Carrier 48TC Rooftop 6 Flashes, Induced-Draft Motor Fault: Hall Effect Sensor 50HJ442730 Checks

On a Carrier 48TC rooftop unit, 6 flashes on the IGC board means "Induced-Draft Motor Fault". Carrier's 48TC Service and Maintenance Instructions (Catalog No. 48TC-1SM) explain that the induced draft fan motor has a Hall Effect sensor that tells the IGC the wheel is up to speed, and they tell you to check the inducer wiring, voltage and motor, then the speed sensor wiring. If the motor is good, the sensor is the fault and your old sensor is labelled 50HJ442730, the part is Carrier 50HJ442730 Hall Sensor — Replacement, our verified replacement for Carrier 50HJ442730.

What does 6 flashes mean on a Carrier 48TC?

48TC-1SM covers the 48TCA04 to 48TCA07 units (nominal 3 to 6 tons, Puron refrigerant). The integrated gas unit controller (IGC) sits in the control box and has one diagnostic LED. The manual's LED table reads:

LED 48TC-1SM description
On Normal operation
Off Hardware failure
1 flash Evaporator fan on/off delay modified (not a fault)
2 flashes Limit switch fault
3 flashes Flame sense fault
4 flashes 4 consecutive limit switch faults
5 flashes Ignition lockout fault
6 flashes Induced-draft motor fault
7 flashes Rollout switch fault
8 flashes Internal control fault
9 flashes Software lockout

The manual notes a 3-second pause between codes. If more than one fault exists, the LED shows all of them in numerical order, so count carefully before you decide the board is showing 6.

How does the IGC know the inducer is running?

48TC-1SM says: "The induced draft fan motor includes a Hall Effect sensor circuit that confirms adequate wheel speed via the Integrated Gas Control (IGC) board." The IGC connection table lists two parts of this circuit:

IGC point What it is (48TC-1SM Table 9)
L1, CM Induced draft combustion motor output (line VAC)
SS (J1, pins 1–3) Speed sensor input (analog)

So a 6-flash code can come from either side: a motor that is not turning fast enough, or a sensor or harness that is not reporting the speed.

What does Carrier say causes the fault?

From the IGC alarm code table in 48TC-1SM:

Item 6 flashes, induced draft motor fault
Action taken by control If heat is off: no gas heating. If heat is on: gas valve off and inducer on.
Reset Inducer sense normal, or heat call (W) off
Probable cause Inducer sense on when the heat call is off, or inducer sense off when the heat call is on. Check wiring, voltage and operation of the IGC motor. Check speed sensor wiring to the IGC.

Note the action column: with a heat call, the control shuts the gas valve but keeps the inducer on. A unit that runs its inducer with no flame and flashes 6 is behaving as designed for this fault.

How do I narrow it down?

  1. Read the code. Count the flashes after the 3-second pause. Write down any other codes shown in the same sequence.
  2. Note the heat call. Carrier lists two cases: speed sensed with no heat call, or no speed sensed with a heat call. Check whether W is calling when the code appears.
  3. Check the inducer motor. On a heat call, 48TC-1SM says the induced-draft motor is energized and the ignition sequence begins. Check line voltage at the inducer output and watch the wheel. A motor that does not start or runs slowly is the first suspect.
  4. Check the speed sensor wiring. Follow the sensor harness to the SS input (J1, pins 1–3). Look for loose pins, chafed wires and corrosion.
  5. Judge the sensor. Field practice, not from the manual: if the wheel comes up to normal speed, voltage is correct and the harness is sound, but the IGC still flashes 6, the Hall Effect sensor is the likely failure. If the code appears with no heat call at all, look first at the sensor and its wiring.
  6. Reset and test. The 6-flash code clears when the inducer sense returns to normal or the heat call ends. 48TC-1SM also says a lockout may be reset by interrupting power to the unit for at least 5 seconds. Then run a full heat cycle. The manual says the burners should light within 5 seconds of a heat call, and the indoor fan starts 45 seconds after flame.

Parts that fix it

Component Role Link
Hall Effect (speed) sensor Primary fix when the inducer runs at speed but the IGC does not see it. Replaces Carrier 50HJ442730; the listing also replaces 50HJ401484. Carrier 50HJ442730 Hall Sensor — Replacement
Same sensor, listed under 50HJ401484 For units where the old sensor or parts list shows 50HJ401484. Carrier 50HJ401484 Hall Sensor — Replacement

If your checks point to the inducer motor itself, have the number from the motor label ready and browse our Carrier Replacement Parts collection, or ask us to match it.

Working on a residential Carrier 48VL package unit instead? There, 6 flashes points to the pressure switch and inducer, not a Hall Effect sensor. See Carrier 48VL 6 Flashes, Induced-Draft Motor Fault: Checks Before You Replace 345585-75111.

Which units this applies to

  • Carrier 48TCA04, 48TCA05, 48TCA06 and 48TCA07 single-package rooftop units (nominal 3 to 6 tons), as covered by 48TC-1SM
  • Units whose IGC shows 6 flashes for an induced-draft motor fault and whose inducer uses a Hall Effect speed sensor

Scope: The LED codes, alarm table, IGC connections and heating sequence come from 48TC-1SM and apply to the 48TCA04–A07 units it covers. 48TC-1SM does not list sensor part numbers. Match the replacement by the number on your old sensor or your unit's parts list: our listings cover Carrier 50HJ442730 and 50HJ401484.

Before you order

Have the full model and serial number from the unit's rating plate and the number on the old sensor. If the sensor has no readable number, contact us or email help@totalhvacparts.com with the model and serial and we will check it before you order.

Frequently Asked Questions

What does 6 flashes mean on a Carrier 48TC rooftop?

In 48TC-1SM, 6 flashes on the IGC LED is "Induced-Draft Motor Fault". The IGC either does not see inducer speed during a heat call, or sees it when there is no heat call.

What does the Hall Effect sensor do on a 48TC?

Carrier says the induced draft fan motor includes a Hall Effect sensor circuit that confirms adequate wheel speed to the IGC board. It connects to the IGC speed sensor input, SS (J1, pins 1–3).

Why does the inducer keep running with no flame?

That is the control's action for this fault. With a heat call, 48TC-1SM says the gas valve goes off and the inducer stays on until inducer sense returns to normal or the heat call ends.

Is 50HJ442730 the same as 50HJ401484?

Our 50HJ442730 listing states that it also replaces Carrier 50HJ401484, and we list the same sensor under both numbers.

Sources

Safety: Only qualified service personnel should do this work. Shut off the gas supply and lock out / tag out electrical power before opening the unit, and check for gas leaks with a soap solution after any repair.