On a WaterFurnace 7 Series, E47 means the Aurora control lost communication with the EEV controller and the EEV "has gone independent mode"; the compressor drops to safe mode speed until communication comes back. Check the EEV communication cable first, then the EEV control board. E71 Loss of Charge is different: it locks out on high superheat with a high EEV opening for a long time. On R-410A units, WaterFurnace IM2700ANA (7 Series 700A11 Installation Manual, R-410A) lists the board as 17P561-01 and the cable as 11P843-01: 17P561-01 — WaterFurnace Pkg Units Or 7SISAECK NVZ Splits -EEV Control Board and 11P843-01 — WaterFurnace Harness-EEV To VSD Comm 7S.
What do E47, E48 and E71 mean?
The fault table (IM2700ANA p.37) lists these EEV-related codes:
| Code | Name | Lockout / reset | Description as printed |
|---|---|---|---|
| E47 | SafeMd-EEVIndCom | No / Auto | Com with EEV is interupted EEV has gone independent mode |
| E48 | SafeMd-EEVOutCom | No / Auto | Com with EEV is interupted EEV has gone independent mode |
| E71 | Fault-LossofCharge | Yes / Hard or Soft | High superheat and high EEV opening % for a long time will trigger a loss of charge fault |
| E14 | CriticAXBSnsrErr | Yes / Hard or Soft | Sensor Err for EEV or HW |
| E72 | SafeMd-SucTmpSnr | No / Auto | Suction Temperature Sensor is invalid (-76 to 392 F) |
WaterFurnace OMW7-0018W (7 Series 700A11 R-454B Operation & Maintenance) explains the first two (p.54). E47: "The communication with the indoor EEV controller has been interrupted" and "The system will go to safe mode speed and return to normal operation when communication has been re-established." E48 is the outdoor EEV controller and is marked "Not used in GSHP." On a geothermal unit, expect E47, not E48. The Aurora fault LED also has "Fault - EEV Error" as flash code 25 (IM2700ANA p.43).
What is safe mode?
IM2700ANA (p.39) describes safe mode as the drive "running the compressor at a fixed speed of 2400 rpm awaiting the problem to be solved." "If the problem cannot be solved the drive stops and issues an alarm." So a unit sitting in E47 still runs, but at a fixed compressor speed.
How does the EEV talk to the rest of the unit?
The 7 Series EEV "is set to maintain optimal superheat setting for maximum efficiency," and "All operation parameters are communicated to the VS drive and the Aurora system" (IM2700ANA p.31). The wiring diagram (p.42) shows an EEV control board with an "EEV COMM" connection, and the parts list (p.59) includes an "EEV/VS Drive Communication Cable". A wiring note on p.41 reads: "Communication cable routed through Ferrite Toroid four times." The start-up checklist (p.47) says: "Confirm EEV2 is added and communicating."
How do I troubleshoot E47?
The manuals give the meaning and the parts but no step-by-step tree for E47. These checks follow the wiring notes and parts list; the order is ours:
- Confirm the code. Read the AID Tool fault history. E47 resets on its own, so note whether it is constant or intermittent.
- Check EEV2 in the AID Tool. Confirm EEV2 is added and communicating, as the start-up checklist asks (p.47).
- Check the communication cable. Power down and wait for the drive to discharge, then reseat both ends of the EEV/VS drive cable at the EEV COMM connection and look for damage. Confirm it still passes through the ferrite toroid four times (p.41).
- Check power to the EEV board. Field practice, not from the manual: if the board has no supply, it cannot communicate; check the board's supply wiring against the p.42 diagram.
- Replace the cable, then the board. If E47 stays with a good, correctly routed cable, the EEV control board is the next part.
How do I troubleshoot E71 Loss of Charge?
WaterFurnace OMW7-0018W (7 Series 700A11 R-454B Operation & Maintenance) (p.53): "The EEV sensors have determined that the unit has experienced a severe loss of charge and will be locked out." Treat E71 as a refrigerant problem first: find and repair the leak. But a restricted EEV can look the same. The IM2700ANA heat of extraction/rejection table (p.52) has a row "Restricted EEV (Check Service Advisory)":
| Symptom | Head pressure | Suction pressure | Compressor amps | Superheat | Subcooling | Air temp. diff. | Water temp. diff. |
|---|---|---|---|---|---|---|---|
| Restricted EEV | High | Low | Normal/Low | High | High | Low | Low |
High superheat with high subcooling points at a restriction; a true undercharge usually shows low subcooling. That reading is our explanation. The manual adds: "Check superheat and subcooling with an AID Tool" (p.54), and WaterFurnace OMW7-0018W (7 Series 700A11 R-454B Operation & Maintenance) (p.55): "Check for EEV operation. EEV opening percentage should change as compressor speed changes." The refrigerant monitoring kit described on p.48 includes a heating liquid line temperature sensor, so check that sensor's reading before you trust a subcooling figure or condemn the valve.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| EEV control board | Primary fix for E47 that stays after the cable checks out. Listed as "EEV Board 17P561-01" in IM2700ANA p.59. | 17P561-01 — WaterFurnace Pkg Units Or 7SISAECK NVZ Splits -EEV Control Board |
| EEV / VS drive communication cable | Primary fix for a damaged or loose comm cable. Listed as 11P843-01. | 11P843-01 — WaterFurnace Harness-EEV To VSD Comm 7S |
| Electronic expansion valve | For a restricted or failed valve (E71 with high subcooling). Listed as "EEV 33P617-01"; the EEV solenoid coil is a separate number, 33P617-02. | 33P617-01 — WaterFurnace Pulse Motor Expansion Valve EEV |
| Heating liquid line thermistor | Liquid line sensor used for refrigerant monitoring; listed as 12P555-03. | 12P555-03 — WaterFurnace Liquid Line Heating Temperature Thermistor 7-Series |
Which units this applies to
- WaterFurnace 7 Series 700A11 R-410A units (IM2700ANA, sizes 036, 048, 060): all four parts above are in the p.59 parts list.
- 7 Series 700A11 R-454B units (OMW7-0018W): the parts lists (pp.89–90) show the same EEV 33P617-01, coil 33P617-02 and thermistor 12P555-03, and the 11P843-01 cable on the horizontal list. They list the EEV board as "Power Supply/EEV Board (OptiDry only)" 17P568-02, so check your own unit's parts list for the board.
Scope: Codes and descriptions come from IM2700ANA (pp.31, 37, 39, 41–43, 47–48, 52, 54, 59) and OMW7-0018W (pp.53–55, 89–90). The order of the E47 checks is ours; the manuals do not give one.
Before you order
Read the full model and serial number from the unit nameplate, note the refrigerant (R-410A or R-454B) and the AID Tool fault history, and read the number on the old board or cable. Browse WaterFurnace Replacement Parts or contact us (help@totalhvacparts.com). Related: 7 Series E41 and E58 drive temperature faults and how to reset a WaterFurnace lockout.
Frequently Asked Questions
What does E47 mean on a WaterFurnace 7 Series?
Communication with the indoor EEV controller was interrupted and the EEV went to independent mode. The unit runs at safe mode speed and returns to normal when communication is re-established.
What is the difference between E47 and E48?
E47 is the indoor EEV controller and E48 the outdoor one. WaterFurnace's R-454B O&M marks E48 "Not used in GSHP."
Does E71 always mean the unit is low on refrigerant?
E71 trips on high superheat with a high EEV opening for a long time. The manual's table shows a restricted EEV also gives high superheat, but with high subcooling, so check both.
What speed does the compressor run in safe mode?
IM2700ANA describes safe mode as a fixed compressor speed of 2400 rpm while the problem is solved; if it is not, the drive stops and issues an alarm.
Sources
- WaterFurnace IM2700ANA, 7 Series 700A11 Installation Manual (R-410A)
- WaterFurnace OMW7-0018W, 7 Series 700A11 R-454B Operation & Maintenance
- Live product titles and listing data for the parts above
The 7 Series variable speed drive holds a dangerous charge after power is removed, and the unit has line voltage and pressurized refrigerant. Wait the time stated in the manual before touching drive wiring. Service should be performed only by qualified personnel, following the manufacturer's manual for your unit and your facility's lockout/tagout procedures.