A York YK that stops on "Leaving Chilled Liquid – Flow Switch Open" has lost its chilled-water flow signal, either for 5 continuous seconds while running or because the switch never closed during System Prelube. York form 160.54-O1 (YK through Style G OptiView operation guide) lists it as a cycling shutdown that restarts by itself once the switch closes. Prove real water flow first. If flow is good and the switch input still reads open, the usual fix on YK Mod G and Mod H is the flow sensor, York 025-41573-000.
What does "Leaving Chilled Liquid – Flow Switch Open" mean on a York YK?
Section 3 (Display Messages) of form 160.54-O1 describes two flow shutdowns. Both are cycling shutdowns, so the chiller restarts on its own when flow is proven again.
| Message | What trips it (160.54-O1) | Restart |
|---|---|---|
| Leaving Chilled Liquid – Flow Switch Open | Chilled liquid flow switch open for 5 continuous seconds while running, or it failed to close during System Prelube. The delay is 2 seconds in software C.OPT.01.15A.xxx and earlier. | Automatic when the flow switch closes |
| Condenser – Flow Switch Open | Condenser water flow switch open for 30 continuous seconds while running. Bypassed for the first 30 seconds of System Run. The delay is 2 seconds in C.OPT.01.15A.xxx and earlier. | Automatic when the flow switch closes |
Pump contacts behave differently by software version. In C.OPT.01.23.307 and later, the evaporator pump contacts (TB2-44/45) stay closed during the chilled-liquid flow shutdown until a stop command or another fault. The condenser pump contacts (TB2-150/151) do the same during the condenser flow shutdown. In earlier software, those contacts open when coastdown finishes. So on older panels, a flow trip can also stop the pump.
Where can you see the flow switch state on the OptiView panel?
Form 160.54-O1 shows flow status in several places:
- Evaporator screen: Chilled Liquid Flow Switch (open or closed) and the Chilled Liquid Pump run/stop command.
- Condenser screen: the Condenser Liquid Flow Switch LED, which "Illuminates when liquid flow is present", and the Condenser Liquid Pump run/stop status. The manual notes this LED only appears when Heat Recovery is enabled, so on a standard unit use the trend slot below.
- Trending slots: slot 1794, "Leaving Chilled Liquid: Is Flow Switch Closed", and slot 2049, "Leaving Condenser Liquid: Is Flow Switch Closed". Trend one of them with the pump command to catch a switch that drops out briefly.
How do you tell a flow problem from a failed flow sensor?
- Read the message and the software version. Note which message is on the screen, chilled liquid or condenser. Check whether the panel software is C.OPT.01.15A.xxx or earlier (2-second delay) or later (5 seconds chilled, 30 seconds condenser).
- Check the pump command. On the Evaporator or Condenser screen, confirm the panel is calling for the pump. On older software the pump contacts open after coastdown, so a pump that is off after a trip may be a result of the trip, not the cause.
- Prove real flow. Check the pump, strainers, isolation valves and air in the loop. A switch that opens because flow is low is doing its job.
- Watch the switch state. With flow proven, watch the flow switch status on the screen or trend slot 1794 or 2049. A switch that reads open with good flow, or that drops out at random, points to the switch or its wiring.
- Check the wiring and connector. Look for loose terminations and moisture at the sensor plug before you condemn the sensor. Use the wiring diagram for your chiller.
- Replace the sensor if it still fails. Match the part number on the old sensor. On YK Mod G and Mod H, York's parts data lists 025-41573-000.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Flow sensor, 1/2 in. NPT | Proves chilled or condenser water flow to the control center. Listed for YK Mod G and Mod H, YD Mod A–C, CYK Style G and YKEP Mod A. Replaces 025-42453-000. | York 025-41573-000 Sensor, Flow 1/2" NPT | OEM Chiller Part |
| Other YK sensors | Temperature sensors, transducers and thermistors | York Chiller Sensors, Thermistors & Transducers |
| YK parts | Browse parts by chiller line | York YK Centrifugal Chiller Parts |
Which units this applies to
- YK Mod G: covered by form 160.54-O1. 025-41573-000 is listed for it in York renewal parts data (160.75-RP1).
- YK Mod H: 025-41573-000 is listed for it. Mod H is not covered by 160.54-O1, so check the operation manual for your panel.
- YK Mod C, Mod D, Mod E and Mod F: the messages above apply (160.54-O1), but our listing for 025-41573-000 does not include these Mods. Read the part number on your existing flow switch.
- YD Mod C and CYK Style G: the sensor is listed for them; their control messages may differ.
Scope: Message text, delays and pump-contact behavior are from York form 160.54-O1, which covers YK Mod C through Mod G with the OptiView control center. Fits come from the product listing, which cites York renewal parts manuals. Your panel software version changes the delays, so check it before you diagnose.
Before you order
Read the chiller model, Mod letter and serial number off the nameplate. Read the part number off the old flow sensor and note whether it is on the evaporator or condenser line. To confirm fit, contact us or email help@totalhvacparts.com with those details.
Frequently Asked Questions
Is Leaving Chilled Liquid – Flow Switch Open a lockout on a York YK?
No. Form 160.54-O1 lists it as a cycling shutdown. The chiller restarts automatically when the flow switch closes again.
How long does the flow switch have to be open before the YK shuts down?
5 continuous seconds for the chilled liquid flow switch and 30 continuous seconds for the condenser flow switch. Software C.OPT.01.15A.xxx and earlier uses 2 seconds for both.
Why did the chilled water pump stop after a flow switch trip?
In software earlier than C.OPT.01.23.307, the evaporator pump contacts (TB2-44/45) open when coastdown finishes. In C.OPT.01.23.307 and later they stay closed until a stop command or another fault.
Which flow sensor does a York YK Mod G use?
York's renewal parts data lists 025-41573-000, a 1/2 in. NPT flow sensor, for YK Mod G and Mod H. It replaces 025-42453-000. Confirm against the part number on your old sensor.
Sources
- York form 160.54-O1, YK through Style G OptiView Control Center operation guide (YK Mod C, D, E, F and G) (Section 3 Display Messages: Leaving Chilled Liquid – Flow Switch Open and Condenser – Flow Switch Open; Evaporator and Condenser screens; Common Slots table)
- Live product title and fit data for York 025-41573-000, as shown on the product page and York model pages
Chiller control panels carry line voltage and 24 VAC control power. Service should be performed only by qualified personnel, following York's manual for your unit and your facility's lockout/tagout procedures.