On a Daikin Applied rooftop or self-contained unit with the MicroTech III controller, Freeze Problem and Freeze Fault both come from the same device: the optional freezestat on a water, steam or waterside economizer coil. Daikin's OM 920-7 says the difference is whether the fans are running. A Freeze Problem (fans off) clears itself when the freezestat closes. A Freeze Fault (fans running) shuts the fans down and needs a manual clear. If the freezestat itself has failed, the parts are an automatic freezestat such as 107193101 (240" capillary) or 4ELN9178 (144" capillary).
Freeze Problem or Freeze Fault: what is the difference?
| Item | Freeze Problem | Freeze Fault |
|---|---|---|
| Trigger | "the optional freezestat contacts open as a result of detecting an abnormally low water or steam coil temperature", with the fans off | Same freezestat trip, with the fans running |
| Which units | Units with a waterside economizer, chilled water, hot water or steam coil | Same |
| What the controller does | Opens the economizer, chilled water and heating valves and starts a 10-minute timer. On waterside economizer units, the pump output turns on. After 10 minutes it rechecks the freezestat and repeats while it is still open. | Shuts down the fans, opens the valves and runs the same 10-minute recheck |
| How it clears | "Whenever the freezestat closes the Freeze problem automatically clears." | "This continues until the fault is manually cleared through the keypad or via a network signal." |
Source: OM 920-7, Freeze Problem (p.90) and Freeze Fault (p.91). Warnings, Problems and Faults are listed separately in the manual.
Why open the valves on a freeze trip?
OM 920-7 does not give the reason. Our reading: opening the valves (and running the pump on waterside economizer units) moves warmer water or steam through a coil that is close to freezing. It is a protective action, not a sign the valves have failed. OM 920-7's Flow Status section (p.30) also lists, among the conditions that turn on the Pump Start Output, "a Freeze fault or Freeze problem alarm is active or has been active within the past 10 minutes."
How do you clear it?
From the Alarm Clearing section of OM 920-7 (p.84):
- Clear from the keypad in the Active Alarm menu, or over the network (nviClearAlarms on LON, the ClearAlarms object on BACnet).
- ClearAlms values: 1 clears all faults, 2 all problems, 3 all warnings, 4 all alarms.
- "Alarms are cleared only if the conditions required to initiate the alarm do not exist." A Freeze Fault will not clear while the freezestat is still open.
- "Alarms are automatically cleared when power is cycled."
The Alarm Delays menu (p.61) also has Frz DelayTime: "an adjustable item used to set the freeze alarm delay time" (default 30 s, range 0-180 s). Check that setting on your controller before you assume the freezestat is tripping instantly.
How do you check the freezestat?
- Note which alarm you have and whether the fans were running. That tells you Problem or Fault.
- Field practice, not from the manual: look at the coil and the air. Check the outdoor air damper position, the mixed air temperature, and whether water or steam is actually flowing to the coil. A real freeze condition should be fixed before the alarm is cleared.
- Field practice, not from the manual: check the capillary. The freezestat senses along its capillary across the coil face. A capillary that has come loose from its clips, been kinked, or been moved to one cold corner can trip on a small cold spot.
- Field practice, not from the manual: test the contacts. With power isolated, check the switch for continuity at room temperature. Contacts that read open when the capillary is warm mean a failed freezestat.
- Field practice, not from the manual: replace like for like. Match the part number on the old control and the capillary length, so the new element covers the coil the same way.
OM 920-7 does not give a freezestat setpoint. Use the setting on the old control or the unit's IM manual.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Automatic freezestat, 240 in capillary | Replace a freezestat that reads open when warm, or one with a damaged capillary. The listing gives the capillary length but no unit model; match the part number on your old control. | Daikin Applied 107193101 — Automatic Freeze Stat, 240"Cap |
| Automatic freezestat, 144 in capillary | Same role, for a shorter capillary. Match the number on your old control. | Daikin Applied 4ELN9178 — Automatic Freeze Stat, 144" Cap |
More rooftop parts: Daikin Parts for Daikin Applied. Other MicroTech III rooftop alarms: Duct High Limit, OAD Stuck. For the chiller version of freeze protection, see Daikin MicroTech III Evaporator Flow Loss and Freeze Protect Alarms.
Which units this applies to
- Daikin Applied units with the MicroTech III unit controller covered by OM 920-7: DPS, MPS, RAH, RCS, RDS, RDT, RFS, RPS, SWP and SWT
- Only units with the optional freezestat: waterside economizer, chilled water, hot water or steam coil
Scope: The alarm behavior is from OM 920-7. The capillary lengths come from the product listings. The freezestat checks are general field practice. OM 920-7 ties the freezestat to units with a waterside economizer, chilled water, hot water or steam coil.
Before you order
Note the unit model and serial number, the alarm text, and the part number and capillary length of the old freezestat. Contact us or email help@totalhvacparts.com to match it.
Frequently Asked Questions
What is the difference between Freeze Problem and Freeze Fault on a Daikin rooftop?
Both come from the freezestat opening. OM 920-7 sets a Freeze Problem when the fans are off; it clears when the freezestat closes. A Freeze Fault happens with the fans running, shuts the fans down and must be cleared manually.
Why did the chilled water valve open on a freeze alarm?
OM 920-7 says the controller opens the economizer, chilled water and heating valves and runs a 10-minute timer on a freeze trip. On waterside economizer units it also turns on the pump.
Why won't the Freeze Fault clear?
OM 920-7 says alarms clear only if the conditions that set them no longer exist. If the freezestat is still open, the fault stays.
Which freezestat do I need?
Match the part number on the old control and its capillary length. Our listings include a 240 in capillary (107193101) and a 144 in capillary (4ELN9178).
Sources
- Daikin Applied OM 920-7 (August 2019), MicroTech III Unit Controller for Commercial Rooftop, Applied Rooftop and Self-Contained Systems (Flow Status p.30, Alarm Delays menu p.61, Alarm Clearing p.84, Freeze Problem p.90, Freeze Fault p.91)
- Live product titles and listed capillary lengths, read from our catalog