Daikin CJ Error: Remote Controller Thermistor or Field Setting?

A Daikin CJ code means the thermistor inside the wired remote controller has opened or shorted. The system keeps running, but the controller can no longer use that sensor for room temperature. Daikin's SkyAir service manual SiUS281811EA (p.251) checks two things first: whether CJ is really there or just noise, and the thermistor field settings 10(20)-2 and 10(20)-6. If both are right, the fix is to replace the remote controller. Daikin's BRC1H71W Madoka has a built-in temperature sensor and is listed for SkyAir FCQ, FHQ, FAQ, FBQ and FTQ indoor units.

What does CJ mean?

Item SiUS281811EA, p.251
Name Remote controller thermistor abnormality
Applicable models All indoor models
Detection "Error detection is carried out by the temperature detected by remote controller thermistor."
Decision "When the remote controller thermistor becomes disconnected or shorted while the unit is running." The error code is displayed but the system operates continuously.
Supposed causes Defective remote controller thermistor; defective remote controller PCB; external factor (noise, etc.)

Why does the remote controller have a thermistor?

SiUS281811EA section 6.1 (p.124) says temperature is controlled by both the remote controller thermistor and the indoor unit's suction air thermistor, when the field setting for the remote controller thermistor is set to Use. Near the set point, the unit fine-tunes with the thermistor nearer to the user. FTQ-TA models do not have a suction air thermistor, so they work differently. The thermistor used is chosen with field setting 10(20)-2 (p.153):

10(20)-2 setting Room temperature is controlled by
01 (factory setting) Remote controller thermistor and suction air thermistor for indoor unit
02 Suction air thermistor for indoor unit
03 Remote controller thermistor

On FTQ-TA models, 02 selects the optional remote sensor thermistor and 03 the remote controller thermistor. Field setting 10(20)-6 (pp.154-155) controls group control: 01 means remote controller thermistor control is not permitted during group control, and 02 means it is permitted. The manual notes that with 02, several indoor units are controlled by one remote controller thermistor, so room temperature might be uneven.

How do you troubleshoot CJ?

Turn off the power switch before you plug or unplug any connector. The CJ chart (p.251):

  1. Clear the error code history. Press and hold the ON/OFF button for 4 seconds or more while the error code is displayed.
  2. Is CJ displayed again? If not, the manual calls it an "External factor other than equipment error" (for example, noise).
  3. Is field setting 10(20)-2 correct? If not, correct it.
  4. Is the remote controller used for group control? If not, replace the remote controller.
  5. If it is group control, is 10(20)-6 set to 02? If not, set 10(20)-6 to 02. If it already is, replace the remote controller.

The manual does not test the remote's thermistor on its own. The thermistor is inside the controller, so a confirmed CJ means a new controller. Field practice, not from the manual: if CJ comes and goes, look for a remote cable run next to line-voltage wiring or a variable-speed drive before you replace anything. The manual lists noise as a cause.

Can I just stop using the remote thermistor?

Yes, on units that have a suction air thermistor. Setting 10(20)-2 to 02 makes the unit use only the indoor unit's suction air thermistor (p.153). That takes the remote's sensor out of control, but it does not repair it. Field practice, not from the manual: use this as a stopgap while a replacement remote is on order, and keep in mind that the suction air thermistor reads the air at the unit, not where people sit.

Parts that fix it

Component Role Link
Wired remote controller Replace when CJ returns after the history is cleared and the field settings are right. SiUS281811EA lists BRC1E73 and BRC2A71 as the wired remotes for these units. Daikin's BRC1H71W submittal data sheet lists the Madoka as compatible with SkyAir FAQ, FBQ, FCQ, FHQ and FTQ indoor units and says "Temperature sensor built-in with configurable offset." Check the indoor unit model before ordering. Daikin Applied BRC1H71W — Madoka Remote Controller
Suction air thermistor If you switch 10(20)-2 to 02, the indoor unit relies on its suction air thermistor alone (a fault there shows as C9). This listing is titled for suction air but does not name a model, so match the number on your old thermistor. Daikin Applied 2258261 — Thermistor (Suction Air)

If the controller shows U5 or U8 instead, see Daikin U5 or U8 Error: Remote Controller Setting, Wiring or Bad PCB?. For indoor thermistor codes (C4, C9 and others), see Daikin C4, C9, J3, J5, J6, H9 Error Codes. More parts: Daikin Parts for VRV Units.

Which units this applies to

  • SkyAir indoor units covered by SiUS281811EA: FCQ, FHQ, FAQ, FBQ and FTQ, paired with RZR/RZQ TA outdoor units
  • Wired remote controllers named in that manual: BRC1E73 and BRC2A71

Scope: Codes, steps and settings come from SiUS281811EA. Remote compatibility comes from the BRC1H71W submittal data sheet. Other Daikin families and controllers can use different settings. Some VRV systems use the Madoka too, but this article covers SkyAir only.

Before you order

Write down the indoor and outdoor model numbers, the model of your current remote, and whether it controls a group. Contact us or email help@totalhvacparts.com and we will confirm the remote for your system.

Frequently Asked Questions

What does CJ mean on a Daikin remote?

CJ is remote controller thermistor abnormality: the thermistor in the wired remote is disconnected or shorted while the unit is running. The system keeps operating (SiUS281811EA, p.251).

How do I clear a CJ error on a Daikin?

Press and hold the ON/OFF button for 4 seconds or more while the code is displayed. If CJ does not return, the manual treats it as an external factor such as noise.

Which field setting controls the Daikin remote thermistor?

Field setting 10(20)-2: 01 uses both the remote and suction air thermistors (factory setting), 02 uses only the suction air thermistor, and 03 uses only the remote controller thermistor.

Does the Daikin Madoka have a temperature sensor?

Yes. The BRC1H71W submittal data sheet lists "Temperature sensor built-in with configurable offset" and lists SkyAir FAQ, FBQ, FCQ, FHQ and FTQ indoor units as compatible.