On an ICP *8MPN or *8MPL 80% single-stage furnace, 4 flashes on the control's diagnostic light means "Limit or roll-out switch open (less than 2 minutes)", and 7 flashes means the switch stayed open longer than 2 minutes and the control went into a soft lockout. ICP's installation instructions (form 441 01 2613 06) tie temperature rise to blower speed. Field practice, not from the manual: a blower that is not moving enough air is a common reason a limit opens. If the PSC blower motor has failed and its label reads 1009053, the part is International Comfort (ICP) 1009053 Blower Motor 1/2 Hp — Replacement, our verified replacement for ICP 1009053.
What do 4 and 7 flashes mean on an ICP 80% furnace?
The diagnostic code table in the ICP instructions lists these codes:
| Diagnostic light | Meaning (ICP 441 01 2613 06) |
|---|---|
| OFF | 24 VAC or 115 VAC is off, or the fuse is open |
| Heartbeat | Normal operation, or no previous diagnostic code |
| 2 flashes | Pressure switch(es) closed when they should be open |
| 3 flashes | Pressure switch open when it should be closed |
| 4 flashes | "Limit or roll-out switch open (less than 2 minutes)" |
| 5 flashes | Flame sensed out of sequence |
| 6 flashes | Failure to ignite, or flame sense lost while running |
| 7 flashes | Soft lockout: limit or roll-out switch open longer than 2 minutes (1 hour delay). The roll-out switch requires a manual reset. |
| 10 flashes | 115 VAC line voltage polarity reversed |
The same table lists "ON solid" as a soft lockout for a furnace control error, 6 + 1 flashes as a lockout after the maximum ignition trials, and 8 flashes as a permanent lockout for a gas valve relay or wiring fault.
How does the blower affect the limit on these furnaces?
ICP's sequence of operation: on a heat call the inducer starts and the pressure switch must close. After a 15-second prepurge the igniter warms up for 17 seconds, the gas valve opens and the burners light. The control delays the blower 30 seconds from gas valve opening. When the call ends, the gas valve closes, the inducer post-purges for 15 seconds, and the blower stays on at heat speed until the selected heat fan off delay ends.
The instructions say blower speed must be set to give the temperature rise marked on the rating plate, and that "A higher blower speed will lower the temperature rise." A lower speed raises it. ICP also warns that, to avoid reduced furnace life, you should use only the blower speed taps listed in the furnace's blower data.
Field practice, not from the manual: if the blower does not start, starts slowly, or runs well below its normal speed, the heat exchanger runs hot and the limit opens. A dirty filter or closed registers do the same thing, so check those before you condemn the motor.
How do I check the blower motor before I replace it?
- Read the code. Count the flashes. 4 flashes is a limit or roll-out open now; 7 flashes is the lockout.
- Check the roll-out switch. ICP says the roll-out switch requires a manual reset. If it is open, find out why before you reset it.
- Confirm the temperature rise. Compare the measured rise with the range on the rating plate. ICP's fix for a high rise is a higher blower speed, using only the taps listed in the blower data.
- Watch the blower on a heat call. It should start about 30 seconds after the gas valve opens.
- Field practice, not from the manual: if it does not start or runs slow, check voltage, the run capacitor and the motor. With power off and the capacitor discharged, check the capacitor against the value printed on it, and check the motor windings for opens and for shorts to ground. The ICP specification tables list the capacitor for each size (for example 10/370 or 7.5/370 on 1/2 HP models, 40/370 on 3/4 HP models).
- Lock out power before you change speed taps or the motor. ICP's instructions say to turn off power, lock out and tag the switch before changing taps.
Blower motor sizes in ICP's specification tables:
| Model family | Blower motor (type / HP) |
|---|---|
| N8MPN | PSC 3/4 HP on 100J22 and 125J22; PSC 1/2 HP on all other sizes |
| N8MPL | PSC 3/4 HP on 100J22 and 125J22; PSC 1/2 HP on all other sizes |
| *8MPN | PSC 3/4 HP on 150J20; PSC 1/2 HP on all other sizes |
Parts that fix it
| Component | Role | Link |
|---|---|---|
| Blower motor, 1/2 HP | Primary fix when a 1/2 HP blower motor labeled 1009053 has failed. The listing also replaces ICP 1012513, 1013341, 1172487, 603688, 604007, 609277, 609887, 84748 and 99728. | International Comfort (ICP) 1009053 Blower Motor 1/2 Hp — Replacement |
| Blower motor, 1/2 HP | Same replacement, listed under ICP 1013341 for motors carrying that label number. | International Comfort (ICP) 1013341 Blower Motor 1/2 Hp — Replacement |
More ICP parts are in our International Comfort (ICP) Replacement Parts collection.
Which units this applies to
- Codes, sequence and blower guidance: ICP 80% single-stage, Category I furnaces N8MPN, N8MPL, C8MPN, H8MPN, T8MPN, C8MPL, H8MPL and T8MPL, covered by ICP installation instructions 441 01 2613 06.
- Parts: any furnace whose existing blower motor label reads 1009053 or one of the numbers the listing replaces.
Scope: The ICP instructions list blower motor type, horsepower and capacitor by model, but not blower motor part numbers. This article does not claim that 1009053 is the motor in a given model. Match the motor by the number on the old motor's label. Sizes with a 3/4 HP motor need a 3/4 HP motor, not this one.
Before you order
Read the part number, horsepower and capacitor rating on the old motor, and have the furnace model and serial number from the rating plate. If your label number is not one listed above, contact us or email help@totalhvacparts.com with the model, serial and old part number and we will check it before you order.
Frequently Asked Questions
What does 4 flashes mean on an ICP furnace?
On *8MPN / *8MPL furnaces, ICP's code table says 4 flashes is "Limit or roll-out switch open (less than 2 minutes)."
Why did my ICP furnace go to 7 flashes?
The limit or roll-out switch stayed open longer than 2 minutes, so the control entered a soft lockout with a 1-hour delay. A roll-out switch must be reset by hand.
Can a bad blower motor cause a limit code?
ICP ties temperature rise to blower speed. Field practice, not from the manual: a blower that is not moving enough air raises the rise and can open the limit. Check the filter, rise and blower operation before replacing the motor.
Is 1009053 a 1/2 HP or 3/4 HP motor?
Our listing is a 1/2 HP blower motor. ICP's tables show some sizes use 3/4 HP motors; those need a different motor.
Sources
- ICP (International Comfort Products) Installation Instructions, 80% Single Stage, Category I Gas Furnace, form 441 01 2613 06 (July 2010): N8MPN, N8MPL, C8MPN, H8MPN, T8MPN, C8MPL, H8MPL, T8MPL (diagnostic codes, sequence of operation, temperature rise, specifications)
- Total HVAC Parts product listing: ICP 1009053 replacement
Safety: Only qualified service personnel should do this work. ICP warns that if sparks, odors or unusual noises occur, you should immediately shut off gas and power to the furnace. Lock out and tag out power before changing speed taps, testing the capacitor or replacing the motor.