LG Multi V 5 CH193 or CH194: Fan PCB Heat Sink Overtemperature or Sensor Error — Which Fan Board?

On an LG Multi V 5, CH193 means the outdoor unit fan PCB heat sink got too hot and the system shut off, and CH194 means the fan heat sink temperature sensor reads open or shorted. The LG MULTI V 5 Outdoor Unit Service Manual lists a defective fan PCB assembly as a cause of CH193, after wiring, fan motor and overload checks. On ARUM096 to ARUM241 BTE5 units the fan board LG lists is LG EBR88279203 Fan PCB Assembly – Multi V 5 outdoor unit.

What do CH193 and CH194 mean?

The error code table in the LG MULTI V 5 Outdoor Unit Service Manual (p.134) lists both codes for the master and each slave outdoor unit:

Error Display (master / slave 1 / slave 2) Meaning (error code table, p.134)
193 1931 / 1932 / 1933 Excessive increase in outdoor unit fan heatsink temperature
194 1941 / 1942 / 1943 Outdoor unit fan heatsink temperature sensor error

CH193 is a real high temperature. CH194 is a sensor fault: the Error No. 194 page (p.199) gives the detail as "Disconnection or short circuit of outdoor unit fan heatsink temperature sensor."

At what temperature does CH193 trip?

The manual gives two different figures, so read the one that applies to your copy:

Where in the manual Trip condition as printed
Error code table, p.134 Fan heatsink temperature is >203°F
Error No. 193 page, p.198 Fan PCB heat sink temperature is >194°F

A second copy of the same manual shows the same two values on the same pages. Neither page gives a Celsius value. Either way, CH193 means the board's heat sink is running hotter than LG allows, and the checks are the same.

What causes CH193?

The Error No. 193 page (p.198) lists four causes:

  1. Fan PCB IPM connection is not correct.
  2. Outdoor unit fan motor is not operating correctly.
  3. Outdoor unit fan PCB assembly is defective.
  4. Overload operation: a clogged pipe, a blocked fan, a defective EEV or refrigerant overcharge.

How do I troubleshoot CH193?

The flowchart on p.198 asks four questions in this order. Work through them before you order a board:

  1. Was the system installed correctly? If not, recheck power and installation. The check items include clogged or damaged pipes, blocked outdoor or indoor unit fans, the EEV assembly connection and operation, refrigerant pressure, and power wiring.
  2. Is the fan PCB IPM connected correctly? If not, check the fan PCB connections and reconnect or rewire.
  3. Is the outdoor unit fan motor operating normally? If not, check fan motor operation or whether the fan has locked up, and fix that first. See our guide to LG CH67 and CH79 outdoor fan errors.
  4. Is the fan PCB assembly correct? The last check item is to replace the fan PCB assembly if it is faulty.

Our reading: p.198 prints these four questions in this order, plus the action boxes "Recheck power and installation.", "Check fan connection installation.", "Check fan PCB connection. Reconnect or rewire if errors are found.", "Check the outdoor unit fan motor operation, or if the fan has locked up." and "Replace fan PCB assembly." Which action follows each answer is our reading of the flowchart layout, so confirm the routing on the printed page.

Field practice, not from the manual: compare the fan heat sink temperature in LGMV with the outdoor air temperature and the fan speed at the time of the trip. A trip on a mild day with the fan turning freely points more at the board or its mounting than at load.

How do I check CH194, the fan heat sink sensor?

The Error No. 194 page (p.199) gives three causes: the sensor connection, a sensor that is shorted or open, and a defective outdoor unit PCB. Its flowchart prints the boxes below; the pairing of each answer with an action is our reading of the layout:

  1. "Are the temperature sensor connections correct?" If not: "Check and fix connections."
  2. "Is the temperature sensor resistance value normal?" If not: "Replace sensor."
  3. If the connections and resistance are both normal: "Replace outdoor unit PCB."

The error code table (p.134) lists these check items beside the sensor error rows, including 1941 to 1943: check the connection on the outdoor unit PCB, check for a shorted or open thermistor, check for 12 V DC between 12 V and GND (red to black) and for 5 V DC, then check the signal to GND (white to black) and use the correct chart. The Error No. 194 page (p.199) notes that sensor resistance varies with temperature (±5% tolerance).

The CH194 page says only "outdoor unit PCB". It does not name the board. The heat sink it monitors is the fan PCB heat sink (CH193's wording), so the fan PCB is the board we would check first; that link is our reading, not LG's text.

Parts that fix it

The fan PCB numbers below come from LG's parts-by-model fit lists on each product page. Pick the board by your outdoor unit model.

Component Role in CH193 / CH194 Link
Fan PCB, ARUM096 to ARUM241 BTE5 Primary fix when the fan PCB assembly is defective. LG lists EBR79669809 as interchangeable. LG EBR88279203 Fan PCB Assembly – Multi V 5 outdoor unit
Fan PCB, ARUM096 to ARUM241 DTE5 Same role on the DTE5 models. LG lists EBR79669811 as interchangeable. LG EBR88279204 Fan PCB Assembly – Multi V 5 outdoor unit
Fan PCB, ARUM072BTE5 Fan board for the 6-ton BTE5. LG lists EBR79669810 as interchangeable and suggests it. LG EBR88279206 Fan PCB Assembly – Multi V 5 outdoor unit
Fan PCB, ARUM072DTE5 Fan board for the 6-ton DTE5. LG lists EBR79669806 as interchangeable. LG EBR88279202 Fan PCB Assembly – Multi V 5 outdoor unit

For the other fan board codes (CH75, CH77, CH106, CH107), see LG Multi V fan PCB errors. CH62 is the matching code for the inverter board heat sink: see LG CH62 inverter heat sink overtemperature.

Which units this applies to

  • LG Multi V 5 outdoor units covered by the LG MULTI V 5 Outdoor Unit Service Manual, including ARUM072 to ARUM241 BTE5 and DTE5.
  • Fan board fits as listed by LG: EBR88279203 on ARUM096, 121, 144, 168, 192, 216 and 241 BTE5; EBR88279204 on the same sizes in DTE5; EBR88279206 on ARUM072BTE5; EBR88279202 on ARUM072DTE5.

Scope: Code meanings, trip values, causes and check order come from the LG MULTI V 5 Outdoor Unit Service Manual: error code table p.134, Error No. 193 p.198 and Error No. 194 p.199. Board numbers, fits and interchangeable numbers come from LG's parts-by-model data on our product pages. Other Multi V generations may use different codes and boards.

Before you order

Read the full model and serial number from the outdoor unit nameplate, note the exact error number shown, including the unit digit (1931 is the master, 1932 slave 1, 1933 slave 2), and, if you can, the LG part number printed on the board you are replacing. Browse the LG Parts collection, or contact us or email help@totalhvacparts.com with the model, serial, error code and the readings you took.

Frequently Asked Questions

What does CH193 mean on an LG Multi V 5?

The outdoor unit fan PCB heat sink temperature rose too high and the system shut off. The manual's error table gives the trip as above 203°F; the Error No. 193 page gives above 194°F.

What is the difference between CH193 and CH194?

CH193 is a real overtemperature at the fan heat sink. CH194 means the fan heat sink temperature sensor is disconnected or shorted.

Is CH193 always a bad fan board?

No. The manual lists fan PCB IPM connection, fan motor problems and overload operation (clogged pipe, blocked fan, defective EEV, overcharge) before a defective fan PCB assembly.

Which fan PCB fits my ARUM096BTE5?

LG lists EBR88279203 for ARUM096 to ARUM241 BTE5 and EBR79669809 as interchangeable with it. DTE5 models use EBR88279204.

What does 1932 mean?

The last digit is the unit: 1 is the master, 2 is slave 1 and 3 is slave 2. So 1932 is CH193 on slave unit 1.

Sources

  • LG MULTI V 5 Outdoor Unit Service Manual, LG Electronics U.S.A. (no printed form number): error code table p.134, Error No. 193 p.198, Error No. 194 p.199; cited by name and page, not linked
  • LG parts-by-model data shown on our LG product pages (fit lists and interchangeable numbers)

LG Multi V equipment involves line voltage, stored charge in inverter and fan board capacitors, refrigerant under pressure and rotating fans. Service should be performed only by qualified personnel, following LG's service manual for your unit and your facility's lockout/tagout procedures.