On a Carrier 58CVA or 58CVX furnace, status code 34 means "Ignition Proving Failure": the burners lit, or tried to, but the control did not prove flame. Carrier's troubleshooting guide for these furnaces (Carrier TG-GFC80-01) lists oxide on the flame sensor, low flame current, gas supply and grounding as the things to check, and says to replace the flame sensor if the current stays low after cleaning. If your old sensor carries LH33WZ511, the part is Carrier LH33WZ511 Remote Sensor Bent Tip & 4 Inch Wire and Plug — Replacement, our verified replacement for Carrier LH33WZ511.
How do I read code 34 on a 58CVA?
TG-GFC80-01 says: "EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES." Code 34 is three short flashes followed by four long flashes.
To recall stored codes, the guide says to disconnect the "R" thermostat lead or ABCD connector, reset power, and put setup switch SW1-1 in the ON position. To clear the history, put SW1-1 ON and jumper R, W/W1 and Y/Y2 together until status code 11 flashes.
| Code | TG-GFC80-01 meaning |
|---|---|
| 34 | Ignition proving failure. "Control will try three more times before lockout #14 occurs." |
| 14 | Ignition lockout. The furnace "failed to ignite gas and/or prove flame in 4 attempts." The control auto-resets in 3 hours. |
What does Carrier say to check for code 34?
The code 34 entry in TG-GFC80-01 lists:
- Low inlet gas pressure
- Control ground continuity
- Gas valve defective or turned off
- Manual valve shut off
- "Oxide buildup on flame sensor (clean with fine steel wool)."
- Proper flame sense current: 0.5 microamps DC minimum, 4.0 to 6.0 nominal
- "Green/Yellow wire MUST be connected to furnace sheet metal."
- Inadequate flame carryover or rough ignition
- "Flame sensor must not be grounded."
The guide also notes that if flame signal is lost during the blower on-delay, the blower comes on for the selected blower off-delay.
How do I test the flame sensor?
The code 34 flowchart in TG-GFC80-01 works through the igniter, gas valve, burners and flame current. The flame sensor steps, in short:
- Confirm the code. Recall the stored codes with SW1-1 and make sure it is 34 (or 14 that refers you to 34).
- Check the igniter first. The guide's component test (SW1-6) turns the hot surface igniter and blower on for 15 seconds each. A new igniter should read 40 to 70 ohms cold.
- Check the gas valve. Confirm 24 VAC at the valve, the manual gas cock and valve switch are on, and the burners light.
- Measure flame current. With power off, connect a DC microammeter in series with the flame sensor wire, then restore power and start a heat call (the guide jumpers R, W/W1 and W2). Typical current is 4.0 to 6.0 microamps.
- Below 0.5 microamps: the flowchart says to clean the flame sensor with fine sandpaper, make sure it is properly positioned, and recheck the current.
- Still not near typical after cleaning: the flowchart step reads "Replace electrode." This is the flame sensor.
- Near typical, but the burners still drop out: the guide says to check connections and retry, then check flame carryover, inlet and manifold gas pressure and a slow-opening gas valve. If those are good, it says to replace the variable speed furnace control, not the sensor.
Field practice, not from the manual: a sensor with a cracked porcelain, a bent rod that no longer sits in the flame, or a damaged lead will usually not recover with cleaning. Replace it rather than clean it again.
What if it shows code 14 with the inducer running?
TG-GFC80-01 says that if the inducer is running at full speed during a code 14 lockout, flame sense was lost 3 times within 60 minutes of cumulative gas valve operating time, after the valve had already been on for 70 seconds. The guide says this is "usually caused by flame rollout", for example a vent pipe disconnected inside or near the furnace. Check the vent before you blame the sensor. If the inducer is not running during lockout, the guide sends you to code 34.
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Remote sensor with bent tip, 4 inch wire and plug (per our listing) | Primary fix when flame current stays low after cleaning and your old flame sensor carries LH33WZ511. Replaces Carrier LH33WZ511; the listing also replaces LH680012, LH680014 and LH680534. | Carrier LH33WZ511 Remote Sensor Bent Tip & 4 Inch Wire and Plug — Replacement |
| Same sensor, listed under LH680012 | If your old sensor or parts list shows LH680012. | Carrier LH680012 Remote Sensor Bent Tip & 4 Inch Wire and Plug — Replacement |
| Same sensor, listed under LH680014 | If your old sensor or parts list shows LH680014. | Carrier LH680014 Remote Sensor Bent Tip & 4 Inch Wire and Plug — Replacement |
| Same sensor, listed under LH680534 | If your old sensor or parts list shows LH680534. | Carrier LH680534 Remote Sensor Bent Tip & 4 Inch Wire and Plug — Replacement |
More Carrier parts are in our Carrier Replacement Parts collection. If the same furnace shows code 32 and the inducer will not start, see Carrier Furnace Code 32, Inducer Won't Start: Checks and Which 326628 Inducer Kit to Order.
Which units this applies to
- Carrier 58CVA two-stage, variable-speed, 4-way multipoise gas furnaces
- Carrier 58CVX (low-NOx version)
Scope: The status codes, checks and flowchart steps come from TG-GFC80-01 and apply to the 58CVA/58CVX furnaces it covers. Other Carrier furnaces use similar two-digit codes but may differ; use the guide for your model. TG-GFC80-01 does not list flame sensor part numbers and does not name LH33WZ511. Our LH33WZ511 listing is for a flame sensor that carries that number (or LH680012, LH680014 or LH680534); match the replacement by the number on your old sensor or your furnace parts list.
Before you order
Have the furnace model and serial number from the rating plate and the number on the old flame sensor or its parts list. If you cannot read it, contact us or email help@totalhvacparts.com with the model and serial and we will check it before you order.
Frequently Asked Questions
What does code 34 mean on a Carrier furnace?
On the 58CVA/58CVX, TG-GFC80-01 lists code 34 as "Ignition Proving Failure". The control did not prove flame and will try three more times before lockout code 14.
What flame current should a Carrier flame sensor read?
TG-GFC80-01 gives 0.5 microamps DC as the minimum and 4.0 to 6.0 microamps as nominal, measured with a DC microammeter in series with the flame sensor wire.
Can I clean the flame sensor instead of replacing it?
Yes, try that first. The code 34 list says to clean oxide buildup with fine steel wool; the flowchart says fine sandpaper. If the current is still not near typical after cleaning, the flowchart says to replace the electrode (flame sensor).
How long does a Carrier code 14 lockout last?
TG-GFC80-01 says the variable speed furnace control auto-resets in 3 hours. Find the cause of the code 34 first, or the furnace will lock out again.
Sources
- Carrier TG-GFC80-01 (Edition 11/13): Troubleshooting Guide, Mid-Efficiency Variable-Speed, Two-Stage Induced-Combustion Deluxe 4-Way Multipoise Gas Furnace, 58CVA/58CVX (status codes 14 and 34, code recall, component test, code 34 flowchart)
- Total HVAC Parts product listing: Carrier LH33WZ511 replacement (part numbers replaced)
Safety: Only qualified service personnel should do this work. Shut off the gas supply and lock out / tag out electrical power before opening the unit, and check for gas leaks with a soap solution after any repair.