If a BAC cooling tower with an electric water level control (EWLC) is not filling, start with what the control is telling you: the status LED, the probes and the make-up solenoid valve. BAC's EWLC manuals say the control is fully potted with "no user serviceable electronic components", so a failed control head is replaced as an assembly. For replacements, BAC's 313555 manual names the BAC RK3645 EWLC Replacement Kit – Baltimore Aircoil Cooling Tower.
How does the BAC EWLC open and close the make-up valve?
The EWLC is a conductivity probe control hanging in a stilling chamber in the basin. It drives a normally closed, 120 VAC, slow-closing solenoid valve on the make-up line. The older manual, BAC Universal Electric Water Level Control IOM, MEWLC/4-B (©2014, for EWLC part numbers beginning with 312), Note 2 (p.8):
- "The water level control board is wired in the inverse mode so that the solenoid makeup valve will close if there is a loss of power to the control board."
- When the water reaches the bottom of the make-up valve OFF probe and stays there for at least 6 seconds, the control de-energizes the valve.
- The valve stays closed until the water drops below the bottom of the make-up valve ON probe for at least 6 seconds. "The control then energizes the valve."
So no power to the control means no fill. On the newer 313555 control, the white/clear probe is the valve ON point and the black probe is the valve OFF point; red is low alarm, blue is high alarm and yellow is heater cutout (BAC Universal Electric Water Level Control IOM for Part Number 313555 (RGOMALL-06_R3.0, ©2023), pp.11–13).
What do the EWLC LED codes mean?
The two generations report status differently. Older controls (part numbers beginning with 312) use one LED with flash codes (MEWLC/4-B, p.8):
| LED | Meaning (MEWLC/4-B) | What the manual says clears it |
|---|---|---|
| On steady | Normal operation | – |
| Steady 1 s on, 1 s off | Dirty probes, reading in the capacitance mode. No other codes show until the probes are cleaned. | Clean probes, reset power |
| Two flashes, off 5 s | Make-up valve ran for more than 1 hour. "Possible causes: leaking tank, obstructed fill / defective valve or reduced flow rate." | Not stated; the manual lists causes only |
| Three flashes, off 5 s | Shorted probes or high conductive water | Dilute the water or remove the short, reset power |
| Four flashes, off 5 s | Black probe (P6) reads covered but white probe (P5) does not. Causes short cycling and premature fill valve failure. | Clean the white probe, reset power |
| Does not come on | Unit inoperative | – |
The 313555 control (BAC-EWLC-6P) has separate labelled LEDs instead (pp.14–15):
| LED | Meaning (313555 manual) |
|---|---|
| Power | Power supplied |
| Probe Dirty | Probes read low-conductivity water, indicating organic growth around the probes or dirty probes; the probes need cleaning |
| High Conductive | Sensing probe dipped in high conductivity water |
| Short-Cycle | Water level is sensed at black probe but not at white/clear probe |
| Makeup-Vlv | Makeup valve is on |
| Low-Alarm / High-Alarm / Heater-Cutout | Water level states |
How do I troubleshoot a tower that is not filling?
Neither manual has a symptom table, so these checks follow the manuals' operating notes:
- Power. The older control runs on 120 VAC, +10%/-15%, 60 Hz; the 313555 on 80–270 VAC, 50/60 Hz. With no power, the inverse-mode wiring keeps the valve closed. On an older control a dark LED means "unit inoperative".
- Read the LED. On the 313555, a basin below the white probe should light Makeup-Vlv. If it does, the call is there and the problem is downstream.
- Clean the probes. The 313555 manual (p.15) says to "Clean the stainless-steel electrodes periodically to prevent accumulations of scale, corrosion, sludge" or biological growth; the older manual gives the same advice. The stilling chamber, coupling and probe assembly are not glued, so they come apart for cleaning (MEWLC/4-B, p.3).
- Check the strainer and supply pressure. MEWLC/4-B Note 8: "A strainer is required before the solenoid make-up valve." MEWLC/4-B (Note 5) says the valve is designed to operate at make-up water line pressures of 10 to 125 psig; BAC's Parts & Maintenance Guide (p.15) says BAC valves "are sized for a water pressure between 15 and 50 psig at the valve inlet".
- Check the solenoid valve. If the control is calling (Makeup-Vlv on, or 120 VAC at the valve leads) and the valve stays shut, the valve or coil is the problem.
- Replace the control assembly if power is correct, the probes are clean and the control still will not call for water.
Field practice, not from the manual: bypass the control and hand-fill to confirm the supply line and valve can pass water. BAC itself says to bypass the control at start-up to fill the unit to the overflow connection.
What does RK3645 replace, and what about the probes?
The 313555 manual (p.5) uses RK3645 "When replacing existing EWLC assemblies with new assemblies". It then says: "Cut probes on the new EWLC assembly to correct lengths and set operating level, reference RKM106 as needed." Take care: probes "cannot be repaired or replaced if cut too short." For PSeries and VCA models, an additional stilling chamber cover is required. Retrofit kits for towers that never had an EWLC are a different number (RK3644M5/M3).
Parts that fix it
BAC's manuals list make-up solenoid valves by tower size as 310782 (½"), 310783 (¾"), 310784 (1") and 310785 (1½"). Our slow-acting solenoid listings below are BAC parts in matching sizes, but their listings do not say they replace those 3107xx numbers, so confirm by serial number.
| Component | Role | Link |
|---|---|---|
| EWLC replacement assembly | Primary fix when the sealed control head has failed | BAC RK3645 EWLC Replacement Kit – Baltimore Aircoil Cooling Tower |
| Make-up solenoid, ¾" | Slow-acting make-up valve; BAC's table puts ¾" at 150–250 nominal tons | BAC SA0075 3/4" Slow Act Solenoid – Baltimore Aircoil Cooling Tower |
| Make-up solenoid, 1" | Slow-acting make-up valve; 1" at 250–650 nominal tons | BAC SA0100 1" Slow Act Asco Solenoid – Baltimore Aircoil Cooling Tower |
| Make-up solenoid, 1-1/2" | Slow-acting make-up valve; 1½" at 650–1301 nominal tons | BAC SA0150 1-1/2" Slow Act Solenoid – Baltimore Aircoil Cooling Tower |
Which units this applies to
- BAC cooling towers, closed-circuit coolers and evaporative condensers fitted with a BAC Universal Electric Water Level Control: older controls (part numbers beginning with 312) and the 313555 BAC-EWLC-6P.
- Towers with a mechanical float valve instead: see BAC float valve inspection.
Scope: Operation, LED codes, electrical data, probe and valve notes come from BAC's two EWLC manuals and the Parts & Maintenance Guide (p.15). The RK3645 use comes from the 313555 manual (p.5). Valve sizes are minimums for a single-cell tower; BAC says multi-cell towers may need a larger valve or valves in parallel.
Before you order
Read the BAC model and serial number from the unit nameplate, the part number on the control head, and the size and number on the solenoid valve. Note which LED pattern you see. Contact us or email help@totalhvacparts.com to confirm fit, or browse Baltimore Aircoil Parts (BAC). See also how to find a BAC part number.
Frequently Asked Questions
Why is my BAC electric water level control not filling the tower?
Check power first: the control is wired so the make-up valve closes on loss of power. Then read the LED, clean the probes, check the strainer and supply pressure, and check the solenoid valve.
What does two flashes mean on a BAC EWLC?
On older controls, two flashes then off for 5 seconds means the make-up valve ran more than 1 hour. BAC lists a leaking tank, obstructed fill or defective valve, or reduced flow rate.
How long is the EWLC time delay?
6 seconds. The water must stay at a probe for 6 seconds before the control changes the valve state.
Can the EWLC control head be repaired?
No. BAC says the head is fully potted with no user serviceable electronic components. BAC's 313555 manual uses RK3645 to replace an existing EWLC assembly.
What solenoid valve does a BAC EWLC need?
A normally closed, 120 VAC, slow-closing solenoid valve on the make-up line, sized to the tower; BAC lists ½" to 1½" by nominal tons.
Sources
- BAC Universal Electric Water Level Control IOM for Part Number 313555 (RGOMALL-06_R3.0, ©2023)
- BAC Universal Electric Water Level Control IOM, MEWLC/4-B (©2014, for EWLC part numbers beginning with 312)
- BAC Parts & Maintenance Guide (partsguide_20210421), p.15 Electric Water Level Control and Solenoid Valves
- BAC Electric Water Level Control parts page
Cooling tower controls and make-up valves carry line voltage, and the basin has rotating fans and pumps nearby. Service should be performed only by qualified personnel, following BAC's literature for your unit and your facility's lockout/tagout procedures.