Daikin A3 Error: Drain Pump, Float Switch or Clogged Drain?

A Daikin A3 code means the indoor unit's drain level control system tripped. Daikin's SM-TS3 code list names it "Drain Level Control System Abnormality" and gives three causes: drain clogging or an upward slope, a defective drain pump, and a defective float switch or short circuit connector. On RZR-TA/RZQ-TA SkyAir systems, service manual SiUS281811EA applies A3 to the FCQ-TA cassette and FBQ-P ducted units, and its checks end at the drain pump, the float switch (S1L), the short circuit connector or the indoor unit main PCB (A1P).

What does the A3 code mean?

Source Code name Supposed causes listed
SM-TS3 (Indoor Unit) "Drain Level Control System Abnormality" "Drain clogging, upward slope, etc."; "Defective drain pump"; "Defective float switch or short circuit connector"
SiUS281811EA, p. 219 "Drain level control system (S1L) abnormality" Defective drain pump; improper drain piping work; drain piping clogging; defective float switch; defective indoor unit PCB; defective short circuit connector on the PCB

The detection method in SiUS281811EA is float switch OFF detection. The decision condition is "When the float switch goes OFF when conditions for rise of water level are not met" (p. 219). In plain terms, the float has lifted and opened the circuit, or the board reads it as open. That can be real water in the pan, or a switch, connector or board fault that only looks like water.

Which indoor units does this apply to?

In SiUS281811EA, the A3 section lists FCQ-TA and FBQ-P as the applicable models. Other Daikin indoor units can show A3 too, since SM-TS3 is a general list, but use the A3 section of your own model's service manual for the test values.

How do you check an A3 before replacing parts?

The A3 flowchart (SiUS281811EA, p. 220) runs in this order. Turn off the power before connecting or disconnecting connectors.

  1. Is the drain pump mechanism connected? If the unit has no drain pump, the chart checks that the short circuit connector is fitted to the indoor unit PCB (connect it if not), then checks its continuity. No continuity: replace the short circuit connector. Continuity good: replace the indoor unit main PCB (A1P).
  2. Is a drain pump connected to the indoor unit PCB? If not, connect the drain pump.
  3. Does the drain pump work after restarting operation? If it does not, set the unit to "emergency" and check the voltage at the drain pump connector (table below). Voltage in accordance with the criteria: replace the drain pump. Voltage not in accordance: replace the indoor unit main PCB (A1P).
  4. If the pump runs, is the drain water level abnormally high? If yes, the chart calls it a drain system abnormality. Clear the drain line and check the piping. SM-TS3 lists clogging and upward slope; SiUS281811EA also lists improper drain piping work.
  5. If the level is normal, is the float switch (S1L) connected to the indoor unit PCB? If not, connect it, check that drain water is being drained and that the drain pipe is not clogged.
  6. Isolate the float switch. Remove the float switch, attach a jumper connector and restart. If the error does not come back, replace the float switch (S1L). If the error is displayed again, replace the indoor unit main PCB (A1P).

Which connectors and voltages does the manual give?

Indoor unit Float switch / short circuit connector Drain pump connector Drain pump voltage
FCQ-TA X15A X10A 13 VDC
FBQ-P X15A X25A 220-240 VAC

Source: SiUS281811EA, p. 220 (notes under the flowchart). The manual also notes: "If a PCB that does not have X15A connector detects A3 error code, the PCB is defective." So a board without X15A that still shows A3 points to the board, not the pump.

What is the related AF code?

AF, "Drain level above limit" (p. 236), also applies to FCQ-TA and FBQ-P. It is detected when the float switch changes from ON to OFF while the compressor is not operating. Unlike A3, the error is displayed but the system keeps operating. Listed causes are a drain pipe installation error, a defective float switch, a defective indoor unit PCB, a defective connector connection and a defective drain pump. The checks cover drain-up height, horizontal pipe length, trap installation, connector X15A, the drain pump kit connection, pump operation, and whether water builds up or flows back when the pump stops.

Parts that fix it

Component Role Link
Drain pump Named cause in SM-TS3 and SiUS281811EA; the chart says replace it if it does not run but its connector voltage meets the criteria. The listing title does not name a model; match the part number on your old part or your unit's parts list. Daikin Applied 2013437 — Condensate Drain Pump
Drain pump assembly Alternate drain pump listing. The listing title does not name a model; match the part number on your old part or your unit's parts list. Daikin Applied 5011011 — Drain Pump Assembly
Float switch (S1L) Named cause; the chart says replace it if the A3 does not return with a jumper connector in place of the float switch. The listing title does not name a model; match the part number on your old part or your unit's parts list. Daikin Applied 139502J — Float Switch
Drain hose Drain piping clogging and upward slope are listed causes. The listing title does not name a model; match the part number on your old part or your unit's parts list. Daikin Applied 2539335 — Drain Hose
More VRV and ductless parts Indoor PCBs and other drain parts Daikin Parts for VRV Units

Which units this applies to

  • A3 meaning and causes: any Daikin unit covered by the SM-TS3 list (its heading names RA, SkyAir, VRV, PA and Heat Reclaim Ventilator).
  • Test steps, connectors and voltages: FCQ-TA and FBQ-P indoor units in SiUS281811EA, paired with RZR18-48TAVJU(A) or RZQ18-48TAVJU(A) outdoor units.

Scope: The connector names and the 13 VDC and 220-240 VAC values come from SiUS281811EA and apply only to the indoor units it lists. Other indoor families use other connectors and pump voltages. The parts above are linked by their live product titles; the titles do not confirm fit for a given model.

Before you order

Write down the indoor unit model and serial number from the nameplate, and the part number printed on the old drain pump or float switch. For other Daikin codes, see our guide to reading Daikin error codes. Send those details to contact us or help@totalhvacparts.com and we will help match the part.

Frequently Asked Questions

What does Daikin error code A3 mean?

Daikin's SM-TS3 list defines A3 as "Drain Level Control System Abnormality". The listed causes are drain clogging or upward slope, a defective drain pump, and a defective float switch or short circuit connector.

Is an A3 always a bad drain pump?

No. On FCQ-TA and FBQ-P units, SiUS281811EA lists the drain pump, the drain piping, the float switch, the short circuit connector and the indoor unit PCB. Check the pan level and drain line first, then the pump voltage and the float switch.

What voltage should the Daikin drain pump get?

For the units in SiUS281811EA, the manual gives 13 VDC at X10A on FCQ-TA and 220-240 VAC at X25A on FBQ-P (p. 220). Use your own model's manual for other units.

What is the difference between A3 and AF?

Both involve the float switch on FCQ-TA and FBQ-P units. AF, "Drain level above limit", is detected when the float switch changes from ON to OFF while the compressor is not operating, and the system keeps operating while it is displayed.

Sources

Daikin inverter systems carry line voltage, high-voltage DC on the inverter circuit, pressurized refrigerant and rotating fans. Service should be performed only by qualified personnel, following the Daikin service manual for your model and your site's lockout/tagout procedures.