Fenwal 35-70 Ignition Control 3 Flashes Lockout: Troubleshooting Before You Replace 35-705506-023

On a Fenwal Series 35-70 120 VAC direct spark ignition (DSI) control, 3 LED flashes means ignition lockout: the control used up its trial(s) for ignition without proving flame, closed the gas valve, and is waiting for a reset. Fenwal's 35-70 instructions (P/N 35-70-02) give a four-line troubleshooting guide that separates a bad control from a shorted electrode, an open valve coil and a poor flame-sense circuit, with a 1.0 µA DC minimum flame current. If the control fails those checks and is labeled 35-705506-023, the fix is Fenwal 35-705506-023 Direct Spark Ignition Control — Replacement, our verified replacement for Fenwal 35-705506-023.

What do the 35-70 LED codes mean?

At power-up the LED lights for one second to show normal operation. During a fault it blinks on and off at 0.2-second intervals, with a 2.5 to 3.0 second pause between codes.

LED Meaning (35-70-02)
Steady on Internal control failure
2 flashes Flame fault
3 flashes Ignition lockout fault

What are the 35-70 specifications?

Item 35-70-02 value
Input voltage 102 to 138 VAC, 50/60 Hz
Trial for ignition (TFI) 4, 7, 10 or 15 seconds
Flame failure response 0.8 seconds maximum
Minimum flame sense current 1.0 µA DC
Pre-purge options None, 5, 15 or 30 seconds
Inter-purge options None, 15 or 30 seconds
Ignition trials 1 (single trial) or 3 (multi trial)

Those options are built into each part number. Fenwal also asks for the lockout recovery method to be specified when ordering. Two 35-70 controls that look identical can behave differently, which is why the replacement must match the full number on your old control, including the suffix.

How does it lock out, and how do I reset it?

When 120 VAC reaches L1, the control self-checks, runs its pre-purge (if it has one), then energizes the gas valve and sparks until flame is detected or the TFI ends. A single-trial control closes the valve and locks out after one failed TFI. A multi-trial control makes two more attempts with an inter-purge between them, then locks out. If established flame is lost, the default "re-ignition" behavior is to resume sparking within 0.8 seconds.

To reset per 35-70-02: set the thermostat below ambient, or remove 120 VAC for 5 seconds. Controls with automatic reset retry after one hour if the call for heat is still present. Note that the 35-70 has no blower relay, so any combustion-air purge is up to the appliance, not the control.

How do I prove the control is bad?

Work through Fenwal's troubleshooting guide by symptom:

  1. Control will not start up: check wiring; check the thermostat if there is no voltage at L1; check the fuse or circuit breaker; check the control transformer. Replace the control only if it is faulty.
  2. Gas valve on, no spark through TFI: re-establish the 1/8 inch electrode gap if it is shorted; check the high-voltage cable connection; check wiring. A shorted electrode is not a control failure.
  3. Spark on, gas valve off: check the valve coil for an open circuit and check the valve wire, then check for voltage at V1. No voltage at V1 during TFI means the control is faulty.
  4. Flame during TFI, but no flame sense after: check electrode position, the high-voltage wire and connection, and the burner ground, then check flame current at the test pins. Below 1.0 µA DC is a sensing problem to fix before replacing the control.
  5. A steady-on LED (internal control failure), or no valve voltage at V1 with good input power, means the control should be replaced.

Parts that fix it

Component Role Link
120 VAC direct spark ignition control Primary fix when the 35-70 control fails the checks above. Replaces Fenwal 35-705506-023. Fenwal 35-705506-023 Direct Spark Ignition Control — Replacement
24 VAC ignition module (Series 35-60) Different series, for 24 VAC appliances. Use only if your old control reads 35-605959-223. Fenwal 35-605959-223 Ignition Module — Replacement

Which units this applies to

  • LED codes, specifications, lockout behavior and troubleshooting: Fenwal Series 35-70 120 VAC direct spark ignition controls, per Fenwal 35-70-02.
  • Part: any appliance whose existing control is labeled 35-705506-023.

Scope: Fenwal 35-70 controls are fitted by many equipment manufacturers, and the appliance's own manual governs its sequence, venting and safety switches. This article covers the control as Fenwal documents it. We do not decode the individual option digits of 35-705506-023 here. Match the full number on the old control. Our listing gives the part as a direct spark ignition control. Values above come from Fenwal 35-70-02.

Before you order

Read the part number on the label of the part you are removing and have the unit's full model and serial number from the rating plate. If the number on your old part is not one of the numbers listed above, or anything about the unit looks different from what is described here, contact us or email help@totalhvacparts.com with the model, serial and old part number and we will check it before you order.

Frequently Asked Questions

What do 3 flashes mean on a Fenwal 35-70?

Ignition lockout fault. The control did not prove flame within its trial(s) for ignition and has closed the gas valve.

How do I reset a Fenwal 35-70 lockout?

Set the thermostat below ambient, or remove 120 VAC power for 5 seconds. Automatic-reset versions retry after one hour if heat is still called for.

What flame current does a 35-70 need?

Fenwal 35-70-02 gives a minimum flame sense current of 1.0 µA DC.

Can I use any 35-70 control as a replacement?

No. TFI time, pre-purge, inter-purge, number of trials and reset type are set by the part number, and Fenwal asks for the lockout recovery method to be specified when ordering. Match the full number on your old control.

Sources

Safety: gas-fired equipment must be serviced by qualified personnel only. Shut off the gas supply and lock out / tag out electrical power before opening the unit, unplugging connectors or handling controls and motors.