On Daikin FTX/RX AXVJU wall-mount heat pumps, EA is "Four way valve abnormality". The board sees indoor coil temperatures that do not fit the mode it is running, so it suspects the reversing valve did not shift. Daikin's DAMA-SM-21-001 service manual (pp.85-86) checks things in this order: the coil and harness, a 500-2300 Ω coil resistance check, the board's coil output, the thermistors, the refrigerant line, and the valve body last. The parts at the end of that chart are the four-way valve coil, such as 4009532, and the valve body.
What triggers EA?
DAMA-SM-21-001 (p.85) says the indoor air, indoor heat exchanger, outdoor temperature and outdoor heat exchanger thermistors "are checked to see if the function within their normal ranges in the operating mode." The error is set when one of these conditions "continues over 10 minute after operating 5 minutes":
| Mode | Condition (as printed, p.85) |
|---|---|
| Cooling / dry | (room temp. − indoor heat exchanger temp.) < −5°C (23°F) |
| Heating | (indoor unit heat exchanger temp. − room temp.) < −5°C (23°F) |
In plain terms: in cooling the indoor coil should be colder than the room, and in heating it should be warmer. If it stays the wrong way round, EA is set. (The manual prints "23°F" next to −5°C. As a temperature difference, 5°C is a 9°F difference; the 23°F figure is a straight temperature conversion.)
What can cause it?
- Connector in poor contact
- Thermistor defective
- Outdoor unit PCB defective
- Four way valve coil or harness defective
- Four way valve defective
- Foreign substance mixed in refrigerant
- Insufficient gas
That list is the manual's "Supposed Causes" (p.85). A bad thermistor is on it because EA is judged from temperatures alone: one bad sensor can look like a valve that did not shift.
How do you troubleshoot EA step by step?
Turn off the power switch before you plug or unplug any connector. The DAMA-SM-21-001 chart (p.86) runs in this order:
- Is the four-way valve coil disconnected or loose? If yes, correct the coil.
- Is the harness disconnected? If yes, reconnect it.
- Check the coil and harness for continuity. Unplug the harness and measure across it. If the resistance is not about 500-2300 Ω, replace the four-way valve coil.
- Check No. 13, the switching output (p.89). If NG, replace the outdoor unit PCB (main PCB).
- Is any thermistor disconnected? If yes, reconnect it.
- Check No. 01, thermistors (p.87). Replace any that are out of range.
- Check No. 14, refrigerant line (p.90): refrigerant shortage, water mixed in, stop valve.
- If everything passes, replace the four-way valve ("defective or dust-clogged").
How do you check the four-way valve output (Check No. 13)?
From DAMA-SM-21-001, p.89:
| Item | What the manual says |
|---|---|
| Coil state by mode | Cooling / Dry / Defrost: not energized. Heating: energized. |
| Test | Turn the power off and on again, then start heating operation. |
| Board output | Voltage at S80 should be 208-230 VAC with the compressor on. If not, replace the outdoor unit PCB (main PCB). |
| Coil | Disconnect the coil and check continuity. If the resistance is not 500-2300 Ω, replace the four-way valve coil. |
| Coil and output both good | Replace the four-way valve. |
What should the thermistors read?
Check No. 01 (p.87): unplug the thermistor assembly from the PCB and measure across its pins.
| Thermistor | Type | Resistance at 25°C (77°F) |
|---|---|---|
| Room temperature (indoor) | B (±2%) | 10 kΩ |
| Indoor heat exchanger | B (±2%) | 10 kΩ |
| Outdoor temperature | A (±5%) | 20 kΩ |
| Outdoor heat exchanger | A (±5%) | 20 kΩ |
The p.87 table also lists values from −20°C to 50°C. Examples: 18.3 kΩ and 39.99 kΩ at 10°C (50°F), and 4.1 kΩ and 7.176 kΩ at 50°C (122°F). Both columns are headed "Room temperature thermistor" on the printed page. Our reading, not Daikin's wording: the column that reads 10.0 kΩ at 25°C matches type B, and the one that reads 20.00 kΩ matches type A.
Field practice, not from the manual: if the coil reads good and S80 has voltage in heating, you can often hear or feel the valve shift when the coil is energized. A valve that never shifts, with a good coil and output, matches the manual's last step: replace the valve. That is a brazing job with refrigerant recovery.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Four-way valve coil | Replace when the coil is outside 500-2300 Ω. The listing does not name a model, so match the number on your old coil. | Daikin Applied 4009532 — Coil, Four-Way Valve |
| Four-way valve coil | Another Daikin four-way valve coil. Match the part number on your coil. | Daikin Applied 4005910 — Coil, Four-Way Valve |
| Four-way valve coil assembly | Coil assembly; match the part number on your coil. | Daikin Applied 6025174 — Four Way Valve Coil Assembly |
| Four-way valve body | The chart's last step, when coil, output, thermistors and refrigerant line all check good. Confirm the number against your unit's parts list. | Daikin Applied 1946976 — Four Way Reversing Valve Body |
More coils and valves: Daikin Parts for VRV Units. If the code is H9 or J6 (an open or shorted outdoor thermistor), see Daikin C4, C9, J3, J5, J6, H9 error codes.
Which units this applies to
- Daikin FTX09/12/18/24AXVJU indoor units with RX09/12/18/24AXVJU outdoor units (heat pump), per DAMA-SM-21-001
- The same manual also covers cooling-only FTK/RK AXVJU pairs. The EA page does not limit the code by model; our reading is that, as a four-way valve check, it concerns the heat pump models.
Scope: The resistance window, S80 voltage and thermistor values come from DAMA-SM-21-001 only. Other Daikin families (SkyAir, VRV) have their own codes and checks for the four-way valve; use their service manuals.
Before you order
Write down the indoor and outdoor model and serial numbers and the part number on the old coil. Note your resistance reading. Contact us or email help@totalhvacparts.com to match the coil or valve.
Frequently Asked Questions
What does EA mean on a Daikin mini split?
On FTX/RX AXVJU wall-mount units, DAMA-SM-21-001 lists EA as "Four way valve abnormality". The indoor coil temperature did not move the way it should for the mode for over 10 minutes, after 5 minutes of operation.
What should a Daikin four-way valve coil read?
DAMA-SM-21-001 gives about 500-2300 Ω across the coil. Outside that range, replace the coil.
Is the four-way valve coil energized in cooling or heating?
Per DAMA-SM-21-001 (p.89), the coil is energized in heating and not energized in cooling, dry and defrost. S80 should show 208-230 VAC in heating with the compressor on.
Can a bad sensor cause an EA error?
Yes. EA is judged from the room and coil thermistors, and the manual lists a defective thermistor and poor connector contact as causes. Check them with Check No. 01 before replacing the valve.
Sources
- Daikin DAMA-SM-21-001, Service Manual, Inverter Split Wall Mounted Type FTK(X) Series (pp.13, 85-87, 89-90)
- Live product titles for the listings above, read from our catalog
Heat pumps carry line voltage and pressurized refrigerant, and replacing a valve body involves brazing. Service should be performed only by qualified personnel, following Daikin's service manual and your site's lockout/tagout procedures.