On Daikin SkyAir indoor units (FCQ, FTQ, FBQ, FAQ, FHQ with RZR/RZQ TA outdoor units), A9 is "Electronic expansion valve coil abnormality, Dust clogging". It is the indoor unit's own expansion valve, not the outdoor one. Daikin's SiUS281811EA manual (pp.234-235) has you check the valve connection at X7A and measure the coil (CHECK 18, p.308) before anything else. Then it points you to the coil (such as 2433473), the valve body, the relay cables or the indoor main PCB.
What does A9 mean?
SiUS281811EA, p.234 (applies to all indoor models):
| Item | What the manual says |
|---|---|
| Detection | Electronic expansion valve coil conditions are checked via microcomputer. The electronic expansion valve main body is checked for dust clogging via microcomputer. |
| Coil condition | Pin input for electronic expansion valve coil is abnormal when initializing microcomputer. |
| Clogging condition (unit stopped) | R1T − R2T > 8°C (14.4°F), or R2T shows fixed degrees or below. R1T is suction air temperature; R2T is the liquid pipe of the heat exchanger. |
| Supposed causes | Defective electronic expansion valve coil; defective indoor unit main PCB; defective relay cables |
Our reading, not Daikin's wording: if the indoor coil keeps getting colder than the room air while the unit is off, the board reads it as refrigerant still flowing through a valve that should be shut.
What do the A9 sub codes say?
When the BRC1E navigation remote controller is in use, SiUS281811EA (p.210) gives two sub codes:
| Sub code | Description | Diagnosis |
|---|---|---|
| A9-01 | Electronic expansion valve error | There is an error in the electronic expansion valve coil or a connector disconnected. |
| A9-02 | Refrigerant leakage detection error | Refrigerant leaks even if the electronic expansion valve is closed. Replace the electronic expansion valve. |
So A9-01 points to the coil or its connection, and A9-02 points to the valve body.
How do you troubleshoot A9 step by step?
Turn off the power switch before you plug or unplug any connector. The chart on p.235 runs in this order:
- "Power is supplied." The chart's NO branch is "Replace the electronic expansion valve main body." (The first box is printed exactly this way in the manual; we quote it as is.)
- Is the valve connected to X7A on the indoor unit PCB? If not, connect it, shut the power off and restart.
- Check the coil with CHECK 18 (p.308). If the coil is not normal, replace the electronic expansion valve coil.
- Are the relay cables shorted or disconnected? If yes, replace the relay cables.
- If none of the above, and the unit still will not run after a power-off restart, replace the indoor unit main PCB (A1P).
What should the expansion valve coil read (CHECK 18)?
Measure pin to pin at the coil connector (SiUS281811EA, pp.308-309):
| Indoor model | Pins | Reading |
|---|---|---|
| FCQ-TA, FTQ-TA | 1-6, 2-6, 3-6, 4-6 | 35-55 Ω each |
| FBQ-P, FAQ-TA | 1-3 and 2-4 | 300 Ω |
| FBQ-P, FAQ-TA | 1-5 and 2-6 | 150 Ω |
| FHQ-P, FHQ-M | 1-3 and 2-4 | 300 Ω |
| FHQ-P, FHQ-M | 1-5 and 2-6 | 150 Ω |
The wire colours differ by model. On FCQ-TA/FTQ-TA the pins are 1 orange, 2 red, 3 yellow, 4 black, 6 gray. On FBQ-P/FAQ-TA they are 1 white, 2 yellow, 3 orange, 4 blue, 5 red, 6 brown. Our reading: because the coils read so differently (35-55 Ω against 150/300 Ω), do not swap coils between indoor models. Match the part number.
Field practice, not from the manual: a reading of 0 Ω or an open circuit on any winding is a failed coil. If the coil reads correctly and the code is A9-02, the valve itself is the suspect, as the sub code says.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Electronic expansion valve coil | Replace when CHECK 18 is out of range. The listing does not name a model, so match the number on your old coil. | Daikin Applied 2433473 — Coil/el. Expansion Valve |
| Electronic expansion valve coil | Another Daikin EEV coil. Match the part number on your coil. | Daikin Applied 2254050 — Coil/elec Exp Valve |
| Electronic expansion valve coil | Another Daikin EEV coil. Match the part number on your coil. | Daikin Applied 2430474 — Coil/ Electronic Txv |
| Electronic expansion valve (body) | A9-02 (valve leaks while closed) or the chart's "main body" branch. Confirm against your unit's parts list. | Daikin Applied 142054J — Electronic Expansion Valve |
For the outdoor expansion valve code (E9), see Daikin L5 and E9 errors. For indoor thermistor codes C4/C9, see Daikin C4, C9, J3, J5, J6, H9 error codes. More parts: Daikin Parts for VRV Units.
Which units this applies to
- SkyAir indoor units FCQ-TA, FTQ-TA, FBQ-P, FAQ-TA, FHQ-P and FHQ-M, as covered by SiUS281811EA
- Paired with RZR/RZQ18-48TAVJU outdoor units
Scope: The detection rule, sub codes and coil readings are from SiUS281811EA. Other Daikin indoor families (VRV, wall-mount) have their own service manuals and coil values.
Before you order
Write down the indoor model and serial number, the A9 sub code if your remote shows one, your coil readings, and the part number on the old coil or valve. Contact us or email help@totalhvacparts.com to match it.
Frequently Asked Questions
What does A9 mean on a Daikin ceiling cassette or ducted unit?
On SkyAir indoor units, SiUS281811EA lists A9 as "Electronic expansion valve coil abnormality, Dust clogging": a coil input fault at start-up, or signs that refrigerant flows through the closed valve.
How do I test a Daikin indoor EEV coil?
Unplug it and measure pin to pin per CHECK 18. On FCQ-TA and FTQ-TA, pins 1-6, 2-6, 3-6 and 4-6 should read 35-55 Ω. On FBQ-P, FAQ-TA and FHQ, pins 1-3 and 2-4 read 300 Ω and pins 1-5 and 2-6 read 150 Ω.
Coil or valve body: which do I replace?
If the coil reads out of range, replace the coil. Sub code A9-02 ("Refrigerant leaks even if the electronic expansion valve is closed") says to replace the valve itself.
Can a bad board cause A9?
Yes. SiUS281811EA lists a defective indoor unit main PCB as a cause. The chart replaces the PCB last, after the connection, the coil and the relay cables check good.
Sources
- Daikin SiUS281811EA, Service Manual, SkyAir RZR/RZQ TA series (pp.210, 234-235, 308-309)
- Live product titles for the listings above, read from our catalog
Indoor units carry line voltage and refrigerant under pressure. Service should be performed only by qualified personnel, following Daikin's service manual for your unit and your site's lockout/tagout procedures.