American Standard / Trane Furnace 3 Flashes Draft Pressure Error: Vent, Switch or Inducer BLW01137?

On American Standard / Trane single-stage, fan-assisted gas furnaces such as the CUB1 and CDB1, 3 red flashes on the integrated furnace control (IFC) means "Draft Pressure Error". The guide lists three possible causes: a venting problem, a pressure switch problem or an inducer problem. American Standard IOM 41-5010-25 also explains that if the pressure switch does not sense pressure, the gas valve will not open and the unit will not start. Rule out the vent and the switch first. If the inducer is the failed part and its label reads BLW01137 or D330757P01, the fix is Trane BLW01137 Draft Inducer 115V/60HZ 3000 Rpm — Replacement, our verified replacement for Trane BLW01137.

What do the IFC flash codes mean?

IFC LED Meaning (41-5010-25)
Flashing slow Normal, no call for heat
Flashing fast Normal, call for heat
Continuous on Replace IFC
Continuous off Check power
2 flashes System lockout (retries or recycles exceeded)
3 flashes Draft pressure error: a) venting problem, b) pressure switch problem, c) inducer problem
4 flashes Open temperature limit circuit
5 flashes Flame sensed when no flame should be present
6 flashes 115 volt AC power reversed, poor grounding or system voltage too low
7 flashes Gas valve circuit error
8 flashes Low flame sense signal

Where does the inducer fit in the heating sequence?

Per 41-5010-25, when R and W close, the control runs a self-check. After it verifies that the pressure switch contacts are open and the limit switch contacts are closed, it energizes the draft blower (inducer). "As the induced draft blower comes up to speed, the pressure switch contacts will close and the ignitor warm up period will begin." The ignitor heats for about 17 seconds, then the gas valve opens, and the flame sensor must confirm ignition within the 4-second trial. The indoor blower starts after a fixed 45-second fan-on delay.

A 3-flash furnace stops at the step where the pressure switch should close. If you see the ignitor glow, the switch has proven and you are chasing something else.

How do I check vent, switch and inducer?

  1. Read the flash code before you remove the blower door or kill power, and confirm it is 3 flashes.
  2. Check the vent first. Under "Abnormal Conditions," 41-5010-25 says that if pressure against the induced draft blower outlet becomes excessive, the pressure switch will shut off the gas valve until acceptable combustion pressure returns. Look for a blocked flue, a nest or debris at the termination, or a disconnected or sagging connector.
  3. Check the pressure switch tubing for cracks, kinks or a loose fit, and make sure the switch port and the inducer tap are clear.
  4. Call for heat and watch the inducer. It should start after the control's self-check and come up to speed. If the inducer does not start, or does not come up to speed, it is the likely failure.
  5. If the inducer runs strongly and the vent and tubing are good but the switch never closes, the pressure switch is the next suspect, not the inducer.
  6. If 6 flashes is also logged, fix the 115 V polarity, grounding or low voltage first. The guide lists all three as 6-flash causes, and they can confuse the rest of the diagnosis.

To clear a lockout after the repair, the guide's Problem Solver table says: "Turn power on-off-on-off twice in 30 seconds."

Parts that fix it

Component Role Link
Draft inducer, 115 V / 60 Hz, 3000 rpm Primary fix when the inducer has failed. Replaces Trane BLW01137; the listing also covers D330757P01. Trane BLW01137 Draft Inducer 115V/60HZ 3000 Rpm — Replacement
Draft inducer, 115 V / 60 Hz, 3200 rpm Only if your old inducer reads BLW01138. This is a different Trane number with a different listed speed. Trane BLW01138 Draft Inducer 115V/60HZ 3200 Rpm — Replacement

Which units this applies to

  • Flash codes, sequence and abnormal-condition behavior: American Standard CUB1 and CDB1 single-stage gas furnaces listed in IOM 41-5010-25 (for example CUB1B080A9361A and CDB1C100A9601A).
  • Part: any furnace whose existing inducer or Trane / American Standard parts list shows BLW01137 or D330757P01 (the numbers our listing replaces).
  • Not this part: inducers labeled BLW01138. See the second row of the table.

Scope: The codes, sequence timings and reset method are quoted from 41-5010-25 and apply to the furnaces it covers. Other Trane and American Standard furnaces use similar IFC codes but may differ in timing and in their extra codes. Use the label on your furnace door. 41-5010-25 does not list inducer part numbers by model, so this article matches the part only by the number on the old inducer. Our part's ratings (115 V / 60 Hz, 3000 rpm) come from its listing.

Before you order

Read the part number on the label of the part you are removing and have the unit's full model and serial number from the rating plate. If the number on your old part is not one of the numbers listed above, or anything about the unit looks different from what is described here, contact us or email help@totalhvacparts.com with the model, serial and old part number and we will check it before you order.

Frequently Asked Questions

What does 3 flashes mean on an American Standard or Trane furnace?

In 41-5010-25, 3 flashes is "Draft Pressure Error," with a venting problem, a pressure switch problem or an inducer problem as the possible causes. The furnace will not open its gas valve until the pressure switch proves.

Can a blocked vent cause 3 flashes?

Yes. 41-5010-25 says excessive pressure against the induced draft blower outlet, for example from a flue blockage, makes the pressure switch shut off the gas valve until acceptable combustion pressure returns. Check the vent and termination before replacing parts.

Is BLW01138 the same as BLW01137?

No. Our listings show BLW01137 at 3000 rpm and BLW01138 at 3200 rpm. Order the number printed on your old inducer.

How do I reset the lockout?

41-5010-25 says to turn power on-off-on-off twice in 30 seconds.