On a Pentair MiniMax NT Low NOx pool heater, the flame loss fault icon means the hot-surface ignition (HSI) module locked out: the main burner did not light, or flame was not detected during the trial for ignition. Pentair's manual (P/N 471593) gives a five-step ignition module service check covering power, the W call, igniter, gas valve and flame sense, plus a 0.7 µA minimum flame current. Use those checks to separate the module from the igniter, valve and sensor. If the module is the fault and its label reads 472447 or Fenwal 35-662902-113, the fix is Pentair 472447 Pool Heater Ignition Control — Replacement, our verified replacement for Pentair 472447.
How does the MiniMax NT Low NOx ignition sequence work?
Per Pentair 471593, on a call for heat the module runs a self-check. Units made before 10-15-01 also flash the module's diagnostic LED for up to four seconds. After a fan pre-purge of about 2 minutes, the hot-surface igniter heats for about 40 seconds, then the gas valve opens for the trial for ignition. Once flame is detected, the igniter turns off and the gas valve stays energized.
If the burner does not light or flame is not detected during the trial, the control locks out and turns the gas valve off, and the 7800 control shows the flame loss fault icon. If flame is lost while running, the control responds within 1 second. Flame loss is a hard lockout that needs a manual reset once the cause is corrected.
What do the fault icons mean?
| Fault (471593) | Lockout type | What is behind it |
|---|---|---|
| Flame loss | Hard lockout, manual reset after correction | No flame proven during trial, or flame lost and not re-established |
| Blower / gas pressure | Hard lockout, manual reset | Low gas pressure switch, and the fan and air pressure switch circuit |
| High limit | Soft lockout, clears on its own | Temperature returns to normal (three high limits: two on the inlet/outlet header, one on the exhaust) |
| Insufficient water flow | Soft lockout, clears when flow returns | Water pressure switch |
The module will not run unless the factory-set air pressure (fan) switch and all other safety switches are closed. A blower or gas-pressure fault is not a reason to replace the ignition module.
How do I test the ignition module before replacing it?
These are Pentair's ignition module service checks, in the manual's order:
- Dead: check for miswiring, a bad transformer, a bad fuse or breaker, or a bad control. The LED should be steady on.
- Thermostat on, no ignition: check for miswiring, or a bad thermostat with no voltage at terminal W.
- Valve on, no igniter: check for a defective igniter, miswiring, or a bad control. Check the voltage at the igniter.
- Igniter on, no valve: check for an open valve coil or wire, or a bad control. Check the voltage between V1 and V2.
- Flame okay during trial, no flame sense after trial: check for a bad igniter, a bad S1 wire, a poor burner ground or a poor flame. Check the flame current.
Flame current: Pentair gives 0.7 µA as the minimum to avoid lockout, measured through the FC1/FC2 terminals with a microammeter. If the meter reads below zero, the meter leads are reversed.
The module is the likely failure when the LED is not steady on with good power and fuse (check 1), when W is present but nothing starts (check 2), or when voltage is missing at the igniter or across V1-V2 while the module is calling for it (checks 3-4). To reset after the repair, reset the 7800 thermostat, or turn off the main power switch (in the junction box behind the right door) for 5 seconds.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Pool heater ignition control (HSI module) | Primary fix when the module fails the service checks. Replaces Pentair 472447; the listing also covers Fenwal 35-662902-113, Pentair 6273-0212, 47-110-1780, PUR-151-4101 and PEN472447. | Pentair 472447 Pool Heater Ignition Control — Replacement |
| Pool heater ignition control | Same cross-reference, listed under the Fenwal 35-662902-113 number | Fenwal 35-662902-113 Pool Heater Ignition Control — Replacement |
Which units this applies to
- Sequence, fault icons and service checks: Pentair MiniMax NT Low NOx pool and spa heaters, models 200, 250, 300 and 400 (natural gas), per Pentair 471593 Rev. C.
- Part: any heater whose existing ignition control is labeled with one of the numbers in the table above.
Scope: Pentair 471593 lists the ignition control module (item 45) in its parts list, but it does not name 472447, so this article does not claim which MiniMax NT build uses 472447. Match the label on your old module. The service checks and values are quoted from 471593 and apply to the heaters it covers.
Before you order
Read the part number on the label of the part you are removing and have the unit's full model and serial number from the rating plate. If the number on your old part is not one of the numbers listed above, or anything about the unit looks different from what is described here, contact us or email help@totalhvacparts.com with the model, serial and old part number and we will check it before you order.
Frequently Asked Questions
Why does my MiniMax NT show the flame loss fault?
Per Pentair 471593, the module locked out because the burner did not light or flame was not detected during the trial, or flame was lost and not re-established. It needs a manual reset after the cause is corrected.
What flame current does the MiniMax NT Low NOx need?
Pentair gives 0.7 µA as the minimum to avoid lockout, measured at FC1/FC2 with a microammeter.
How do I reset the heater after a lockout?
Reset the 7800 thermostat, or turn off the main power switch in the junction box behind the right door for 5 seconds.
Is Pentair 472447 the same as Fenwal 35-662902-113?
Our 472447 listing states that it also replaces Fenwal 35-662902-113 and several other Pentair numbers, so either label is covered.
Sources
- Pentair P/N 471593 Rev. C (11-1-01), MiniMax NT Low NOx Pool & Spa Heaters (models 200, 250, 300, 400) Operation & Installation Manual
- Total HVAC Parts product listing: Pentair 472447 replacement (cross-reference numbers)
Safety: gas-fired equipment must be serviced by qualified personnel only. Shut off the gas supply and lock out / tag out electrical power before opening the unit, unplugging connectors or handling controls and motors.