WaterFurnace 7 Series Hot Water Generator Pump Not Running: E15, Switch, Breaker or the 24P501A01 Pump?

If the hot water generator (desuperheater) pump on a WaterFurnace 7 Series is not running, check the setup before the pump. The pump only runs when the cabinet HWG switch is on, HWG is enabled in the AID Tool, and the water is below the set point (E15 means the limit was reached). Then check the 5 amp pump breaker and for an air-bound pump. If the pump itself has failed, both WaterFurnace IM2700ANA (7 Series 700A11 Installation Manual) and WaterFurnace OMW7-0018W (7 Series 700A11 R-454B Operation & Maintenance) list it as 24P501A01 — WaterFurnace Desuperheater Pump 1/25 HP-230V-TB4-BRZ-UP15-18B5.

Is the hot water generator actually enabled?

Two settings have to be on: the cabinet switch is taped off at the factory, and HWG has to be enabled in the AID Tool:

  • Cabinet switch. IM2700ANA (p.14): "The hot water generator switch is taped in the disabled position at the factory." The parts list calls it "Rocker Switch - HWG ON/OFF".
  • AID Tool. "Use an AID Tool to enable HWG and select the desired water heating set point." The path is Setup, then AXB Setup. "Selectable set points are 100°F – 140°F in 5°F increments (default 130°F)."

The start-up checklist (p.47) says the pump switch stays "OFF" unless piping is completed and air has been purged, so a new or recently serviced unit may simply never have been switched on.

Why does the pump stop on its own? (E15)

The 7 Series control shuts the pump off when the tank is hot enough. IM2700ANA (p.30): "An alert will occur when the hot water input temperature is at or above the set point (130°F default)" for 30 continuous seconds. "This alert will appear as an E15 on the AID Tool and the hot water pump de-energizes." Pump operation resumes on the next compressor cycle, or after 15 minutes of continuous compressor operation in the same thermostat demand cycle.

Code Name Lockout Reset Description (IM2700ANA p.37)
E15 Alarm-HotWtr No Auto HW over limit or logic lockout. HW pump deactivated.
E14 CriticAXBSnsrErr Yes Hard or Soft Sensor Err for EEV or HW

The Aurora fault LED shows "Alarm - Hot Water" as flash code 15 (p.43). E15 is an alert, not a failure: if the water at the HWL sensor really is at set point, the pump is doing what it should.

The manual adds a cooling-mode limit (pp.30–31): because hot gas temperature depends on loop temperature in cooling, "loop temperatures may be too low to allow proper heating of water," and the control "will monitor water and refrigerant temperatures to determine if conditions are satisfactory for heating water." So the pump may stay off in cooling with a cold loop.

How do I check the hot water limit thermistor?

The control reads the tank-side water temperature with the HWL thermistor, listed as "HWL Thermistor-Pink (AXB P17)" (p.59). It is a 10k thermistor. Compare its resistance with the manual's table (p.50, "Thermistor Resistance (10k Ohm) for FP1, FP2, HWL, LWT and LLT") at the actual water temperature:

Temperature Resistance range (ohms)
50°F 20570–19230
77°F 10310–9688
104°F 5480–5172
122°F 3700–3504
140°F 2554–2424

Our explanation, not the manual's: a sensor that reads hotter than the water (resistance too low) would trip E15 early and keep the pump off. A sensor fault on the AXB can also show as E14.

How do I troubleshoot a pump that will not run?

  1. Read the AID Tool. Look for E15 or E14, and confirm HWG is enabled in AXB Setup.
  2. Check the cabinet HW switch. It must be on. The parts list gives it as 13P607A01.
  3. Check the pump breaker. The parts list includes "Pump Circuit Breaker - 5 amp, 250v 19P583-01". The electrical data table (p.22) gives the HWG pump FLA as 0.4 A.
  4. Check the pump output. The wiring schematic (p.41, Figure 1, "Optional Internal Hot Water Generation Pump Wiring Schematic") shows the DHW pump and the cabinet HW switch, with the note "COM NO K6 Relay Connects to L2 and NO on AXB Board".
  5. Purge air. Turn the venting (burping) screw in the center of the pump "two (2) turns open" until water drips out, wait until all air is purged, then tighten. "CAUTION: Never operate the HWG circulating pump while dry."
  6. Check the plumbing. Make sure the valves in the HWG circuit are open, and inspect the water heater cold inlet dip tube: "If a check valve is present it must be removed or damage to the hot water generator circulator will occur."
  7. Replace the pump if it has power when called and still does not circulate.

Field practice, not from the manual: with the pump called, measure voltage at the pump leads. Voltage present with no rotation and a hot motor usually means a seized rotor; no voltage points back to the breaker, switch, wiring or AXB relay.

Also note p.54: "Refrigerant tests must be made with hot water generator turned "OFF"."

Parts that fix it

Component Role Link
Hot water generator pump Primary fix when the pump has power but will not circulate. Listed as 24P501A01 for all sizes in both 7 Series manuals. 24P501A01 — WaterFurnace Desuperheater Pump 1/25 HP-230V-TB4-BRZ-UP15-18B5
HWL thermistor (AXB P17) Tank-side water sensor; a bad reading can stop the pump (E15) or set E14. 12P555-04 — WaterFurnace Hot Water Limit Thermistor 7-Series
Pump circuit breaker, 5 A Protects the pump circuit; listed as 19P583-01. 19P583-01 — WaterFurnace Circuit Breaker 5 AMP Legacy 024-070

Which units this applies to

  • WaterFurnace 7 Series 700A11 units with the hot water generator option: R-410A units (IM2700ANA, sizes 036, 048, 060) and R-454B units (OMW7-0018W, sizes 024 to 060, horizontal and vertical).
  • Our 24P501A01 listing also lists other WaterFurnace models; their controls differ, so use their own manuals for setup.

Scope: Setup steps, control logic, alert codes, the thermistor table and wiring notes are from IM2700ANA (pp.14, 22, 30–31, 37, 41, 43, 47, 50, 54, 59). Part numbers 24P501A01, 13P607A01, 19P583-01 and 12P555-04 appear in the IM2700ANA parts list (p.59) and the OMW7-0018W parts lists (pp.89–90). E15 control text also appears in OMW7-0018W (p.25).

Before you order

Read the full model and serial number from the unit nameplate and the number on the old part. Note any code on the AID Tool. Browse WaterFurnace Replacement Parts or contact us (help@totalhvacparts.com) to confirm fit. For other Aurora codes, see WaterFurnace Aurora fault codes.

Frequently Asked Questions

What does E15 mean on a WaterFurnace 7 Series?

Hot water limit: the water at the HWL sensor stayed at or above the set point (130°F default) for 30 seconds, so the control turned the hot water pump off. It resets automatically.

When does the hot water pump come back on after E15?

On the next compressor cycle, or after 15 minutes of continuous compressor operation in the same thermostat demand cycle.

Why is my WaterFurnace desuperheater pump off in cooling?

In cooling, hot gas temperature depends on loop temperature, and the control checks water and refrigerant temperatures before heating water. A cold loop may keep the pump off.

Can I run the hot water generator pump to test it with no water?

No. The manual says: "Never operate the HWG circulating pump while dry." Keep the cabinet switch off until the piping is filled and purged.

What is the part number for the 7 Series hot water generator pump?

24P501A01, for every size in the IM2700ANA and OMW7-0018W parts lists.

Sources

WaterFurnace heat pumps involve line voltage, 24 V controls, hot water at up to 140°F set point, pressurized refrigerant and rotating equipment. Service should be performed only by qualified personnel, following the manufacturer's manual for your unit and your facility's lockout/tagout procedures.