Daikin Rooftop OAD Stuck Warning: Economizer Damper and Actuator Checks

On Daikin Applied units with the MicroTech III unit controller, "OAD Stuck" means the controller thinks the outdoor air damper is stuck open or stuck closed: the damper command and the damper end switch disagree for too long. Daikin Applied's OM 920-7 sets the limits at 180 seconds and 30 seconds (p. 86), and the warning clears itself once the cause is gone. The usual fixes are the actuator, its linkage, the end switch or a recalibration of the end switch positions.

Which economizer warnings can appear?

Warning (OM 920-7) What it points to Default limit in the manual
Over Economizing (p. 85) Damper appears stuck open in Econo or Cooling, or economizing while OAT is above the limit Max OAT Lmt 75°F
Under Economizing (p. 85) Damper appears stuck closed in Econo or Cooling, or not economizing while OAT is below the limit Min OAT Lmt 70°F
Excess OA (p. 85) Damper stuck open, same damper criteria as Over Economizing Max OAT Lmt 75°F
OAD Stuck (p. 86) Damper stuck open or stuck closed, or end switch reads unreliably 180 s / 30 s criteria

All four are warnings. The manual says they clear automatically "when the conditions causing the alarm are no longer present." The damper warnings are only active when EconFDD (Commission Unit / Econo Set-up) is set to ON, apart from the OAT/RAT changeover and network-controlled economizer cases (p. 86); the setup menu lists Econo FDD with a default of ON (pp. 47-48).

How does the controller decide the damper is stuck?

OM 920-7 compares the damper command with calibrated end switch positions (p. 86):

  • Stuck open: the command stays below the calibrated end switch closed value for 180 seconds while the end switch input stays open, or the end switch does not change within 30 seconds of the command dropping below the calibrated open value less the maximum switch differential.
  • Stuck closed: the command stays above the calibrated end switch open value for 180 seconds while the end switch input stays open, or the switch does not change within 30 seconds of the command rising above the calibrated closed value plus the minimum switch differential.
  • Unreliable switch: the end switch input stays closed while the command is between the calibrated closed and open values, adjusted by the switch differentials.

What are the calibration defaults?

Item (Econo Set-Up, pp. 47-48) Default Range
Calibrate OAD No No / Yes
PosSwOpen 97% 0-100%
Max Sw Diff 3% 0-100%
PosSwClose 3% 0-100%
Min Sw Diff 5% 0-100%
OAD Sw Status Read only Open / Closed

"Calibrate OAD" captures the command positions where the end switch opens and closes. PosSwOpen and PosSwClose can also be adjusted by hand. If the actuator or the linkage has been changed, the stored values may no longer match the damper.

How do you work an OAD Stuck warning?

  1. Read which warning is active. Over Economizing, Under Economizing, Excess OA or OAD Stuck each have their own criteria.
  2. Watch OAD Sw Status. Note whether the end switch reads Open or Closed at the current damper command.
  3. Drive the damper by hand. In manual control, "OAD/Econo" sets the damper position from 0% to 100% (p. 63). Command full closed and full open and watch the actuator and blades.
  4. Field practice, not from the manual: if the actuator does not move, check its 24 V power and the command signal at the actuator, then the actuator itself.
  5. Field practice, not from the manual: if the actuator moves but the blades do not, check the linkage, shaft coupling and blade bearings.
  6. Field practice, not from the manual: if the damper moves but OAD Sw Status never changes, check the end switch and its wiring.
  7. Recalibrate. After any repair, run Calibrate OAD so the switch positions match the damper again.
  8. For Under Economizing, also check the OAT and RAT sensors; the manual lists an unreliable OAT or RAT sensor as one trigger under OAT/RAT changeover.

Parts that fix it

Component Role Link
Modulating spring-return actuator Listed as a 0-10 VDC proportional spring-return actuator. OM 920-7 does not give the actuator part number for each unit, so match the old actuator's part number. Daikin Applied 113139601 — 0-10vdc Prop 62in# Sr Actuator
Spring-return actuator Listed as a 24 VAC spring-return actuator motor. The listing title does not name a model; match the part number on your old part or your unit's parts list. Daikin Applied 113139501 — 24 vac Actuator Motor S/r
Other Daikin Applied parts Sensors, end switches and controls Daikin Parts for Daikin Applied

Which units this applies to

  • Daikin Applied units covered by OM 920-7: DPS, MPS, RAH, RCS, RDS, RDT, RFS, RPS, SWP and SWT, with the MicroTech III unit controller and an economizer.
  • Damper fault detection requires Econo FDD set to ON.

Scope: The criteria and defaults are from OM 920-7 (August 2019). Other controller versions can differ. The actuator listings are shown by live title; the manual does not tie these part numbers to a unit.

Before you order

Copy the part number and signal type from the old actuator's label, and note the unit model and serial number. Contact us or email help@totalhvacparts.com and we will help match it.

Frequently Asked Questions

What does OAD Stuck mean on a Daikin rooftop?

It is a MicroTech III warning that the outdoor air damper appears stuck open or stuck closed, based on the damper command and the end switch (OM 920-7, p. 86).

Does OAD Stuck shut the unit down?

No. OM 920-7 lists it as a warning, and it clears automatically when the conditions causing it are no longer present.

What are the default Over and Under Economizing limits?

Max OAT Lmt defaults to 75°F and Min OAT Lmt to 70°F (OM 920-7, pp. 47-48 and 85-86).

Do I need to recalibrate after replacing the actuator?

The manual's Calibrate OAD function captures where the end switch opens and closes. After an actuator or linkage change, run it so the stored PosSwOpen and PosSwClose values match the damper.

Sources

Rooftop and air handling units carry line voltage, rotating fans, pressurized refrigerant and, on gas units, fuel gas. Service should be performed only by qualified personnel, following the Daikin Applied manual for your unit and your site's lockout/tagout procedures.