On a Daikin Applied VAV unit with the MicroTech III controller, "Duct High Limit" means the duct high pressure limit control (DHL) opened its contacts while the unit was running. Daikin Applied's OM 920-7 says the unit shuts down and stays down until the fault is cleared manually at the keypad or over the network (p. 91). Find out why duct pressure went high before you reset; if the pressure was normal, test the DHL switch and the duct static pressure sensor.
What triggers the Duct High Limit fault?
| Item | OM 920-7, p. 91 |
|---|---|
| Unit type | Variable air volume units |
| Trigger | The contacts of the duct high pressure limit control (DHL) open |
| When | The unit state is not Off or Startup |
| Action | The unit is shut down |
| Reset | Manual, through the unit keypad or via a network signal |
The manual's manual-control section (p. 8) lists Duct High Limit among the alarms the unit still responds to during manual control. So the DHL protects the ductwork even while you are running the fans by hand.
How is it different from the Airflow fault?
The two faults look at opposite problems. The Airflow fault (p. 90; the manual's text names the resulting fault "Fan Fail") is set when the PC7 airflow switch does not detect airflow for longer than the airflow timer, default 120 seconds. On VAV units, duct static pressure must also be below half of its setpoint after the unit leaves Startup. The unit shuts down and needs a manual clear. With a discharge fan VFD, the fault only occurs if Fan Retry has already happened twice in the previous 24 hours; retry allows up to three restart attempts in 24 hours. The manual notes: "There is no Fan Retry function or three retry function when a unit has a CAV supply fan."
| Fault | Device | What it means | Reset |
|---|---|---|---|
| Duct High Limit | DHL contacts | Duct pressure too high (VAV) | Manual |
| Airflow | PC7 airflow switch, plus duct static on VAV | No airflow proven | Manual |
What do you check before resetting?
OM 920-7 defines the fault but does not give a troubleshooting chart for it. Steps marked "field practice" are common checks for a high-limit trip on a VAV system, not from the manual:
- Confirm the code. Read the active fault and its time from the alarm log. Check whether an Airflow fault or other alarm came at the same time.
- Field practice, not from the manual: look for a real pressure spike. Closed fire or smoke dampers, VAV boxes driven closed, or an isolation damper that did not open can all raise duct pressure quickly.
- Compare duct static with setpoint. The DSP status item shows the current duct static pressure reading (p. 25). Field practice: if it read normal while the DHL tripped, suspect the switch or its tubing.
- Check the duct pressure sensing. The manual notes duct pressure is measured where the duct static pressure tap was field installed, and that this device is not factory installed (p. 30). Field practice, not from the manual: a blocked or kinked sensing tube gives a false reading.
- Field practice, not from the manual: test the DHL switch. With the system off, check the switch contacts and setpoint against the job's design and your unit's wiring diagram.
- Reset and watch. Clear the fault at the keypad and watch duct static as the fan ramps up.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| High limit air pressure switch | Listed as a high limit air pressure switch; this is the type of device the manual calls the DHL. OM 920-7 does not give its part number, so match your old switch. | Daikin Applied 349956813 — Pressure Control High Limit Air Pressure Switch |
| Duct static pressure sensor | Supplies the duct static reading used in control and in the VAV airflow check. The listing title does not name a model; match the part number on your old part or your unit's parts list. | Daikin Applied 193552102 — Static Pressure Sensor-duct |
| Static pressure sensor, 0-5 in. w.c. | Listed 0-5 in. w.c. range. The listing title does not name a model; match the part number on your old part or your unit's parts list. | Daikin Applied 049545007 — Static Pressure Sensor 0-5"wc |
| More Daikin Applied parts | Switches, sensors and controls | Daikin Parts for Daikin Applied |
Which units this applies to
- Daikin Applied units covered by OM 920-7: DPS, MPS, RAH, RCS, RDS, RDT, RFS, RPS, SWP and SWT, with the MicroTech III unit controller.
- The Duct High Limit fault applies to variable air volume units.
Scope: Fault logic and defaults are from OM 920-7 (August 2019). The switch and sensor listings are shown by live title; the manual does not tie these part numbers to a unit.
Before you order
Note the unit model and serial number and the part number and setpoint range printed on the old switch or sensor. Contact us or email help@totalhvacparts.com and we will help match them.
Frequently Asked Questions
What does Duct High Limit mean on a Daikin rooftop?
On VAV units with MicroTech III, it means the duct high pressure limit control (DHL) opened while the unit was not Off or in Startup. The unit shuts down (OM 920-7, p. 91).
How do you reset a Daikin Duct High Limit fault?
OM 920-7 says it must be cleared manually through the unit keypad or via a network signal. Find the cause first.
What is the default airflow timer for the Airflow fault?
120 seconds. The fault is set when the PC7 airflow switch does not detect airflow for longer than the timer (OM 920-7, p. 90).
Does the unit respond to Duct High Limit in manual control?
Yes. OM 920-7 (p. 8) lists Duct High Limit among the alarms the unit still responds to during manual control.
Sources
- Daikin Applied OM 920-7 (August 2019), MicroTech III Unit Controller for Commercial Rooftop, Applied Rooftop and Self-Contained Systems (pp. 8, 25, 30, 90-91)
- Live product titles for the listings above, read from our catalog
Rooftop and air handling units carry line voltage, rotating fans, pressurized refrigerant and, on gas units, fuel gas. Service should be performed only by qualified personnel, following the Daikin Applied manual for your unit and your site's lockout/tagout procedures.