A Daikin F6 code does not mean the same thing on every unit. On SkyAir RZR/RZQ TA outdoor units, SiUS281811EA lists F6 as "Refrigerant overcharged". On FTK/FTX AXVJU wall-mount units, DAMA-SM-21-001 lists it as "High pressure control in cooling". On both, a thermistor that reads wrong can cause the code. On the wall-mount units, the outdoor fan motor and the expansion valve coil are also on the list. Find out which family you have, then use that manual's checks below.
Which F6 do you have?
| Family | Manual | F6 means | Judged from |
|---|---|---|---|
| SkyAir RZR/RZQ18-48TAVJU outdoor units | SiUS281811EA, p.263 | Refrigerant overcharged | Outdoor air, heat exchanger deicer and liquid pipe temperatures, during a check operation |
| FTK/RK and FTX/RX 09-24 AXVJU wall-mount | DAMA-SM-21-001, p.75 | High pressure control in cooling | Outdoor heat exchanger thermistor, in cooling |
SkyAir RZR/RZQ: what does "refrigerant overcharged" mean?
SiUS281811EA (p.263) says that during a check operation, the unit calculates the refrigerant amount from the outdoor temperature, heat exchanger deicer temperature and liquid pipe temperature. "If the calculated amount exceeds the normal amount by 30%, too much refrigerant has been added." The manual adds: "(Adding only slightly more than the normal amount of refrigerant may also cause F6 to be displayed)".
Supposed causes: refrigerant overcharge; disconnection of the outdoor air, heat exchanger deicer or liquid pipe thermistor; or a defect in one of them. The error code table (p.191) gives sub code F6-02, which lists "Too much refrigerant charged" and "Stop valve closed". The measures are to open the stop valve and to check the amount of refrigerant and recharge.
SkyAir F6 checks (SiUS281811EA, p.263):
- Check the mounting of the outdoor air thermistor, heat exchanger deicer thermistor and liquid pipe thermistor. If any is not fitted correctly, install it correctly.
- Unplug the three thermistors from the outdoor unit PCB and measure their resistance with a multimeter.
- Compare against CHECK 11 (pp.301-302). If one is out, replace that thermistor.
- If they are all normal, rectify the overcharge.
| Thermistor (CHECK 11, p.301) | Symbol | Type | Reading at 25°C (77°F), p.302 |
|---|---|---|---|
| Outdoor air | R1T | E | 20.0395 kΩ |
| Heat exchanger deicer | R4T | A | 19.94 kΩ |
| Liquid pipe | R7T | A | 19.94 kΩ |
Wall-mount FTK/FTX: what does "high pressure control in cooling" mean?
DAMA-SM-21-001 (p.75): in cooling, high-pressure control (operation halt, frequency drop, and so on) kicks in when the outdoor heat exchanger thermistor goes above limit A. It clears below limit B.
| Model | A (trips above) | B (clears below) |
|---|---|---|
| 09, 12 | 59.0°C (138.2°F) | 52.0°C (125.6°F) |
| 18, 24 | 60.0°C (140.0°F) | 51.0°C (123.8°F) |
Supposed causes: installation space not large enough, dirty outdoor heat exchanger, defective outdoor fan motor, defective stop valve, defective electronic expansion valve or coil, defective outdoor heat exchanger thermistor, defective outdoor unit PCB.
Wall-mount F6 checks (DAMA-SM-21-001, pp.75-76):
- Check No. 17, installation (p.91). Check the air suction and discharge clearances, short-circuited discharge air, a very dirty outdoor coil, and blocked airflow or opposing wind. Fix by moving or turning the unit or cleaning the coil. If nothing is wrong, check that the outdoor temperature is within the operating range.
- Check No. 19, outdoor fan (p.92). If the fan is not running, check whether the fan motor lead connector is disconnected and reconnect it. If it is connected, go to Check No. 16, the rotation pulse check on the outdoor PCB. The F6 chart's NG result is to replace the outdoor fan motor or reconnect its leads.
- Check No. 18, discharge pressure (p.91). Is the stop valve open? Is the connecting pipe deformed? Are the air filter or the indoor or outdoor heat exchanger dirty? The F6 chart's NG result is to replace the stop valve.
- Check No. 12, expansion valve (p.88). Check the connector and listen for the latching sound at power-up. Check continuity on pins 5-1 to 5-4 (5P) or 6-1 to 6-5 (6P). No continuity means the coil is faulty. The chart's NG results are to replace the valve or coil, or the outdoor PCB.
- Check No. 01, outdoor heat exchanger thermistor (p.87). It should read 20 kΩ at 25°C (77°F), type A, ±5%. If NG, replace it as an assembly.
- If all pass, replace the outdoor unit PCB (main PCB).
Field practice, not from the manual: on a wall-mount unit, look at the outdoor fan and coil first. A fan that is not turning, or a matted coil, raises the outdoor coil temperature that F6 is judged from.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Liquid pipe thermistor | A liquid pipe thermistor (R7T on SkyAir) is one of the three sensors the overcharge check reads. The listing does not name a model, so match the part number on your old sensor. | Daikin Applied 063151J — Thermistor (For Liquid Line) |
| Air thermistor | The SkyAir outdoor air sensor is R1T. This listing does not name a model, so use it only if the number matches your old sensor. | Daikin Applied 6018704 — Thermistor (Air) |
| Outdoor DC fan motor | Wall-mount F6: replace when Check No. 19 / No. 16 fails. Match the number on your motor. | Daikin Applied 4015261 — DC Fan Motor |
| Electronic expansion valve coil | Wall-mount F6: replace when Check No. 12 finds no continuity. Match your coil's number. | Daikin Applied 2254050 — Coil/elec Exp Valve |
More parts: Daikin Parts for VRV Units. If you also see E7 (outdoor fan), read Daikin A6 and E7 errors. For a high pressure switch trip, read Daikin E3 and E4 errors.
Which units this applies to
- F6 = refrigerant overcharged: RZR/RZQ18/24/30/36/42/48TAVJU SkyAir outdoor units (SiUS281811EA)
- F6 = high pressure control in cooling: FTK/RK and FTX/RX 09/12/18/24 AXVJU wall-mount units (DAMA-SM-21-001)
Scope: Each meaning, threshold and check above belongs to the manual it is quoted from. Do not use the SkyAir overcharge logic on a wall-mount unit, or the reverse. Other Daikin families may use F6 differently; check the service manual for your model.
Before you order
Write down the outdoor model and serial number and the part number on the old sensor, motor or coil. Contact us or email help@totalhvacparts.com and we will match it.
Frequently Asked Questions
Does Daikin F6 mean the system is overcharged?
On SkyAir RZR/RZQ TA units, yes: SiUS281811EA lists F6 as "Refrigerant overcharged", found during a check operation. On FTK/FTX AXVJU wall-mount units it means high pressure control in cooling, judged from the outdoor heat exchanger thermistor.
Can a bad thermistor cause F6?
Yes, on both. SiUS281811EA lists a disconnected or defective outdoor air, deicer or liquid pipe thermistor. DAMA-SM-21-001 lists a defective outdoor heat exchanger thermistor.
At what temperature does a Daikin wall-mount unit show F6?
DAMA-SM-21-001 gives 59.0°C (138.2°F) for 09/12 models and 60.0°C (140.0°F) for 18/24 models, read at the outdoor heat exchanger thermistor in cooling.
Why does F6 show after I added only a little refrigerant?
SiUS281811EA notes that on SkyAir units, "Adding only slightly more than the normal amount of refrigerant may also cause F6 to be displayed".
Sources
- Daikin SiUS281811EA, Service Manual, SkyAir RZR/RZQ TA series (pp.191, 263, 301-302)
- Daikin DAMA-SM-21-001, Service Manual, Inverter Split Wall Mounted Type FTK(X) Series (pp.13, 57, 75-76, 87-88, 91-92)
- Live product titles for the listings above, read from our catalog
Outdoor units carry line voltage, inverter capacitors and pressurized refrigerant. Service should be performed only by qualified personnel, following Daikin's service manual for your unit and your site's lockout/tagout procedures.