On an LG Multi V 5, CH62 means the outdoor unit shut down on "high temperature at the outdoor unit inverter PCB heat sink": the LG MULTI V 5 Outdoor Unit Service Manual (Error No. 62, p.172) sets it when heatsink temperature is above 257°F. The manual's causes are a bad IGBT/IPM connection, a malfunctioning outdoor fan motor, a defective inverter PCB assembly and overload operation, so check installation, the inverter PCB IPM connection and the outdoor fan before replacing the board. On ARUM096, 121, 192, 216 and 241 BTE5 units the inverter board LG lists is LG EBR88279008 Inverter PCB Assembly – Multi V 5 outdoor unit, and the manual calls for heat transfer paste on any new inverter board.
What does CH62 mean?
| Display | Unit | Condition |
|---|---|---|
| 621 | Master | Inverter PCB heat sink above 257°F |
| 622 | Slave 1 | Inverter PCB heat sink above 257°F |
| 623 | Slave 2 | Inverter PCB heat sink above 257°F |
CH62 is a temperature trip. It is different from CH21 (IPM overcurrent) even though both point at the inverter board.
What causes CH62?
- Inverter PCB IGBT/IPM connection is incorrect.
- Outdoor unit fan motor is malfunctioning.
- Outdoor unit inverter PCB assembly is defective.
- Overload operation: a clogged pipe, a blocked fan, a defective EEV or refrigerant overcharge.
How do I troubleshoot CH62?
The Error No. 62 flowchart checks, in order:
- Installation. Is the installation correct? If not, work through the overload checks below.
- Board connection. Is the inverter PCB IPM connection correct? If not, check the inverter PCB connections.
- Outdoor fan. Is the outdoor fan motor operating normally? If not, check fan motor operation and whether it is locked up.
- Board. Is the inverter PCB assembly correct? If not, replace it; if it is, recheck power and installation.
The manual's overload checks for the same code:
- Check piping for clogs or damage.
- Check whether outdoor or indoor unit airflow is blocked.
- Check EEV connections, assembly and operation.
- Check refrigerant pressure.
- Check power wiring for proper connection or damage.
What about the heat sink paste?
The Error No. 62 page says to always apply heat transfer paste to the new inverter PCB heat sink before installing, and the manual's "Replacing the Inverter PCB Heat Sink" page (p.209) gives the steps: wipe and gently scrape the old paste off both the inverter PCB heat sink plate and the outdoor unit heat sink plate without damaging them, evenly coat the inverter PCB heat plate with silicone-based electronic heat sink paste so all applicable areas are covered, keep foreign matter off the paste, and tighten the board screws with a JIS screwdriver (a standard Phillips screwdriver will strip them) without overtightening. More detail is in LG inverter PCB heat sink paste: when RAC34537401 is required.
Parts that fix it
| Component | Role in CH62 | Link |
|---|---|---|
| Inverter PCB, ARUM096/121/192/216/241BTE5 | Cause 3. LG lists EBR82376303 as interchangeable. | LG EBR88279008 Inverter PCB Assembly – Multi V 5 outdoor unit |
| Inverter PCB, ARUM072/144/168BTE5 | The inverter board LG lists for these sizes. | LG EBR88279009 Inverter PCB Assembly – Multi V 5 outdoor unit |
| Heat transfer paste | Required on the new inverter PCB heat sink per the manual. | LG RAC34537401 Heat Transfer Paste for Inverter PCB & Heat Sink Service |
| Outdoor fan motor, ARUM096-241BTE5 | Cause 2: a malfunctioning or locked outdoor fan. | LG EAU43080032 DC Fan Motor, Outdoor – Multi V outdoor unit |
| Outdoor fan motor, ARUM072BTE5 | The fan motor LG lists for the ARUM072BTE5. | LG EAU43080022 DC Fan Motor, Outdoor – Multi V outdoor unit |
460V DTE5 units use different boards: LG lists EBR88279003 for ARUM096/121/192/216/241DTE5 and EBR88279006 for ARUM072/144/168DTE5. Their fan motors also differ from the BTE5 units.
Which units this applies to
- LG Multi V 5 outdoor units ARUM072 through ARUM241, BTE5 (208-230V) and DTE5 (460V).
- EBR88279008 also appears in LG's fit list for ARWM BAS5 water-source units; the CH62 values above are from the air-source Multi V 5 manual.
Scope: The code, threshold, causes and checks are from the LG MULTI V 5 Outdoor Unit Service Manual, Error No. 62 (p.172) and the inverter PCB heat sink page (p.209). Board and fan motor fits come from LG's parts-by-model data on our product pages and model pages such as ARUM096BTE5. For overcurrent faults on the same board, see LG CH21 IPM fault.
Before you order
Read the full model and serial number from the outdoor unit nameplate (and the indoor unit nameplate for indoor faults), note the exact error number shown, including the unit digit, and, if you can, the LG part number on the part you are replacing. Fit lists on our product pages follow LG's parts-by-model data. For help matching a part, contact us or email help@totalhvacparts.com with the model, serial, error code and the readings you took.
Frequently Asked Questions
What temperature sets CH62 on an LG Multi V 5?
The manual's Error No. 62 condition is heatsink temperature above 257°F at the outdoor unit inverter PCB heat sink.
Can a bad outdoor fan cause CH62?
Yes. A malfunctioning outdoor fan motor is cause 2, and the flowchart checks whether the fan motor is operating or locked before it reaches the board.
Do I need new paste when I replace the inverter board?
Yes. The manual says to apply heat transfer paste to the new inverter PCB heat sink before installing, after removing old paste from both plates.
Which inverter board fits an ARUM144BTE5?
LG's parts data lists EBR88279009 for ARUM072, 144 and 168 BTE5. ARUM096, 121, 192, 216 and 241 BTE5 use EBR88279008.
Sources
- LG MULTI V 5 Outdoor Unit Service Manual, LG Electronics U.S.A., Error No. 62 (p.172), Replacing the Inverter PCB Heat Sink (p.209); cited by name and page; LG publishes no printed form number for this manual; read page by page, not linked
- LG parts-by-model data for Multi V 5 ARUM models as shown on our LG model pages (for example ARUM096BTE5) and each product page's fit list
LG Multi V equipment involves line voltage, stored charge in inverter and fan board capacitors, refrigerant under pressure and rotating fans. Service should be performed only by qualified personnel, following LG's service manual for your unit and your facility's lockout/tagout procedures.