On an LG Multi V 5, CH67 means the outdoor fan "has locked up" and CH79 means the fan motor failed to start on its first position sensing. The LG MULTI V 5 Outdoor Unit Service Manual (Error No. 67, p.174 and Error No. 79, p.178) lists the fan motor first for both, followed by wrong U, V, W wiring, a defective fan PCB and, for CH67, snow or blocked airflow. If the motor tests bad, the outdoor fan motor LG lists for ARUM096 to ARUM241 BTE5 units is LG EAU43080032 DC Fan Motor, Outdoor – Multi V outdoor unit; other sizes and the 460V units use different motors.
What do CH67 and CH79 mean?
| Error | Display (master / slave 1 / slave 2) | Meaning in the manual |
|---|---|---|
| 67 | 671 / 672 / 673 | Outdoor unit fan has locked up |
| 79 | 791 / 792 / 793 | Outdoor unit fan operation error: the fan motor is experiencing first position sensor failure |
What causes CH67 and CH79?
Error No. 67 causes:
- Fan motor is defective, or the assembly is not correct.
- Fan motor connection is wrong (U, V, W output).
- Rotation reversed after the RPM target was achieved.
- Fan PCB assembly is defective.
- Airflow is blocked by heavy snowfall.
Error No. 79 causes:
- Fan motor is defective, or the assembly is not correct.
- Fan motor is disconnected at the U, V, W output.
- Fan PCB is defective.
How do I test an LG Multi V 5 outdoor fan motor?
Both flowcharts follow the same path. With power off and locked out:
- Obstruction and assembly. Confirm the fan turns freely and the motor and blade are assembled correctly. If the unit is covered in thick snow, the manual says to remove it before operating the system.
- Winding resistance. Measure resistance between each pair of motor output terminals (U-V, V-W, W-U) and compare with the manual's table for your frame size. The three pairs should read alike.
- Insulation. Check insulation resistance from U, V and W to the pipe. The Error No. 79 page prints the limit as over 100M (no unit shown).
- Wiring. Check the wiring between the fan motor and the fan PCB, and confirm the U, V, W wire colors match the board's output terminals. Look for damaged or disconnected wires.
- Fan PCB. If the motor and wiring pass, check the fan PCB assembly and its IPM. Replace the fan PCB if it is at fault.
- If nothing is found, recheck power and installation.
A motor that is stiff or noisy by hand, reads open or unbalanced between phases, or fails insulation is the part to replace. A motor that passes all three checks points you to the fan PCB.
Which outdoor fan motor does my Multi V 5 use?
LG's parts data splits the Multi V 5 outdoor fan motor by size and voltage. The ratings below are from LG's own item descriptions on each product page.
| Models (LG fit list) | LG fan motor | LG item rating |
|---|---|---|
| ARUM096, 121, 144, 168, 192, 216, 241 BTE5 | LG EAU43080032 DC Fan Motor, Outdoor – Multi V outdoor unit | 900W, DC310V |
| ARUM072BTE5 | LG EAU43080022 DC Fan Motor, Outdoor – Multi V outdoor unit | 1500W, DC310V |
| ARUM096 to ARUM241 DTE5 |
LG EAU43080051 DC Fan Motor, Outdoor – Multi V outdoor unit LG EAU43080021 DC Fan Motor, Outdoor – Multi V 5 outdoor unit |
900W, DC540V (both listed for these models) |
| ARUM072DTE5 | LG EAU43080025 DC Fan Motor, Outdoor – Multi V 5 outdoor unit | 1200W, DC540V |
Parts that fix it
| Component | Role in CH67 / CH79 | Link |
|---|---|---|
| Outdoor fan motor, ARUM096-241BTE5 | Cause 1 for both codes. | LG EAU43080032 DC Fan Motor, Outdoor – Multi V outdoor unit |
| Outdoor fan motor, ARUM072BTE5 | Cause 1 for both codes. | LG EAU43080022 DC Fan Motor, Outdoor – Multi V outdoor unit |
| Outdoor fan motor, 460V DTE5 | Cause 1 for both codes. | LG EAU43080051 DC Fan Motor, Outdoor – Multi V outdoor unit |
| Fan PCB, ARUM096-241BTE5 | Replace when the motor and wiring test good. | LG EBR88279203 Fan PCB Assembly – Multi V 5 outdoor unit |
Which units this applies to
- LG Multi V 5 outdoor units ARUM072 through ARUM241, BTE5 (208-230V) and DTE5 (460V).
- EAU43080032 also appears in LG's fit list for ZRUM096BTE6 and ZRUM144BTE6.
Scope: Codes, causes and checks are from the LG MULTI V 5 Outdoor Unit Service Manual, Error No. 67 (p.174) and Error No. 79 (p.178). Motor and board fits and ratings come from LG's parts-by-model data and item descriptions on our product pages and model pages such as ARUM096BTE5 and ARUM096DTE5. For indoor fan motors see LG Multi V indoor fan motors and blower wheels.
Before you order
Read the full model and serial number from the outdoor unit nameplate (and the indoor unit nameplate for indoor faults), note the exact error number shown, including the unit digit, and, if you can, the LG part number on the part you are replacing. Fit lists on our product pages follow LG's parts-by-model data. For help matching a part, contact us or email help@totalhvacparts.com with the model, serial, error code and the readings you took.
Frequently Asked Questions
What does CH67 mean on an LG Multi V?
On Multi V 5, Error No. 67 means the outdoor unit fan has locked up. 671, 672 and 673 identify the master, slave 1 and slave 2 units.
Can snow cause CH67?
Yes. The manual lists airflow blocked by heavy snowfall as a cause and says to remove thick snow before operating the system.
Is CH79 the motor or the board?
The manual lists the fan motor, a disconnected U, V, W output and the fan PCB. Test winding resistance, insulation and wiring first; if they pass, check the fan PCB.
Do 208-230V and 460V Multi V 5 units use the same fan motor?
No. LG lists EAU43080032 for ARUM096-241BTE5 and EAU43080051 or EAU43080021 for ARUM096-241DTE5, with separate motors for the 072 size.
Sources
- LG MULTI V 5 Outdoor Unit Service Manual, LG Electronics U.S.A., Error No. 67 (p.174), Error No. 79 (p.178); cited by name and page; LG publishes no printed form number for this manual; read page by page, not linked
- LG parts-by-model data for Multi V 5 ARUM models as shown on our LG model pages (for example ARUM096BTE5) and each product page's fit list
- LG item descriptions (ratings) on the EAU43080032, EAU43080022, EAU43080051, EAU43080021 and EAU43080025 product pages
LG Multi V equipment involves line voltage, stored charge in inverter and fan board capacitors, refrigerant under pressure and rotating fans. Service should be performed only by qualified personnel, following LG's service manual for your unit and your facility's lockout/tagout procedures.