Skip to content

LG Multi V CH75, CH77, CH106, CH107: Outdoor Fan PCB Errors and When to Replace the Fan Board

On an LG Multi V 5, CH75, CH77, CH106 and CH107 all point at the outdoor fan drive: the fan current sensor, fan overcurrent, the fan PCB's IPM and the fan DC link. The LG MULTI V 5 Outdoor Unit Service Manual (pp.176, 177, 187 and 189) lists a defective fan PCB assembly as a cause of every one of them, along with the fan motor, wiring and the 15 V / 13.5 V DC supply. If the supply and motor test good, the fan PCB LG lists for ARUM096 to ARUM241 BTE5 units is LG EBR88279203 Fan PCB Assembly – Multi V 5 outdoor unit.

What do the Multi V 5 fan board codes mean?

Error Display Meaning and condition in the manual
75 751 / 752 / 753 Fan CT sensor error: the MICOM offset of fan motor phase current is not 2.5V ± 0.3V
77 771 / 772 / 773 Outdoor unit fan overcurrent: fan current above 10 A on 208-230V units or above 5 A on 460V units
106 1061 / 1062 / 1063 Fan PCB IPM error: the outdoor unit fan IPM overcurrent protection circuit was activated
107 1071 / 1072 / 1073 Fan DC link low voltage: below 50 V for at least 250 μs (208-230V and 460V units)
87 871 / 872 / 873 Outdoor unit fan PCB EEPROM error: EEPROM check sum error at initial operation after power is supplied (Error No. 87, p.181)

The last digit is the unit: 1 master, 2 slave 1, 3 slave 2.

What causes each code?

  • CH75: input voltage not correct (not 15V), defective fan PCB, disconnected or shorted power wiring, defective inverter PCB.
  • CH77: overload operation, defective fan motor, defective fan PCB, fan motor connector not inserted, condenser iced up or blocked.
  • CH106: overload (clogged piping, blocked fan, defective EEV, overcharge), incorrect fan motor assembly (disconnected or shorted coil, damaged insulation), defective fan PCB, or power to the inverter 1 and/or 2 terminals on the main PCB below 13.5 V DC.
  • CH107: wrong wiring between the inverter PCB and fan PCB, defective fan PCB, poor reactor terminal contact, defective or disconnected DC link wiring, defective diode bridge, or a damaged capacitor on the inverter driver board. The Error No. 107 page also gives a fan PCB DC link supply below 140 V (208-230V units) or below 380 V (460V units) as a condition.
  • CH87: EEPROM with a bad connection or inserted incorrectly, a different EEPROM version, or a fan PCB assembly damaged after power was turned on. The flowchart checks that the EEPROM is inserted correctly (socket and EEPROM facing the same direction) before the fan PCB assembly.

How do I check the fan PCB before replacing it?

  1. Power and installation. Recheck power and installation first; every flowchart starts or ends here.
  2. Supply to the fan drive. For CH75, check the DC 15V input power on the inverter compressor PCB and its wiring. For CH106, confirm the inverter 1 and inverter 2 terminals on the main PCB are not below 13.5 V DC.
  3. Fan motor. Confirm the motor is not locked, then check winding resistance between each output terminal and insulation from U, V, W to pipe (printed as over 100M). The manual lists a disconnected or shorted coil and damaged insulation as CH106 causes.
  4. Wiring. Check the U, V, W colors match the board, the cable between the inverter compressor PCB and fan PCB, the fan PCB connections and the fan PCB-to-heat sink assembly (CH106).
  5. DC link (CH107). Starting at the inverter socket on the noise filter PCB, check the DC link wiring and contacts and measure the DC link voltage.
  6. Board. If the supply, motor and wiring pass, replace the fan PCB assembly.

If the motor fails these checks, replace it as well as any failed fan PCB; the manual lists both the motor assembly and the fan PCB as CH106 causes.

Which fan PCB does my Multi V 5 use?

Models (LG fit list) LG fan PCB LG interchangeable
ARUM096, 121, 144, 168, 192, 216, 241 BTE5 LG EBR88279203 Fan PCB Assembly – Multi V 5 outdoor unit EBR79669809
ARUM096 to ARUM241 DTE5 LG EBR88279204 Fan PCB Assembly – Multi V 5 outdoor unit EBR79669811
ARUM072BTE5 LG EBR88279206 Fan PCB Assembly – Multi V 5 outdoor unit EBR79669810
ARUM072DTE5 LG EBR88279202 Fan PCB Assembly – Multi V 5 outdoor unit EBR79669806

Parts that fix it

Component Role Link
Fan PCB, ARUM096-241BTE5 Listed cause of CH75, CH77, CH106, CH107. LG EBR88279203 Fan PCB Assembly – Multi V 5 outdoor unit
Fan PCB, ARUM096-241DTE5 Same, 460V units. LG EBR88279204 Fan PCB Assembly – Multi V 5 outdoor unit
Fan PCB, ARUM072BTE5 Same, 072 size. LG EBR88279206 Fan PCB Assembly – Multi V 5 outdoor unit
Outdoor fan motor, ARUM096-241BTE5 Defective or shorted motor (CH77, CH106). LG EAU43080032 DC Fan Motor, Outdoor – Multi V outdoor unit

Which units this applies to

  • LG Multi V 5 outdoor units ARUM072 through ARUM241, BTE5 (208-230V) and DTE5 (460V).

Scope: Codes, conditions and causes are from the LG MULTI V 5 Outdoor Unit Service Manual, Error Nos. 75 (p.176), 77 (p.177), 106 (p.187), 107 (p.189), 87 (p.181) and the Error Code Tables (pp.131-132). Fan PCB fits and interchangeable numbers come from LG's parts data on our product pages and model pages such as ARUM096BTE5. For the full board map, see Which LG Multi V board do I need?

Before you order

Read the full model and serial number from the outdoor unit nameplate (and the indoor unit nameplate for indoor faults), note the exact error number shown, including the unit digit, and, if you can, the LG part number on the part you are replacing. Fit lists on our product pages follow LG's parts-by-model data. For help matching a part, contact us or email help@totalhvacparts.com with the model, serial, error code and the readings you took.

Frequently Asked Questions

What does CH77 mean on an LG Multi V 5?

Outdoor unit fan overcurrent: fan current above 10 A on 208-230V units or 5 A on 460V units. Causes include overload, a defective fan motor or fan PCB, an unplugged motor connector and an iced or blocked condenser.

What does error 1061 mean?

Error No. 106 on the master outdoor unit: the outdoor unit fan IPM overcurrent protection circuit was activated. 1062 and 1063 are slave 1 and slave 2.

Can a low 15 V supply cause a fan board code?

Yes. CH75 lists input voltage not at 15V as a cause, and CH106 lists power to the inverter 1 and 2 terminals on the main PCB below 13.5 V DC.

Is EBR79669809 the same as EBR88279203?

LG's parts data lists them as interchangeable for ARUM096-241BTE5.

Sources

  • LG MULTI V 5 Outdoor Unit Service Manual, LG Electronics U.S.A., Error Nos. 75 (p.176), 77 (p.177), 106 (p.187), 107 (p.189), Error Code Tables (pp.131-132); cited by name and page; LG publishes no printed form number for this manual; read page by page, not linked
  • LG parts-by-model data for Multi V 5 ARUM models as shown on our LG model pages (for example ARUM096BTE5) and each product page's fit list

LG Multi V equipment involves line voltage, stored charge in inverter and fan board capacitors, refrigerant under pressure and rotating fans. Service should be performed only by qualified personnel, following LG's service manual for your unit and your facility's lockout/tagout procedures.

← Greenheck ERV Energy Wheel Not Turning or...Greenheck BSQ Inline Fan Noisy or Vibrati... →