LG Multi V 5 CH150 Discharge Superheat Not Satisfied: Leaking Indoor EEV, Coil or Piping?

On an LG Multi V 5, CH150 means the outdoor unit could not hold enough compressor discharge superheat, which the LG MULTI V 5 Outdoor Unit Service Manual (Error No. 150, p.192) warns is a high possibility of liquid refrigerant flooding back and damaging the compressor. The first cause the manual lists is an indoor unit EEV that is disconnected or short-circuited, so the indoor expansion valve is the first part to check, such as LG MJX65072205 Electronic Expansion Valve Module – Multi V indoor unit on many ARNU indoor models.

What does CH150 mean?

Error Display (master / slave 1 / slave 2) Meaning
150 1501 / 1502 / 1503 Outdoor unit compressor discharge superheat not satisfied

The manual sets these conditions for the code (p.192):

Condition Value in the manual
Mode Cooling only, with all indoor units in cooling. It cannot occur during simultaneous operation.
When the check starts The master unit calculates compressor superheat after at least 10 minutes of compressor operation.
Trip Superheat below 4.8°F (3°C) for 5 minutes
First and second occurrence System shuts down, CH150 shows on zone sensors and central controls, and the outdoor unit restarts on its own. After a restart the system runs 10 minutes to stabilize before it checks again.
Third occurrence Three occurrences within any 1 hour of compressor operation is a Level 3 error. The system stays off until it is restarted manually.

What causes CH150?

Error No. 150 lists three causes:

  1. Indoor unit EEV disconnected or short-circuited.
  2. Defective compressor EEV (large refrigerant leak has occurred).
  3. Defective liquid and/or vapor piping connections.

The manual's footnote describes what an excessive leak through an indoor unit looks like: with that indoor unit off (EEV at 40 pulses), both its piping inlet and outlet temperatures are below 50°F, and you can hear loud refrigerant flow noise. In other words, an indoor EEV that should be nearly shut is letting liquid through.

How do I troubleshoot CH150?

The flowchart on p.192 prints these question boxes:

  1. "Is there an indoor unit that is leaking a large amount of refrigerant?" (the footnote above defines the sign: pipes below 50°F with the unit off and loud flow noise)
  2. "Is the EEV coil assembly correct?"
  3. "Are the EEV connections correct?"
  4. "The compressor EEV or circuit leaking?"

And these action boxes: "Check liquid and vapor piping connections.", "Re-assemble or replace the EEV coil.", "Connect EEV connections.", "Replace the compressor EEV or EEV assembly." and "Replace EEV assembly."

Our reading: a leaking indoor unit leads to the piping check, a bad coil assembly to re-assembling or replacing the coil, bad connections to reconnecting, and coil and connections that are both correct to "Replace EEV assembly." The branch layout is hard to read in the copies we used, so confirm the yes/no routing on the printed page.

The manual does not say which valve it means by "compressor EEV", so treat the indoor unit checks above as the starting point and follow the printed flowchart for the rest.

Field practice, not from the manual: with the system in cooling and one indoor unit at a time switched off, watch that unit's pipe temperatures and EEV pulses in LGMV. The unit whose pipes stay cold with its EEV at 40 pulses is the one to open up.

Is it a different code from high discharge temperature?

Yes. CH150 is the opposite problem to CH32 and CH33: too little superheat (liquid floodback) instead of a discharge line that is too hot. For CH32 and CH33, and the outdoor EEV coil and body, see LG CH32 or CH33 high discharge temperature.

Parts that fix it

LG lists the indoor expansion valve by model. The numbers below come from LG's parts-by-model data on our product pages. Match the number to your indoor unit model, or to the label on the old valve. Our guide to LG Multi V indoor thermistors and EEVs explains how LG labels them.

Component Role in CH150 Link
Indoor EEV module (item spec ending 500) Primary fix for a leaking or failed indoor EEV. Listed on many ARNU TRD4, CEA4/CEU4, L1G4, B1G2/B3G2/B3G4 and BHA models, among others. LG lists the older number AJU36719706 as interchangeable; our parts data marks AJU36719706 obsolete and replaced by MJX65072205. LG MJX65072205 Electronic Expansion Valve Module – Multi V indoor unit
Indoor EEV module (item spec ending 800) Indoor EEV listed on ARNU073TUC4 and ARNU073, 093 and 123 TUD4, among others. Not a swap for the 500 version. LG MJX65072201 Electronic Expansion Valve Module – Multi V indoor unit
Indoor valve assembly, larger units Listed on ARNH K2A4/K3A4 and ARNU B8A4/B8Z4 models, among others. LG lists AJU32452003 as a one-way substitute for it. LG AJU36719728 Valve Assembly – Multi V system

Which units this applies to

  • LG Multi V 5 outdoor units covered by the LG MULTI V 5 Outdoor Unit Service Manual (ARUM BTE5 and DTE5), running in cooling.
  • The indoor units connected to them. EEV part numbers depend on the indoor model: check the fit list on each product page or the ARNU073TUD4 model page as an example.

Scope: The code meaning, trip values, restart rules, causes and check items come from the LG MULTI V 5 Outdoor Unit Service Manual, Error No. 150 (p.192). Indoor EEV numbers, fits and alternatives come from LG's parts-by-model data on our product and model pages. The manual does not name indoor EEV part numbers.

Before you order

Note the exact code including the unit digit, then find the indoor unit that is leaking through. Read that indoor unit's full model and serial number from its nameplate, and the number on the old valve if you can. Browse the LG Parts collection, or contact us or email help@totalhvacparts.com with the outdoor and indoor models, serials and the pipe temperatures you measured.

Frequently Asked Questions

What does CH150 mean on an LG Multi V 5?

Compressor discharge superheat not satisfied: superheat stayed below 4.8°F (3°C) for 5 minutes in cooling, which the manual says means liquid may be flooding back to the compressor.

Why does CH150 come back after the unit restarts itself?

The outdoor unit restarts on its own after the first and second trips. Three trips within any 1 hour of compressor operation make it a Level 3 error that needs a manual restart.

How do I find which indoor unit is causing CH150?

The manual describes the sign: with the indoor unit off (EEV at 40 pulses), its inlet and outlet pipes are both below 50°F and there is loud refrigerant flow noise.

Can CH150 happen in heating?

No. The manual says it can only occur in cooling with all indoor units in cooling, not during simultaneous operation.

Is MJX65072205 the same as MJX65072201?

No. Both are LG indoor EEV modules, but their item specs end in 500 and 800 and LG lists them on different models. MJX65072205 is interchangeable with AJU36719706.

Sources

  • LG MULTI V 5 Outdoor Unit Service Manual, LG Electronics U.S.A. (no printed form number): Error No. 150 p.192 and error code table; cited by name and page, not linked
  • LG parts-by-model data shown on our LG product and model pages (fit lists, item specs and alternatives)

LG Multi V equipment involves line voltage, refrigerant under pressure and rotating fans. Opening the refrigerant circuit to replace an EEV requires recovery and evacuation. Service should be performed only by qualified personnel, following LG's service manual for your unit and your facility's lockout/tagout procedures.