Skip to content

LG Multi V CH10: Indoor Fan Motor Error — Motor, Connector or Indoor Board?

On an LG Multi V indoor unit, CH10 is the indoor unit BLDC fan motor communications error: the LG MULTI V 5 Outdoor Unit Service Manual (Error No. 10, p.142) sets it when the "indoor BLDC fan motor feedback signal has been absent for at least 50 seconds." The causes are a disconnected or failed motor connector, a locked indoor fan motor and an indoor PCB error. If the motor fails the manual's check, the replacement depends on the indoor unit type; for example, LG lists LG 4681A20172Z DC Fan Motor, Indoor – Multi V and mini split system for many ARNU 4-way ceiling cassettes.

What does CH10 mean on an LG Multi V indoor unit?

The indoor PCB drives a brushless DC (BLDC) fan motor and reads back its speed signal. When that feedback is missing for at least 50 seconds, the indoor unit stops the fan and shows CH10. The fault can be the motor, its connector or the board, so it pays to test before ordering.

What causes CH10?

  1. Fan motor connector disconnected, removed or malfunctioning.
  2. Indoor fan motor locked.
  3. Indoor PCB error.

How do I troubleshoot CH10?

The manual warns: "Check the fan motor connection to the PCB only when power is OFF." Then:

  1. Connection. Is the fan motor connector installed properly on the indoor PCB? If not, connect it properly.
  2. Free rotation. With power off, turn the blower or fan by hand. A motor that binds or will not turn is locked.
  3. Motor test. Is the fan motor operating normally? The manual judges this by resistance between motor connector pins, measuring pins 1, 5, 6 and 7 against pin 4 and comparing with its table (±10%). If the readings are outside the table, replace the indoor fan motor.
  4. Board. If the motor tests normal, replace the indoor unit PCB. After a PCB replacement, the manual says to perform the Auto Addressing procedure and input the central control address.

The last step matters on a Multi V job: plan the auto addressing and central control setup into the repair. For which indoor board to buy, see LG Multi V indoor main PCB vs communication PCB.

Which indoor fan motor do I need?

The motor is specific to the indoor unit type and chassis. Three common examples from LG's parts data:

Indoor unit type (examples from LG fit list) LG fan motor
4-way ceiling cassette: ARNU073TAA4 through ARNU483TAA4, ARNU243TMA4, ARNU363TNC4, ARNU423TMC4 LG 4681A20172Z DC Fan Motor, Indoor – Multi V and mini split system
Ducted: ARNU073L1G4 to ARNU243L3G4 and ARNU CEA4 / CEU4 / CFA4 / CFU4 sizes LG 4681A20198G DC Fan Motor, Indoor – Multi V indoor unit
Wall mount: ARNU053SJR4 to ARNU153SJS4 and others LG EAU62004010 DC Fan Motor, Indoor – Multi V and mini split system

These are examples, not the full list. Each product page carries LG's full fit list, and LG model pages such as ARNU243TAA4 show the motor location on the exploded view. For other chassis, see LG Multi V indoor fan motors and blower wheels by unit type.

Parts that fix it

Component Role in CH10 Link
Indoor fan motor, 4-way cassette Replace when the motor is locked or fails the pin-to-pin test. LG 4681A20172Z DC Fan Motor, Indoor – Multi V and mini split system
Indoor fan motor, ducted (L and CE/CF chassis) As above. LG 4681A20198G DC Fan Motor, Indoor – Multi V indoor unit
Indoor fan motor, wall mount As above. LG EAU62004010 DC Fan Motor, Indoor – Multi V and mini split system

Which units this applies to

  • LG Multi V indoor units connected to Multi V outdoor units (ARNU and ZRNU models), using the Multi V 5 service manual's Error No. 10 procedure.
  • Some of the same motors are listed for LG single-zone and multi-zone indoor units; check the fit list on the product page.

Scope: The code, the 50-second condition, causes and checks are from the LG MULTI V 5 Outdoor Unit Service Manual, Error No. 10 (p.142), which covers indoor unit errors reported in a Multi V 5 system. Motor fits come from LG's parts data on our product pages. The manual's pin-resistance values are not reproduced here; use the table in your manual.

Before you order

Read the full model and serial number from the outdoor unit nameplate (and the indoor unit nameplate for indoor faults), note the exact error number shown, including the unit digit, and, if you can, the LG part number on the part you are replacing. Fit lists on our product pages follow LG's parts-by-model data. For help matching a part, contact us or email help@totalhvacparts.com with the model, serial, error code and the readings you took.

Frequently Asked Questions

What does CH10 mean on an LG indoor unit?

Error No. 10 is the indoor unit BLDC fan motor error: the fan motor feedback signal has been absent for at least 50 seconds.

Is CH10 always a bad fan motor?

No. The manual lists a disconnected or failed motor connector, a locked fan motor and an indoor PCB error. It tests the motor before telling you to replace the PCB.

What do I do after replacing the indoor PCB for CH10?

The manual says to perform the Auto Addressing procedure and input the central control address.

Which fan motor fits an ARNU243TAA4 cassette?

LG's parts data lists 4681A20172Z for the ARNU243TAA4 and the other ARNU TAA4 cassette sizes from 073 to 483.

Sources

  • LG MULTI V 5 Outdoor Unit Service Manual, LG Electronics U.S.A., Error No. 10 (p.142); cited by name and page; LG publishes no printed form number for this manual; read page by page, not linked
  • LG parts-by-model data and fit lists on the 4681A20172Z, 4681A20198G and EAU62004010 product pages and the ARNU243TAA4 model page

LG Multi V equipment involves line voltage, stored charge in inverter and fan board capacitors, refrigerant under pressure and rotating fans. Service should be performed only by qualified personnel, following LG's service manual for your unit and your facility's lockout/tagout procedures.