Greenheck Kitchen Controls 'Temp Sensor Error' or Hood Fans Not Starting: Sensor 384925 Checks

A Greenheck Kitchen Controls panel that shows "Temp Sensor Error", or hood fans that will not start on their own when cooking begins, usually comes down to a greasy hood temperature sensor, a wiring fault, or set points that are too high. Greenheck's Kitchen Controls manual (document 484600) lists those causes first. The hood and supply sensor it names is part 384925, which we list as the Greenheck 384925 Temperature Sensor, Dwyer TE-IBN-E0448-00. Clean and check the sensor, the wiring and the set points before you replace it.

What does "Temp Sensor Error" mean on Greenheck Kitchen Controls?

The fault screen describes it as a faulty connection to, or failure of, a room or hood temperature sensor. The fault list on page 54 says what the panel does while the fault is active: "Associated fan(s) in that zone will be forced on (and to max speed, if VAV) until the fault is rectified." So a hood whose fans are running flat out with no cooking going on may be in this fault.

The manual's troubleshooting table gives three causes:

Possible cause (484600) Corrective action (484600)
"Dirty temperature sensor(s)" "Clean grease from temperature sensor(s)"
"Incorrect main board configuration" "Check the temperature sensor settings (consult factory)"
"Faulty wiring to temperature sensor(s)" "Check wiring at control panel and at hood connection / room sensor"

Why don't the hood fans turn on when cooking starts?

With the Room Temp setting on Preset, the manual says the fans in a zone turn on "If a hood temp sensor in that zone raises above preset room temp plus zone temp interlock offset temp". Room Temp can also be set to use a room sensor instead of the preset value. The defaults in the manual are a 25°F offset (range 1 to 50°F) and a 75°F Preset Room Temp (range 50 to 80°F). The troubleshooting table lists four causes when fans do not turn on automatically:

Possible cause (484600) Corrective action (484600)
"Dirty temperature sensor(s)" "Clean grease from temperature sensor(s)"
"The zone Temp Interlock Offset set point set too high" "Decrease the Temp Interlock Offset set point"
"Preset Room Temp is set too high" "Decrease the Preset Room Temp"
"Room sensor placed too close to the cooking equipment" "Move room sensor away from cooking equipment."

The opposite complaint, fans that will not shut off, has its own row: "Cooking temperatures detected, causing fans to stay on until cooking temperature subside." The fix there is to check the sensor readings under Diagnostics, Temp Sensors. With Auto Fan Off set to Yes, fans shut down once hood temperatures fall below the interlock offset minus the hysteresis (default 10°F) and stay there for the hysteresis timer (default 30 minutes).

How do you check the hood temperature sensor?

  1. Read the sensors on the panel. Diagnostics lets you view all room sensor and temperature sensor values. Compare each hood sensor with the room. Field practice, not from the manual: a sensor reading far off from the others on a cold hood, or a reading that never moves, points at that sensor or its wire.
  2. Clean the sensor. Grease on the probe is the first cause in both tables. Lock out the hood and clean it.
  3. Check the mounting. Page 6 says to mount the sensor on a flat area at the top inside of the hood, in front of the filters toward the front, and not within 12 inches (304.8 mm) of any light fixture. If the hood has no flat space, the sensor may go in the exhaust collar. It is sealed with compression seal 484000 and tightened to 35 ft-lbs (47.5 Nm).
  4. Check the wiring at both ends. The standard main board has inputs TS-1 to TS-8 for hood sensors. On hood control boards, TS-1 and TS-2 are for hood sensors and TS-3 and TS-4 for supply sensors. Factory supply plenum sensors are mounted inside the top left of the supply plenum.
  5. Check the room sensor. The manual says it is a PT1000 sensor wired with an 18 to 22 gauge pair to RS-A and RS-B, mounted as close to chest height (about 60 in. above the floor) as possible, and not too close to the hood, to a cooking appliance, or on the ceiling.
  6. Check the set points. If the sensors read correctly and the fans still do not start, review the Temp Interlock Offset and Preset Room Temp against the defaults above.
  7. Replace the sensor. If a clean, correctly wired sensor still reads wrong, replace it with the part number the manual lists.

Page 6 identifies the hood sensor as a "PT1000 Temperature Sensor (PN: 384925)". The manual does not publish a resistance table for it.

Parts that fix it

These part numbers come from the Kitchen Controls replacement parts list (page 82):

Component Role Link
Hood/supply temperature sensor Listed by Greenheck as "Hood/Supply Temp Sensor Only" (384925) Greenheck 384925 Temperature Sensor, Dwyer TE-IBN-E0448-00
Hood/supply sensor assembly Listed as "Ship Loose Hood and Supply Temp Sensor Assembly" (1022388) Greenheck 1022388 Temperature Sensor Assembly, Ship Loose
Room sensor assembly Listed as "Ship Loose Room Sensor Assembly" (1022391); used when the interlock reads room temperature Greenheck 1022391 Room Sensor Assembly, Ship Loose

The compression seal (484000) is also in the parts list. For hood filters and lights, see our articles on Grease Grabber filters and hood lights.

Which units this applies to

  • Greenheck Kitchen Controls panels covered by 484600 (software PRG V5.00): Standard and Advanced platforms.
  • Constant volume, variable volume (DCV/VAV) and sump-wash-only applications, as described in the manual.
  • Older Greenheck kitchen fan control centers and temperature interlocks have their own manuals and may use different sensors.

Scope: Fault descriptions, troubleshooting rows, set point defaults, mounting rules and part numbers come from Greenheck document 484600. The manual defers incorrect board configuration to the factory. Check the software version on your panel against the manual before you change settings.

Before you order

Note the panel's software version, the hood model and serial number, which sensor input reports the problem (TS number or room sensor), and the part number on the old sensor. To confirm fit, contact us or email help@totalhvacparts.com, or browse Valent, Innovent & Greenheck Replacement Parts.

Frequently Asked Questions

Why are my Greenheck hood fans running at full speed with no cooking?

A "Temp Sensor Error" forces the fans in that zone on, and to maximum speed on VAV systems, until the fault is fixed. Check the fault screen, then clean and check the hood and room sensors.

What causes Temp Sensor Error on Greenheck Kitchen Controls?

Manual 484600 lists dirty sensors, incorrect main board configuration and faulty wiring at the panel, hood connection or room sensor.

What is the default temperature interlock offset?

25°F, with a range of 1 to 50°F. The default Preset Room Temp is 75°F, with a range of 50 to 80°F.

Where should the hood temperature sensor be mounted?

On a flat area at the top inside of the hood, in front of the filters toward the front, and not within 12 inches of a light fixture. If there is no flat space, it can go in the exhaust collar.

Sources

Kitchen exhaust controls work with line-voltage fans, hood lights and fire suppression interlocks. Service should be performed only by qualified personnel, following Greenheck's manual, local fire codes and your facility's lockout/tagout procedures.