Goodman Furnace 3 Flashes, Inducer Runs but No Ignition: Pressure Switch Checks and Inducer 11009001

On Goodman GMS8, GDS8 and GHS8 furnaces, 3 flashes means "Pressure switch circuit not closed" while the induced draft blower is operating. The symptom is an inducer that "runs continuously with no further furnace operation." Goodman's troubleshooting chart in IO-242C lists the causes as a blocked, pinched or misconnected pressure switch hose, a blocked flue or weak induced draft blower, an incorrect pressure switch setpoint or bad switch contacts, and loose or misconnected wiring. If the inducer is the weak link and its label reads 11009001, the fix is Goodman 11009001 Blower Motor, Draft Inducer 115V — Replacement, our verified replacement for Goodman 11009001.

What do 1, 2 and 3 flashes mean on a Goodman GMS8 / GDS8?

All three codes involve the inducer circuit, so it helps to see them side by side. The wording below is from the IO-242C troubleshooting chart.

LED Fault (IO-242C) Possible causes Goodman corrective actions
1 flash Furnace lockout due to an excessive number of ignition attempts and "retries" Failure to establish flame; loss of flame after establishment; insufficient conditioned air over the heat exchanger Correct gas interruption; replace or realign igniter; clean flame sensor; verify proper induced draft blower performance; check circulator blower
2 flashes Pressure switch circuit is closed; induced draft blower is not operating Pressure switch contacts sticking; shorts in pressure switch circuit Replace pressure switch; repair short
3 flashes Pressure switch circuit not closed; induced draft blower is operating Hose blocked, pinched or connected improperly; blocked flue or weak induced draft blower; incorrect setpoint or malfunctioning contacts; loose or improperly connected wiring Inspect hose; inspect flue for blockage, length, elbows and termination; correct setpoint or contact motion; replace pressure switch; tighten wiring

Two chart footnotes matter when you arrive at a no-heat call. The LED flash code "will cease if power to the control module is interrupted through the disconnect or door switch," so read it before you pull the blower door. And the control module "will automatically attempt to reset from lockout after one hour."

How do I tell a weak inducer from a vent or switch problem?

  1. Read the code before you open the blower door or switch off power, and write it down.
  2. Inspect the pressure switch hose end to end: blocked, pinched or improperly connected are all listed 3-flash causes, and any of them gives 3 flashes with a healthy inducer.
  3. Inspect the flue as IO-242C directs: check for blockage, then compare the length, the number of elbows and the termination against the venting tables in the manual.
  4. Tighten and check wiring at the pressure switch and the control. Goodman lists loose or improperly connected wiring as a 3-flash cause.
  5. Watch the inducer on a call for heat. Goodman lists a "weak induced draft blower" as a cause; with the hose, flue and wiring cleared, an inducer that cannot bring the switch closed is the remaining suspect on that line of the chart.
  6. If the hose, flue and wiring are good and the inducer runs strongly but the switch still never closes, the switch setpoint or contacts are the next suspect. Replace the switch only with the proper replacement part, as Goodman specifies.

Goodman also warns: "Turn power OFF prior to repair." Read the Electrostatic Discharge precautions in the manual before handling the control module.

Parts that fix it

Component Role Link
Draft inducer motor assembly, 115 V Primary fix when the inducer is weak or failed. Replaces Goodman 11009001; the listing also covers Goodman 11009002 and 11009003. Goodman 11009001 Blower Motor, Draft Inducer 115V — Replacement
Draft inducer motor assembly, 115 V Same cross-reference, listed under the 11009002 number Goodman 11009002 Blower Motor, Draft Inducer 115V — Replacement
Draft inducer motor assembly, 115 V Same cross-reference, listed under the 11009003 number Goodman 11009003 Blower Motor, Draft Inducer 115V — Replacement

Which units this applies to

  • Flash codes, causes and corrective actions: Goodman GMS8, GDS8 and GHS8 single-stage furnaces covered by IO-242C (05/05).
  • Part: any furnace whose existing inducer, or Goodman / Amana parts list, shows 11009001, 11009002 or 11009003 (the numbers our listing replaces).

Scope: The codes and chart wording are from Goodman IO-242C and apply to the models it names. Later Goodman and Amana furnaces use similar codes, but you should confirm against the label on your unit. IO-242C does not list inducer part numbers by model, so this article matches the part only by the number on the old inducer. Our part's rating (115 V) comes from its listing.

Before you order

Read the part number on the label of the part you are removing and have the unit's full model and serial number from the rating plate. If the number on your old part is not one of the numbers listed above, or anything about the unit looks different from what is described here, contact us or email help@totalhvacparts.com with the model, serial and old part number and we will check it before you order.

Frequently Asked Questions

What does 3 flashes mean on a Goodman furnace?

In IO-242C, 3 flashes means "Pressure switch circuit not closed" while the induced draft blower is operating. Typically the inducer runs and nothing else happens.

Does 3 flashes always mean a bad inducer?

No. Goodman lists hose problems, a blocked flue, the switch setpoint or contacts, and loose wiring alongside a weak induced draft blower. Check those before replacing the inducer.

Why did the code disappear when I opened the door?

Goodman notes the flash code ceases if power to the control is interrupted through the disconnect or door switch. Read the code before opening the blower door.

Are 11009001, 11009002 and 11009003 interchangeable?

Our 11009001 listing states that it also replaces Goodman 11009002 and 11009003, so one replacement covers all three numbers.

Sources

Safety: gas-fired equipment must be serviced by qualified personnel only. Shut off the gas supply and lock out / tag out electrical power before opening the unit, unplugging connectors or handling controls and motors.