Greenheck Kitchen Controls 'Exh. Fan Not Proving' or 'Proving Loss': Current Switch 1022214 Checks

When Greenheck Kitchen Controls shows "Exh. Fan Not Proving", "Sup. Fan Not Proving" or a "Proving Loss" fault, the panel did not see enough fan current, so it shut the fans off and is waiting for a manual reset. On fans without Modbus VFDs, proving comes from a current switch on one leg of the fan's power. Greenheck's Kitchen Controls manual (document 484600) lists that switch as part 1022214, "Current Switch for fan proving operation". Check that the fan really runs, that the conductor passes through the switch, and the Proving % setting before you replace the switch.

What do the proving faults mean?

Fault as displayed Meaning (484600, p. 33) Reset
Sup. Fan Not Proving Supply fan failed to prove Manual reset
Sup. Fan Proving Loss Supply fan failed to prove during operation Manual reset
Exh. Fan Not Proving Exhaust fan failed to prove Manual reset
Exh. Fan Proving Loss Exhaust fan failed to prove during operation Manual reset
Proving Calib. Failed Fan calibration test failed See calibration below

The fault list on page 54 says each Not Proving and Proving Loss fault "Requires manual reset to allow fan operation to continue". The manual says the fan proving faults are the ones that need the RESET button on the current faults screen; the others clear on their own.

How does Greenheck fan proving work?

Fan proving is an option in the panel settings. The manual says: "This setting provides a means to interlock fan operation based on local code." It can be set to No, Supply Only, or Exhaust and Supply. The sequence, from pages 36 and 37:

  • Fan monitoring uses current sensor switches. On VFDs controlled over Modbus, monitoring runs over the VFD communication to the main board instead.
  • Supply fans in a zone start first. "They are given a maximum of 90 seconds to prove." If they do not, they shut off and a fault occurs.
  • "Next, the exhaust fans on that zone will be given a maximum of 90 seconds to prove." A failure shuts off both exhaust and supply fans.
  • "If there is a loss of proving for 15 consecutive seconds, a proving fault will occur, and all fans will shut off."

The Proving % setting (pages 42 and 44) "Sets the minimum percentage of drive rated amperage that needs to be detected in order for fan to prove." The default is 20%, with a range of 1 to 100%. It only appears for fans that are not on Modbus VFD control.

How do you check the current switch?

  1. Make sure the fan actually runs. Field practice, not from the manual: look at the fan. A broken belt, a tripped overload or a failed motor will fail proving every time, and a new switch will not fix that.
  2. Check the conductor through the switch. Page 12 says "one hot leg needs to be wired through the current switch opening." Page 19 says to route one fan power leg through the middle of the switch unless the factory already did. Some switches are shipped loose (labelled CS-E/S_ (SHIP LOOSE) on the diagram), so check that one was installed on each proven fan.
  3. Check the low-voltage leads. The two leads go back to terminal blocks E/S_-PA and E/S_-PB in the panel.
  4. Watch the red LED. Page 19 says the switch has a 0.5A fixed set point, and its red LED shows the set point has been reached and the contacts are closed, meaning the fan is proving.
  5. Small fan, low current? Page 19 says to wrap the conductor through the sensing hole for more turns: "Measured current = actual current x the number of turns."
  6. Check the Proving % setting. A Proving % set higher than the fan draws at its running speed will fail a good fan. The default is 20%.
  7. Run Fan Calibration. Page 49 says calibration starts the fans (at minimum speed on VAV systems) and reports "Successful" or "Unsuccessful" after 90 seconds. An Unsuccessful result is the "Proving Calib. Failed" fault.
  8. Replace the switch. If the fan draws current, the conductor passes through the switch and the LED never lights, the switch is the suspect.

What if the fans run on VFDs?

With VFDs on Modbus, proving comes over VFD communication, not a current switch. The panel has separate "VFD Alarm" and "VFD Communication" faults. The parts list includes the Modbus harnesses and cables, so a damaged cable is worth checking:

Component Role Link
Current switch Proves fan operation on non-Modbus fans; listed as 1022214 in the parts list Greenheck 1022214 Current Switch, 1P, 135V, 0-200A, Dwyer CCS-121050
A1000/V1000 VFD Modbus harness Parts list: "A1000/V1000 VFD 10" Modbus Harness" (386937) Greenheck 386937 Elec, Cord, Shld, 24G-8C, Rj45,300V, 10In
GA500 VFD Modbus harness Parts list: "GA500 VFD 10" Modbus Harness" (388431) Greenheck 388431 Cord, Shielded RJ45, 24G-8C, 300V, 10", GA500
4 ft RJ45 cable Parts list: "4FT RJ45 CAT5 User Interface/VFD Cable" (386816) Greenheck 386816 Cord, Cat5E, 4 Pair, 300V, 75C, Green, 4Ft, Rj45

Our article on belt-drive exhaust fans that won't run covers the fan side. The live titles above use the supplier's descriptions; the Greenheck part numbers match the Kitchen Controls parts list.

Which units this applies to

  • Greenheck Kitchen Controls panels covered by 484600 (software PRG V5.00), Standard and Advanced platforms, with fan proving enabled.
  • Constant volume and variable volume (DCV/VAV) kitchen ventilation systems controlled by that panel.
  • Fans on Modbus VFDs prove over VFD communication and do not use the current switch.

Scope: Fault names, the proving sequence, the 90-second and 15-second timers, the Proving % default, current switch wiring and the part numbers come from Greenheck document 484600. Fan proving requirements come from your local code; the manual says the setting interlocks fan operation based on local code.

Before you order

Write down the exact fault text, which fan it names, whether that fan is on a VFD, and the panel's software version. Note the hood or panel serial number. To confirm the part, contact us or email help@totalhvacparts.com, or browse Valent, Innovent & Greenheck Replacement Parts.

Frequently Asked Questions

What does Exh. Fan Not Proving mean on Greenheck Kitchen Controls?

The exhaust fan failed to prove. The panel gives exhaust fans up to 90 seconds to prove after the supply fans; a failure shuts off both exhaust and supply fans, and the fault needs a manual reset.

How do I reset a fan proving fault?

Fix the cause, then press RESET on the current faults screen. Manual 484600 says proving faults require a manual reset to allow fan operation to continue.

What is the default Proving % on Greenheck Kitchen Controls?

20%, with a range of 1 to 100%. It is the minimum percentage of drive rated amperage that must be detected for the fan to prove, and it applies to fans not on Modbus VFD control.

Why does a small fan fail proving with a good current switch?

The switch has a 0.5A fixed set point. The manual says to wrap the conductor through the sensing hole more times; measured current equals actual current times the number of turns.

Sources

Fan proving circuits run through line-voltage fan conductors. Service should be performed only by qualified personnel, following Greenheck's manual, the electrical code and your facility's lockout/tagout procedures.