Daikin U5 or U8 Error: Remote Controller Setting, Wiring or Bad PCB?

Daikin U5 is a transmission error between the indoor unit and its remote controller; U8 is a transmission error between a main and a sub remote controller. Daikin's SM-TS3 list gives the causes: wiring or transmission faults, two remote controllers both set as main (U5) or a sub-to-sub connection (U8), a defective remote controller PCB, a defective indoor unit PCB (U5) and noise. Check the main/sub setting and wiring first; when the service manual's checks point to a part, it is the wired remote controller, such as the Madoka BRC1H71W, or the indoor unit PCB.

What do U5 and U8 mean?

Code SM-TS3 name SM-TS3 supposed causes
U5 "Malfunction of transmission between indoor unit and remote controller" "Transmission error between indoor unit and remote controller"; "Connection of 2 main remote controllers (when using 2 remote controllers)"; "Defective indoor unit PCB"; "Defective remote controller PCB"; "Transmission error caused by noise"
U8 "Malfunction of transmission between remote controllers" "Transmission error between main and sub remote controller"; "Connection between sub remote controllers"; "Defective remote controller PCB"

What does the service manual check?

In the RZR-TA/RZQ-TA service manual SiUS281811EA, U5 (p. 282) and U8 (p. 283) apply to all indoor units, and both decide the error when "Normal transmission does not continue for specified period."

U5 checks (flowchart, p. 282):

  1. Two controllers? If two remote controllers control the unit and both are set to Main, set one to Sub, turn the power off temporarily and restart.
  2. Is the indoor PCB's microcomputer monitor blinking normally? If not, turn the power off temporarily. If the unit does not reset normally, replace the indoor unit PCB. If it does reset, the error could be produced by noise: check the surrounding area (for example, heavy-duty wireless equipment) and restart.
  3. Monitor blinking normally: replace the remote controller and restart. If operation is still not normal, replace the indoor unit PCB and restart. If it is still not normal after that, the chart again points to noise.

U8 checks (flowchart, p. 283):

  1. One controller: if its Main/Sub setting is not Main, set it to Main, turn the power off once and restart.
  2. Two controllers, both set to Sub: set one of them to Main, turn the power off once and restart.
  3. Two controllers, not both Sub: turn the power off and restart. If the error occurs again, replace the remote controller PCB.

The manual refers to p. 90 for the Main/Sub setting procedure.

What does the Madoka BRC1H71W handbook add?

The BRC1H71W installation handbook (3P607378-1) covers the wiring and the main/sub setting on that controller:

Item BRC1H71W handbook
Terminals "Connect the terminals (P1, P2) of the remote controller to the terminals (P1, P2) of the indoor unit." P1/P2 are not polarity sensitive (p. 9)
Wire Non-shielded, 2-conductor, stranded copper, AWG-18 (p. 9)
Maximum length 1640 feet (500 m) (p. 9)
Main / sub "A controller displaying 1 is set as main, and a controller displaying 2 is set as sub." (p. 13)
U5 at start-up If the sub remote controller is not set at power-on, U5 is displayed in the connection checking screen (p. 13)
Error display "If an error occurs, the icon, an error code and unit number are displayed." The status LED blinks red while an error is occurring (pp. 4-5)

So a U5 that appears right after you add a second Madoka can be a setup step, not a failure: the handbook has you wait for a U5 or U8 code after powering on the second controller, then press and hold until "2" (on U5) or "1" (on U8) appears. The handbook also says that if the sub controller does not show the home screen two minutes after designation, turn off the power and check the wiring (p. 13).

Parts that fix it

Component Role Link
Wired remote controller Defective remote controller PCB is a listed cause of both U5 and U8. The BRC1H71W handbook says some items may not display depending on the connected model, and it refers you to the indoor unit's installation manual. Daikin Applied BRC1H71W — Madoka Remote Controller
Indoor unit main PCB Defective indoor unit PCB is a listed cause of U5. The listing title does not name a model; match the part number on your old part or your unit's parts list. Daikin Applied 6025170 — Printed Circuit Assy (Main)
Other indoor PCBs Browse boards by part number Daikin Parts for VRV Units

Which units this applies to

  • U5 and U8 meanings: units covered by Daikin's SM-TS3 list.
  • Service steps: indoor units covered by SiUS281811EA (FCQ-TA, FHQ-P, FHQ-M, FAQ-TA, FBQ-P, FTQ-TA) with RZR/RZQ-TA outdoor units.
  • Wiring and main/sub setting values: the BRC1H71W Madoka wired remote controller.

Scope: SiUS281811EA's U5 and U8 pages do not name a specific remote controller model. Confirm that BRC1H71W is approved for your indoor unit in that unit's installation manual before ordering it as a replacement. Listings are shown by live title.

Before you order

Note the indoor unit model and serial number, the model of the existing remote controller, and whether one or two controllers are on the unit. For other Daikin communication codes, see our article on the Daikin U4 transmission fault. Contact us or email help@totalhvacparts.com with those details.

Frequently Asked Questions

What does Daikin U5 mean?

SM-TS3 defines U5 as "Malfunction of transmission between indoor unit and remote controller". Causes include wiring faults, two controllers both set as main, a defective indoor unit PCB, a defective remote controller PCB and noise.

What does Daikin U8 mean?

U8 is "Malfunction of transmission between remote controllers": a fault between the main and sub controller, sub controllers connected to each other, or a defective remote controller PCB.

Why does my new Madoka show U5?

The BRC1H71W handbook says that with one indoor unit controlled by two remote controllers, U5 is displayed on the connection checking screen if the sub remote controller is not set at power-on. Finish the main/sub designation, then check the wiring if the sub does not reach the home screen.

How far can a BRC1H71W be from the indoor unit?

The handbook gives a maximum wiring length of 1640 feet (500 m) with non-shielded, 2-conductor, stranded AWG-18 wire on P1 and P2.

Sources