A Daikin F3 code means the discharge pipe got too hot, or the board thinks it did. Daikin's service manuals point to three likely causes: a bad discharge pipe thermistor, a refrigerant-side problem (low charge, closed stop valve, failed electronic expansion valve or coil), or a bad outdoor board. SiUS281811EA (SkyAir RZR/RZQ TA) and DAMA-SM-21-001 (FTK/FTX AXVJU wall-mount) both start with a resistance check of the discharge pipe thermistor. Replacement thermistors such as 2425775 are covered below.

What does F3 mean on a Daikin unit?

Manual Name of F3 How it is detected
SiUS281811EA, p.262 (RZR/RZQ TA, all outdoor units) Discharge pipe temperature abnormality "The discharge pipe temperature rises to an abnormally high level." or "The discharge pipe temperature rises suddenly."
DAMA-SM-21-001, p.74 (FTK/FTX AXVJU) Discharge pipe temperature control The compressor stops when the discharge pipe thermistor reads above the limit. The error clears when the temperature drops back, and if it repeats the system shuts down.

DAMA-SM-21-001 gives the limits by model size (p.74) and the reset rule: "Continuous run for about 60 minutes without any other error".

Model (DAMA-SM-21-001) Compressor stops above Error clears below
09, 12 110.0°C (230.0°F) 88.0°C (190.4°F)
18, 24 110.0°C (230.0°F) 95.0°C (203.0°F)

What do the two manuals list as causes?

SiUS281811EA (p.262) DAMA-SM-21-001 (p.74)
Defective discharge pipe thermistor (R2T) Defective discharge pipe thermistor (or the outdoor heat exchanger or outdoor temperature thermistor)
Disconnection of discharge pipe thermistor (R2T) Defective electronic expansion valve or coil
Defective outdoor unit PCB Refrigerant shortage; water mixed in refrigerant; defective stop valve
Defective outdoor unit PCB

On the SkyAir units, the remote controller can also show a sub code. The error code table in SiUS281811EA (p.191) lists F3-01 as "Discharge pipe temperature too high" with "Stop valve closed" and "Refrigerant undercharged" as causes, and the measures "Open the stop valve" and "Check the amount of refrigerant and recharge the unit."

How do you troubleshoot F3 on SkyAir RZR/RZQ?

Turn off the power switch before you plug or unplug any connector. The manual warns that parts may be damaged. The SiUS281811EA chart (p.262) runs in this order:

  1. Read the discharge pipe temperature when the unit stops on the error. If it is higher than 120°C (248°F), the chart points to the refrigerant system: "Short of refrigerant, compressor failure, etc. refrigerant system failure."
  2. If it is not that high, check the sensor. Unplug the discharge pipe thermistor from the outdoor unit PCB and measure its resistance with a multimeter.
  3. Compare the reading with CHECK 11 (pp.301-303). If it does not match, replace the discharge pipe thermistor (R2T).
  4. If the thermistor is normal, replace the outdoor main PCB (A1P).

CHECK 11 lists the RZR/RZQ discharge pipe thermistor (R2T) as Type G. Selected Type G values from the table (p.303):

Temperature Type G resistance
25°C (77°F) 231.4 kΩ
50°C (122°F) 78.29 kΩ
100°C (212°F) 13.06 kΩ
120°C (248°F) 7.131 kΩ

The manual marks this data as "for reference purpose only."

How do you troubleshoot F3 on FTK/FTX wall-mount units?

DAMA-SM-21-001 (p.74) runs three checks before it calls the board:

  1. Check No. 01, thermistors (p.87): the discharge pipe, outdoor heat exchanger and outdoor temperature thermistors. Replace any that read out of range. The F3 page (p.74) notes: "When replacing the defective thermistor(s), replace the thermistor as ASSY."
  2. Check No. 12, electronic expansion valve (p.88). Check the connector. Cycle power and listen for the valve's latching sound. If there is no sound, unplug it and check continuity between pins 5-1 to 5-4 (5P connector) or 6-1 to 6-5 (6P connector). No continuity means the coil is faulty. If continuity is good, the manual calls the outdoor unit PCB (main PCB) faulty.
  3. Check No. 14, refrigerant line (p.90). First check whether the discharge pipe thermistor has come out of its holder, and refit it if so. Then check for refrigerant leaks.
  4. If all three pass, replace the outdoor unit PCB (main PCB).

On these units, all three outdoor thermistors are 20 kΩ at 25°C (77°F), resistance type A, ±5% (p.87). The coil is a CAM-M012DM (5P, 5 wires) on 09/12 and a DPFX07-274 (6P, 6 wires) on 18/24 (p.88).

Field practice, not from the manual: a discharge thermistor that has slipped off the pipe, or lost its insulation, reads cooler than the pipe. That gives the opposite of an F3, so look at mounting when the reading and the pipe temperature do not agree.

Parts that fix it

Component Role Link
Discharge pipe thermistor Replace when the resistance check fails. The listing title does not name a model, so match the part number on your old thermistor or your unit's parts list. Daikin Applied 2425775 — Thermistor
Electronic expansion valve coil Replace when Check No. 12 finds no continuity. DAMA-SM-21-001 names the wall-mount coils CAM-M012DM (09/12) and DPFX07-274 (18/24); this listing does not name a model, so use it only if the number matches your old coil or parts list. Daikin Applied 2254074 — Coil/elec Exp Valve

More sensors and coils: Daikin Parts for VRV Units. If the code is J3 (a shorted or open discharge thermistor) rather than F3, see Daikin C4, C9, J3, J5, J6, H9 error codes. For EEV coil codes see Daikin L5 and E9 errors.

Which units this applies to

  • SkyAir outdoor units RZR18/24/30/36/42/48TAVJU and RZQ18/24/30/36/42/48TAVJU (SiUS281811EA)
  • Wall-mount inverter splits FTK09-24AXVJU / RK09-24AXVJU and FTX09-24AXVJU / RX09-24AXVJU (DAMA-SM-21-001)

Scope: The limits, thermistor types and checks above come from these two manuals only. Other Daikin families use different thermistor curves. The SkyAir R2T is a Type G sensor (231.4 kΩ at 25°C), while the wall-mount discharge thermistor is 20 kΩ at 25°C. Do not use one family's values on the other.

Before you order

Write down the outdoor unit model and serial number and the part number printed on the old thermistor or coil. Note whether the code is F3 or J3. Contact us or email help@totalhvacparts.com and we will check the number against our listings.

Frequently Asked Questions

What does F3 mean on a Daikin heat pump?

It is a discharge pipe temperature error. SiUS281811EA calls it "Discharge pipe temperature abnormality" and DAMA-SM-21-001 calls it "Discharge pipe temperature control". In both, the reading comes from the discharge pipe thermistor.

Is F3 always a bad thermistor?

No. On SkyAir RZR/RZQ, if the discharge pipe is above 120°C (248°F) when the unit stops, SiUS281811EA points to the refrigerant system rather than the sensor. Sub code F3-01 lists a closed stop valve and low charge.

What should a Daikin discharge pipe thermistor read?

It depends on the family. SiUS281811EA lists the RZR/RZQ R2T as Type G, 231.4 kΩ at 25°C (77°F). DAMA-SM-21-001 lists the FTK/FTX outdoor discharge thermistor as 20 kΩ at 25°C, ±5%.

How long until an F3 clears on a Daikin wall-mount unit?

DAMA-SM-21-001 gives the reset condition as "Continuous run for about 60 minutes without any other error". If the error repeats, the system shuts down.

Sources