure sensor", and for both it lists a defective connector contact, the two sensors plugged into each other's connector, a defective sensor and a defective outdoor unit PCB. In the RZR-TA/RZQ-TA service manual (SiUS281811EA), the fix is the high pressure sensor (S1NPH), the low pressure sensor (S1NPL) or the outdoor main PCB (A1P), decided with CHECK 12.

What do JA and JC mean?

Code SM-TS3 name SiUS281811EA decision condition Sensor range in the manual
JA "Malfunction of high pressure sensor" High pressure sensor short circuit or open circuit (p. 265) 0-4.3 MPa (0-624 psi)
JC "Malfunction of low pressure sensor" Low pressure sensor short circuit or open circuit (p. 266) 0-1.7 MPa (0-247 psi)

These are sensor codes, not pressure trips. If the pressure itself is out of range, the codes to look up are E3 and E4, covered in our article on Daikin E3 and E4 errors. JA and JC say the controller cannot trust the sensor signal.

What causes them?

Cause JA (SM-TS3 / SiUS281811EA) JC (SM-TS3 / SiUS281811EA)
Connector "Defective connector contact"; disconnected high pressure sensor "Defective connector contact"; disconnected low pressure sensor
Sensors swapped "Connection of low pressure sensor in mistake for high pressure sensor" "Connection of high pressure sensor in mistake for low pressure sensor"
Sensor "Defective high pressure sensor" "Defective low pressure sensor"
Board "Defective outdoor unit PCB" "Defective outdoor unit PCB"

The swapped-sensor cause matters after any repair where both sensors were unplugged. On the units in SiUS281811EA the two sensors go to different connectors (X17A and X18A) on the same board.

How do you test the sensor (CHECK 12)?

CHECK 12 in SiUS281811EA (p. 304) compares the sensor's output voltage with the actual pressure. For the RZR-TA/RZQ-TA outdoor units it gives these connection points on the outdoor main PCB (A1P):

Sensor Connector on A1P Connector color Part code in the manual
High pressure sensor X17A red S1NPH
Low pressure sensor X18A blue S1NPL

Each sensor has three wires (red, black, white) and is fed +5 V from the board. CHECK 12 says to measure DC voltage between the black and white wires. The manual's conversion formulas (p. 304), with 1 MPa = 145 psi:

Sensor Formula in SiUS281811EA
High pressure PH (MPa) = (4.15 / 3.0) × VH − (4.15 / 3.0) × 0.5
Low pressure PL (MPa) = (1.7 / 3.0) × VL − (1.7 / 3.0) × 0.5

VH and VL are the output voltages (VDC). On both sensors, 0.5 VDC corresponds to 0 MPa on the manual's chart.

  1. Confirm the connectors. Is each sensor on its own connector (high at X17A, low at X18A)? If not, connect it correctly and re-power the unit (first step of the JA and JC flowcharts, pp. 265-266).
  2. Put gauges on. Read the actual high and low side pressures with a manifold gauge.
  3. Measure the sensor voltage. With the unit powered, measure DC voltage at the connector as CHECK 12 shows and compare it with the gauge reading using the chart on p. 304.
  4. Sensor or board. If the sensor voltage does not match the gauge pressure, replace that sensor (S1NPH for JA, S1NPL for JC). If the voltage matches but the pressure the PCB reports (service checker data) does not, replace the outdoor main PCB (A1P).
  5. Reset and restart. If both checks pass, reset the operation and restart the outdoor unit, then check the sensor characteristics again. Not normal: replace the sensor. Normal: the chart ends at replacing the outdoor main PCB (A1P).

Parts that fix it

Component Role Link
High pressure sensor Replace for JA when its voltage does not match gauge pressure. The listing title does not name a model; match the part number on your old part or your unit's parts list. Daikin Applied 6023718 — High Pressure Sensor
Low pressure sensor Replace for JC when its voltage does not match gauge pressure. The listing title does not name a model; match the part number on your old part or your unit's parts list. Daikin Applied 6023719 — Low Pressure Sensor
Pressure sensor Alternate pressure sensor listing; check the part number on the old sensor body. The listing title does not name a model; match the part number on your old part or your unit's parts list. Daikin Applied 2336736 — Pressure Sensor
Outdoor PCBs and more When the sensor tests good and the PCB reading is wrong Daikin Parts for VRV Units

Which units this applies to

  • JA and JC meanings and causes: units covered by Daikin's SM-TS3 list.
  • Ranges, connectors and CHECK 12: RZR18-48TAVJU(A) cooling-only and RZQ18-48TAVJU(A) heat pump outdoor units, with the FCQ-TA, FHQ-P, FHQ-M, FAQ-TA, FBQ-P and FTQ-TA indoor units the manual covers.

Scope: The 0-4.3 MPa and 0-1.7 MPa ranges, the X17A/X18A connectors and the S1NPH/S1NPL names come from SiUS281811EA and apply to RZR-TA and RZQ-TA outdoor units. VRV outdoor units use their own connector names and test pages. The sensor listings above are shown by live title and do not confirm fit for a model.

Before you order

Read the part number off the old sensor body or the unit's parts list, and note the outdoor model and serial number. High and low sensors are not interchangeable: the manual gives them different ranges (0-4.3 MPa and 0-1.7 MPa). Contact us or email help@totalhvacparts.com with those details and we will help confirm the part.

Frequently Asked Questions

What does Daikin JA mean?

SM-TS3 defines JA as "Malfunction of high pressure sensor". SiUS281811EA decides it when the high pressure sensor reads as a short or open circuit.

What does Daikin JC mean?

JC is "Malfunction of low pressure sensor". SiUS281811EA decides it when the low pressure sensor reads as a short or open circuit.

Can swapped sensors cause JA or JC?

Yes. Both SM-TS3 and SiUS281811EA list a low pressure sensor connected in place of the high pressure sensor, and the reverse, as causes.

Where do the pressure sensors plug in on an RZQ-TA?

SiUS281811EA CHECK 12 shows the high pressure sensor at connector X17A (red) and the low pressure sensor at connector X18A (blue) on the outdoor main PCB (A1P).

Sources

Daikin inverter systems carry line voltage, high-voltage DC on the inverter circuit, pressurized refrigerant and rotating fans. Service should be performed only by qualified personnel, following the Daikin service manual for your model and your site's lockout/tagout procedures.