On an LG Multi V 5, CH23 (shown as 231, 232 or 233) means the outdoor unit saw an out-of-range voltage on the inverter compressor DC link: below 50 V, or above 550 V on 208-230V units and 1,000 V on 460V units, for at least 250 μs. The LG MULTI V 5 Outdoor Unit Service Manual (Error No. 23, p.148) blames a capacitor that is not working or out of range, a disconnected DC link, or a damaged capacitor on the inverter driver board. If the supply and DC link wiring check good, the inverter PCB LG lists for ARUM096, 121, 192, 216 and 241 BTE5 units is LG EBR88279008 Inverter PCB Assembly – Multi V 5 outdoor unit.
What does CH23 mean on an LG Multi V 5?
| Item | What the manual says (Error No. 23, p.148) |
|---|---|
| Display | 231 master, 232 slave 1, 233 slave 2 |
| Description | Low DC voltage sensed at the outdoor unit inverter compressor DC link |
| Shut-off condition | DC link below 50 V (208-230V and 460V units), or above 550 V (208-230V units) or 1,000 V (460V units), for a minimum of 250 μs |
| Causes | Capacitor not working properly, or capacitor voltage out of range (high or low); disconnected DC link; damaged capacitor on the inverter driver board |
The last digit tells you which outdoor unit raised it, so a 232 on a three-module system sends you to slave 1, not the master.
What should the input and DC link voltages read?
The checkpoint table on the Error No. 23 page (Table 79) and the manual's measurement pages give these values:
| Check | Where | 208-230V system (3P3W, 220V) | 460V system (3P3W, 460V) |
|---|---|---|---|
| Input voltage | R-S, R-T, S-T at the inverter PCB input (p.210) | 220V ± 15% | 460V ± 15% |
| DC link voltage | P-N on the DC link, meter on DC, compressor running (p.212) | 310V ± 20% | 650V ± 20% |
| Bridge diode | P-R,S,T / N-R,S,T, power off | 0.38V ~ 0.7V | 0.38V ~ 0.7V |
| Inverter PCB IGBT module and diodes | Power off (p.214) | 0.38V ~ 0.7V | 0.38V ~ 0.7V |
Table 79 also lists "Converter PCB damaged" as a checkpoint, with an appearance check (good or damaged) and a 5 V / 15 V line check; we could not read a numeric value for the 5 V / 15 V line on this page. Multi V 5 parts lists show no separate converter board, so our reading is that this check applies to the converter section of the inverter PCB.
How do I check CH23 before replacing the inverter board?
- Start at the noise filter. The manual says to start diagnosis at the inverter socket on the outdoor unit noise filter PCB.
- Measure input voltage. Check R-S, R-T and S-T against 220V ± 15% (208-230V units) or 460V ± 15% (460V units). A supply problem has to be fixed before any board is judged.
- Check the DC link wiring. A disconnected DC link is a listed cause. Inspect the DC link leads and their terminals between the boards.
- Measure the DC link with the compressor running. Read P to N on DC and compare with 310V ± 20% or 650V ± 20%.
- Power off and test the semiconductors. Follow the manual's "Checking the Inverter Insulated-Gate Bipolar Transistor Module" and "Checking the Phase Diode Bridge" pages; normal diode readings are 0.38V ~ 0.7V.
- Inspect the board. A damaged capacitor on the inverter driver board is a listed cause. Our reading: if input voltage and wiring are good and the board is damaged or its readings are not normal, the inverter PCB is the part to replace.
- Apply paste. The Error No. 23 page says: "Always apply heat transfer paste to the new inverter PCB heat sink before installing."
Field practice, not from the manual: let the DC link capacitors discharge and confirm zero volts across P and N with your meter before touching the board or its leads.
Which inverter board and line filter fit my unit?
LG's parts-by-model data lists a different inverter PCB and AC line filter by size and voltage:
| Models (LG fit list) | Inverter PCB | AC line filter |
|---|---|---|
| ARUM096, 121, 192, 216, 241 BTE5 | EBR88279008 (LG interchangeable: EBR82376303) | EAM63430904 |
| ARUM072, 144, 168 BTE5 | EBR88279009 | EAM63430903 |
| ARUM096, 121, 192, 216, 241 DTE5 | EBR88279003 (LG interchangeable: EBR80928310) | EAM63430906 |
| ARUM072, 144, 168 DTE5 | EBR88279006 (LG interchangeable: EBR80908606) | EAM63430905 |
LG's parts lists call the input filter "Filter,AC Line" (location W6200 on the ARUM096BTE5). The CH23 page does not list the filter itself as a cause; it is where the manual starts the diagnosis. Replace it only if you find it damaged.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Inverter PCB, ARUM096/121/192/216/241 BTE5 | Damaged capacitor on the inverter driver board is a listed CH23 cause | LG EBR88279008 Inverter PCB Assembly – Multi V 5 outdoor unit |
| Inverter PCB, ARUM072/144/168 BTE5 | Same, smaller BTE5 sizes | LG EBR88279009 Inverter PCB Assembly – Multi V 5 outdoor unit |
| Inverter PCB, ARUM096/121/192/216/241 DTE5 | Same, 460V units | LG EBR88279003 Inverter PCB Assembly – Multi V 5 outdoor unit |
| Inverter PCB, ARUM072/144/168 DTE5 | Same, smaller DTE5 sizes | LG EBR88279006 Inverter PCB Assembly – Multi V 5 outdoor unit |
| AC line filter, ARUM096/121/192/216/241 BTE5 | Where diagnosis starts; replace if damaged | LG EAM63430904 AC Line Filter – Multi V outdoor unit |
| Heat transfer paste | Applied to the new inverter PCB heat sink, per the manual | LG RAC34537401 Heat Transfer Paste for Inverter PCB & Heat Sink Service |
Which units this applies to
- LG Multi V 5 outdoor units ARUM072 through ARUM241, BTE5 (208-230V) and DTE5 (460V).
- Board and filter numbers above are from LG's fit lists; ARWM water-source models appear on some of the same fit lists but are not covered by this manual.
Scope: The code, condition, causes and check values are from the LG MULTI V 5 Outdoor Unit Service Manual, Error No. 23 (p.148), Checking Input Voltage (p.210), Checking Converter DC Link Voltage (p.212) and Checking Inverter PCB in Case of Power Off (p.214). Fits and interchangeable numbers come from LG's parts data on our product pages and model pages. For the full board map, see Which LG Multi V board do I need? For IPM faults, see LG CH21 IPM fault.
Before you order
Read the full model and serial number from the outdoor unit nameplate, note the exact error number shown, including the unit digit, and, if you can, the LG part number printed on the part you are replacing. Fit lists on our product pages follow LG's parts-by-model data. For help matching a part, contact us or email help@totalhvacparts.com with the model, serial, error code and the readings you took.
Frequently Asked Questions
What does error 231 mean on an LG Multi V?
Error No. 23 on the master outdoor unit: the inverter compressor DC link voltage was below 50 V, or above 550 V (208-230V) or 1,000 V (460V), for at least 250 μs. 232 and 233 are slave 1 and slave 2.
What should the DC link read on a Multi V 5?
With the compressor running, the manual gives 310V ± 20% for 220V three-phase units and 650V ± 20% for 460V units, measured P to N on DC.
Does CH23 always mean a bad inverter board?
No. The manual also lists a capacitor out of range and a disconnected DC link, and it starts the check at the noise filter and the input voltage. Replace the board only after those check good.
Is EBR82376303 the same as EBR88279008?
LG lists them as interchangeable both ways for the ARUM096, 121, 192, 216 and 241 BTE5 sizes.
Sources
- LG MULTI V 5 Outdoor Unit Service Manual, LG Electronics U.S.A., Error No. 23 (p.148), Checking Input Voltage in Case of Power On (p.210), Checking Converter DC Link Voltage in Case of Compressor Operating (p.212), Checking Inverter PCB in Case of Power Off (p.214); cited by name and page; no printed form number
- LG parts-by-model and substitute data as shown on our LG model pages (for example ARUM096BTE5) and each product page's fit list
LG Multi V equipment involves line voltage, stored charge in inverter and fan board capacitors, refrigerant under pressure and rotating fans. Service should be performed only by qualified personnel, following LG's service manual for your unit and your facility's lockout/tagout procedures.