On a WaterFurnace 7 Series variable speed heat pump, E41 "Derate-DriveTemp" and E58 "Fault-HiDrivTemp" both mean the VS drive's power electronics have passed 239°F (115°C). E41 slows the compressor and resets on its own. E58 locks the unit out. The first part to check is the drive's washable fan filter, 59P512-01 — WaterFurnace Variable Speed Drive FAN Filter, listed for every size in the 7 Series manuals (IM2700ANA and OMW7-0018W).
What do E41 and E58 mean on a WaterFurnace 7 Series?
The 7 Series 700A11 installation manual (IM2700ANA, p.37) lists both codes in its VS drive fault table:
| Fault | Code | Lockout | Reset | Description |
|---|---|---|---|---|
| Derate-DriveTemp | 41 | No | Auto | "Drive Temp has reached critical High Temp (>239˚F/115˚C)" |
| Fault-HiDrivTemp | 58 | Yes | Hard or Soft | "Drive Temp has reached critical High Temp >239 F" |
The Aurora status LED list on p.35 also has "Warning! VS Derated" as Flash Code 8. The R-454B 7 Series manual (OMW7-0018W) explains that on E41 the drive slows the compressor until the temperature returns to normal.
What makes the VS drive overheat?
OMW7-0018W gives the causes for E58: "Possible causes are insufficient cooling due to a defective cooling fan, blocked air circulation" and "extreme high ambient temperature."
IM2700ANA adds two installation points:
- Dirt and debris in the unit location "may be drawn into the VS drive causing overheating of the VS drive" (p.5).
- "The VS drive is limited to a maximum of 125°F ambient temperature." The control will derate the compressor when ambient air is above 125°F (p.6).
A clogged drive filter is blocked air circulation, and it is the cheapest thing to fix. That is why we start there.
Where is the VS drive filter and how do you clean it?
IM2700ANA (p.58) covers it under Filters. The air filters and the variable speed drive filter "should be inspected monthly under normal operating conditions and be replaced when necessary." The manual also says "The VS drive filter is located on the lower left corner of the cabinet."
The cleaning steps in the manual are:
- Remove the two screws in the honeycomb grill to reach the filter.
- Run the filter under warm water and gently rub it.
- Let the filter dry.
- Reinstall the filter and the cover.
The startup checklist (p.47) has a line for it too: "Variable speed drive filter is clean and in place." The Filters section adds: "Units should never be operated without a filter."
How do you work an E41 or E58?
- Record the code. Note whether it is E41 (derate, auto reset) or E58 (lockout), and how often it has happened.
- Isolate power before opening the cabinet. Apply your lockout/tagout procedure. The drive holds line voltage.
- Check the drive filter. Clean it as above. If it is torn, misshapen or will not come clean, replace it with 59P512-01.
- Check the space around the unit. Look for dust or debris near the cabinet and for a hot mechanical room. The drive is rated for a 125°F maximum ambient.
- Check the drive cooling fan. OMW7-0018W names "a defective cooling fan" as a cause. Field practice, not from the manual: with power restored and the unit running, confirm air is moving through the filter grill.
- Reset E58 the way the manual says. OMW7-0018W says that to restart after E58, "it is necessary to cycle power to the drive and to perform a reset." The same manual cautions "Frequent cycling of power to the drive can damage the drive!" and says to wait at least 5 minutes between power cycles.
- Watch it run. If E58 returns with a clean filter, normal ambient and a working fan, the drive itself is the suspect.
Field practice, not from the manual: put the filter on the same monthly check as the air filter, and clean it whenever the room has had construction dust.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| VS drive fan filter | Primary fix. Same part for all 7 Series sizes in IM2700ANA and OMW7-0018W. | 59P512-01 — WaterFurnace Variable Speed Drive FAN Filter |
| VS drive control, size 036 | If the drive fails (R-410A 700A11, IM2700ANA p.59) | 17P560-04 — WaterFurnace Variable Speed Drive 3.8kW |
| VS drive control, size 048 | If the drive fails (R-410A 700A11) | 17P560-05 — WaterFurnace Variable Speed Drive 5.3kW |
| VS drive control, size 060 | If the drive fails (R-410A 700A11) | 17P560-06 — WaterFurnace Variable Speed Drive 6.7Kw |
The R-454B 7 Series 700A11 (OMW7-0018W) uses different drive numbers: 17P560-07 (024 and 036), 17P560-08 (048) and 17P560-09 (060). Those are not listed on our site right now, so contact us for them.
Which units this applies to
- 7 Series 700A11, R-410A (IM2700ANA, 02/21), sizes 036, 048 and 060.
- 7 Series 700A11, R-454B, 60 Hz (OMW7-0018W), sizes 024, 036, 048 and 060. Same filter, different drive part numbers.
- Our 59P512-01 listing also shows confirmed fits on a range of NVV and NVH model numbers.
Scope: Codes, limits, filter care and part numbers are from WaterFurnace IM2700ANA and OMW7-0018W. Other variable speed WaterFurnace lines (for example Versatec 700) have their own manuals and parts lists. Use the manual for your unit.
Before you order
Read the model and serial number off the nameplate and the part number off the old drive or filter. Note the refrigerant on the nameplate, since R-410A and R-454B 7 Series units use different drives. To confirm fit, contact us or email help@totalhvacparts.com. For other Aurora codes, see WaterFurnace Aurora Base Control fault codes.
Frequently Asked Questions
What is E58 on a WaterFurnace 7 Series?
E58 is "Fault-HiDrivTemp": the VS drive temperature has passed 239°F. It is a lockout that needs a hard or soft reset (IM2700ANA, p.37).
What is the difference between E41 and E58?
Both are drive over-temperature. E41 is a derate: the drive slows the compressor and the code resets automatically. E58 is a lockout.
Where is the VS drive filter on a WaterFurnace 7 Series?
In the lower left corner of the cabinet, behind a honeycomb grill held by two screws (IM2700ANA, p.58).
How often should the VS drive filter be checked?
WaterFurnace says the air filters and VS drive filter should be inspected monthly under normal operating conditions and replaced when necessary.
What is the maximum ambient temperature for the VS drive?
125°F. Above that the control derates the compressor (IM2700ANA, p.6).
Sources
- WaterFurnace IM2700ANA, 7 Series 700A11 Installation Manual (R-410A) (unit location pp.5–6; Aurora LEDs p.35; VS drive fault table p.37; startup checklist p.47; filters p.58; service parts p.59)
- WaterFurnace OMW7-0018W, 7 Series 700A11 R-454B Operation & Maintenance (drive power-cycle cautions pp.29 and 37; fault table p.35; E41/E58 descriptions pp.53–54; service parts pp.89–90)
- Live product titles and fit data for the parts listed above, as shown on each product page
WaterFurnace heat pumps involve line voltage, 24 V control circuits, high-voltage drive electronics, pressurized refrigerant and rotating equipment. Service should be performed only by qualified personnel, following the manufacturer's manual for your unit and your facility's lockout/tagout procedures.