Skip to content

Greenheck Kitchen Hood Light Out: Round LED 483765, Bulbs and Wiring Checks

When a light in a Greenheck kitchen hood goes out, the fix depends on the fixture type. Greenheck's hood manual (document 452413) says bulbs are not provided except on hoods with round LED fixtures, so an incandescent or CFL fixture takes a standard E26 base bulb up to 100 watts. A round LED fixture is replaced as a unit: Greenheck lists it as part 483765, and the clear glass globe as part 453498. Check the circuit first.

What kind of light does your hood have?

Greenheck document 452413 (Kitchen Hoods, Type I and Type II IOM, Rev. 23) lists these fixture types and ratings:

Fixture (452413) Lamp or rating
Incandescent or CFL fixture Standard E26 base bulb up to 100 watts (bulbs not provided)
Fluorescent fixture Check the label inside the fixture for the recommended tube type
Round 8-inch LED hood light 115 VAC, 20 watts per fixture, black and white wires
LED fixture specification 115 VAC, 50-60 Hz, 0.167 A each, 1800 lumens, 3900-4100K, dimmable (0-10 VDC)
Supply plenum LED puck lights 3.5 watts each, 115 VAC

The manual's replacement parts list gives 453498 as the clear glass globe for hood lights and 483765 as the hood 8-inch round LED light.

How is the hood light circuit wired?

Greenheck's wiring notes in 452413:

  • Field connections are made in a junction box on top of the hood.
  • Use minimum 14 AWG copper wire.
  • All 115 VAC field wiring must be high-temperature rated and run in hard or flex conduit.
  • Wiring must not contact the hood surface.
  • On hoods wired for incandescent fixtures with more than 14 lights in total, wire them to multiple circuits with fewer than 14 lights per circuit.
  • The Type I wiring diagram shows 115 VAC for lights at 1200 W maximum; the Type II diagram shows 1400 W maximum. Use the diagram for your hood.

How do you troubleshoot a hood light that is out?

  1. Check whether one light or all are out. All lights out points to the switch, breaker or circuit. One light out points to that fixture or its lamp.
  2. Check the breaker and switch for the hood light circuit, and that the circuit is not over the maximum on your wiring diagram.
  3. Lock out the circuit. Let the fixture cool before you touch it.
  4. Incandescent or CFL fixture: replace the bulb with a standard E26 base bulb up to 100 watts, the limit Greenheck gives.
  5. Fluorescent fixture: read the label inside the fixture for the tube type before you buy a tube.
  6. Round LED fixture: there is no bulb to change. Have a qualified electrician restore power, switch the lights on and check for 115 VAC at the fixture leads (black and white), then lock out again. Voltage present with the fixture dark means the fixture has failed; replace it.
  7. Dimmed LED hoods: the LED fixtures are dimmable on a 0-10 VDC signal. If all the LEDs are dim or dark on a dimmed circuit, check the dimmer signal before replacing fixtures.
  8. Check the globe. A cracked or missing globe should be replaced. Greenheck lists clear glass globe 453498 for hood lights.

Our practical advice: when you open a fixture, look at the wiring in the junction box above it. Greenheck requires high-temperature rated wire for this circuit. Heat-damaged or brittle insulation should be corrected by an electrician before the new fixture goes in.

Parts that fix it

Component Role Link
Round LED hood light 8-inch round LED fixture listed as part 483765 in 452413 Greenheck 483765 Light, Round, Led-L80-20Dn
Clear glass globe Globe for hood lights, listed as part 453498 in 452413 Greenheck 453498 Light Globe, L50-X011

Which units this applies to

  • Greenheck Type I canopy hoods covered by 452413: GH (baffle), GX (Grease-X-Tractor) and GG (Grease Grabber) models.
  • Proximity and crossover hood configurations, and the GO and GD hoods, listed in the same manual.

Scope: Fixture types, ratings, wiring rules and the 453498 and 483765 part numbers are from Greenheck document 452413, Rev. 23. The manual's parts list names the LED as LED-80-20DN; our listing title reads Led-L80-20Dn. Match the part number on your fixture before ordering.

Before you order

Read the hood model and serial number from the hood label and note the fixture type (round LED, incandescent, CFL or fluorescent) and how many lights are out. To confirm fit, contact us or email help@totalhvacparts.com with the model, serial number and old part number.

Frequently Asked Questions

What bulb does a Greenheck kitchen hood light take?

Greenheck manual 452413 says incandescent and CFL fixtures take a standard E26 base bulb up to 100 watts. Bulbs are not provided unless the hood has round LED fixtures.

What is the Greenheck part number for the round LED hood light?

452413 lists 483765 as the hood 8-inch round LED light. It is rated 115 VAC, 20 watts per fixture.

Are Greenheck hood LED lights dimmable?

Yes. The LED fixture specification in 452413 lists them as dimmable on a 0-10 VDC signal.

What wire is required for Greenheck hood lights?

Minimum 14 AWG copper. All 115 VAC field wiring must be high-temperature rated, run in hard or flex conduit, and must not contact the hood surface.

Sources

Hood light circuits carry 115 VAC and the fixtures sit over hot cooking equipment. Service should be performed only by qualified personnel, following Greenheck's manual, the electrical code and your facility's lockout/tagout procedures.