Skip to content

Greenheck Kitchen Controls 'Low Detergent' Fault: Refill, Float Sensor 385987 and Pump Fuse

A "Low Detergent" fault on Greenheck Kitchen Controls means the float in the 2.5 gallon detergent tank has dropped, and the panel will not run the detergent pump until it is cleared. Greenheck's Kitchen Controls manual (document 484600) says the detergent pump "will not operate until low detergent fault is rectified (detergent is refilled)". Refill the tank first. If the fault stays on with a full tank, check the float switch wires, then replace the float, part 385987, which we list as the Greenheck 385987 Asm, Float, 8" Snsr, For 2.5G Tank.

What does the Low Detergent fault do?

The fault screen describes it this way: "Indicates detergent is low and needs to be refilled for washing Auto Scrubber hoods or duct sumps". On page 9 the manual explains where the signal comes from: "The tank is also equipped with a float that will trigger an alarm to warn the user when detergent is low." The fault list adds that the pump is locked out until the fault is fixed, so Auto Scrubber hood washes and duct sump washes run without detergent, or not at all, while it is active.

The float and the pump share one connector on the main board. Page 80 lists it as "J6 Detergent Float Switch Input and Detergent Pump 24VAC Output Connector". For a building automation system, the fault is also reported over Modbus and BACnet.

How often should the detergent tank need filling?

Item (484600, p. 9) What the manual says
Tank size The tank holds up to 2.5 gallons (9.5 liters) of detergent
Consumption "If washed once a day, the 2.5 gallon detergent tank will last approximately 24 to 30 days depending on filter type."
Detergent "Detergent model X-701 manufactured by ZEP, Inc., is recommended by Greenheck for use in the wash system."
Tank cleaning "Clean the detergent tank at least every six months."
Strainer "Clean the detergent line strainer at least every six months."
Pump "The detergent pump motor has sealed bearings which do not require lubrication."

If the fault comes back much sooner than the manual's 24 to 30 days at one wash a day, look at how often the system is washing before you suspect the float. Field practice, not from the manual: a wash schedule set to run more than once a day, or a leak at a fitting, empties the tank early. The manual's maintenance list also says to check the tightness of all fittings periodically.

How do you clear the fault and check the float?

Page 9 gives the tank removal and installation steps. We have added the checks in between:

  1. Disconnect the float. "Disconnect the two float switch wires at the quick connect electrical fittings."
  2. Remove the detergent line. Take out the 1/4-inch (6.35 mm) detergent line that enters the tank through the screw-on cap.
  3. Lift out the tank from the utility cabinet.
  4. Remove the cap. Unscrew the 63 mm cap from the tank; this removes the float assembly with it.
  5. Inspect and test the float. Field practice, not from the manual: clean any dried detergent off the float so it moves freely, then check the switch with a meter as you raise and lower it. It should change state. A float that is stuck, cracked or never changes state is the fault.
  6. Fill the tank with the approved detergent.
  7. Reinstall. Install the 63 mm cap and float assembly, lift the tank back into the cabinet, run the 1/4-inch line through the hole in the cap, and reconnect the two float switch wires.
  8. Check the fault screen. Most Kitchen Controls faults clear on their own once the cause is gone; only fan proving faults need the RESET button.

The fault clears but nothing washes. Now what?

The pump's 24 VAC output runs through J6 and a detergent pump fuse. The parts list (page 83) names a 3A detergent pump fuse, a fuse holder and a cover. Field practice, not from the manual: with the panel safe to work in, check that fuse before you condemn the pump, and clean the detergent line strainer, which the manual says to do every six months anyway. Greenheck lists the detergent pump itself as part 484148, and the J6 harness as 1044438 ("Wire Harness, Detergent Pump and Float 4-Wire (J6)"). If you need either, contact us with the panel serial number.

Parts that fix it

Component Role Link
Float sensor assembly Parts list 385987, "Float Sensor and Cab Assembly"; triggers the Low Detergent fault Greenheck 385987 Asm, Float, 8" Snsr, For 2.5G Tank
Detergent pump fuse, 3A Parts list 380750, "Fuse, Detergent Pump 3A" Greenheck 380750 Fuse, 3A, 250V, Time Delay
Fuse holder Parts list 388334, "Fuse Holder, Detergent Pump" Greenheck 388334 Fuse Holder, 30A, 250V, CLR, 1 Pole, LFR250301P
Fuse holder cover Parts list 388335, "Fuse Holder Cover, Detergent Pump" Greenheck 388335 Cover, CLR, 250V, 30A, LFH25030FBC

For other Kitchen Controls faults, see our articles on Temp Sensor Error and hood sensor 384925 and fan proving faults and current switch 1022214.

Which units this applies to

  • Greenheck Kitchen Controls panels covered by 484600 (software PRG V5.00) that control Auto Scrubber hood washing or duct sump washing.
  • Sump wash only (SWO) panels, which the manual says can control up to 8 duct sumps.
  • Older Greenheck wash control panels have their own manuals.

Scope: The fault description, tank size, consumption, detergent recommendation, maintenance intervals, tank steps, the J6 description and part numbers come from Greenheck document 484600. The manual has no troubleshooting row for Low Detergent and no test procedure for the float; the float and fuse checks above are labelled as field practice. Our listing titles use the supplier's descriptions; the Greenheck part numbers match the manual's parts list.

Before you order

Note the panel's software version, the hood or panel serial number, and the number on the old float. To confirm fit, contact us or email help@totalhvacparts.com, or browse Valent, Innovent & Greenheck Replacement Parts.

Frequently Asked Questions

What does Low Detergent mean on Greenheck Kitchen Controls?

The float in the detergent tank reports low detergent. Manual 484600 says the detergent pump will not operate until the fault is rectified, which means the detergent is refilled.

How long does a Greenheck detergent tank last?

The manual says that if washed once a day, the 2.5 gallon tank will last approximately 24 to 30 days depending on filter type.

What detergent does Greenheck recommend for the hood wash system?

Greenheck's manual recommends detergent model X-701 manufactured by ZEP, Inc.

Why is Low Detergent still showing after I filled the tank?

Check that the two float switch wires are connected at their quick connect fittings and that the float moves freely. If it still reads low with a full tank, replace the float sensor assembly, part 385987.

Sources

Hood wash systems combine line voltage, 24 VAC controls, hot water and detergent. Service should be performed only by qualified personnel, following Greenheck's manual, the detergent maker's safety data sheet and your facility's lockout/tagout procedures.

← ICP Furnace 4 or 7 Flashes, Limit Open: B...Carrier or Bryant AC Outdoor Fan Not Runn... →