A York YK-EP is a YK-type centrifugal chiller with a second, smaller compressor added on an economizer loop. York form 160.77-O1 says the YK-EP "operates much the same as the YORK YK Single Stage chiller", with the only exception being "a small economizer loop to compress partially expanded gas to extend capacity and improve efficiency." Per renewal-parts form 160.77-RP1, the YKEP Mod A uses a K7 primary compressor plus a Q3 economizer compressor, so its unique parts are the Q3 compressor, its pre-rotation vanes, VGD, oil cooler, starter and the economizer relief valves.
How does the YK-EP economizer loop work?
Form 160.77-O1 (425), Section 1, describes the refrigerant path. In York's words, step 4:
- "The refrigerant liquid from the condenser is partially expanded to a pressure intermediate to the evaporator and condenser."
- "The partially expanded two phase refrigerant is separated to liquid and vapor streams in the economizer."
- "The liquid stream is expanded a second time to repeat the cycle in the evaporator."
- "The vapor stream is drawn out of the economizer by the economizer compressor."
Step 5 adds: "The high pressure vapor refrigerant is then discharged from the economizer compressor to the condenser." York also notes that economizing "extends the refrigerating effect of the flow through the evaporator and primary compressor."
What does the YK-EP parts list add compared with a YK?
The table of contents of form 160.77-RP1 shows the extra hardware. Most compressor sections appear twice, once for the K7 primary and once for the Q3 economizer compressor. A PRV position sensor kit table appears for the Q3 only.
| 160.77-RP1 section | What it shows |
|---|---|
| Cover | Model YKEP, 2,700 to 3,200 ton, R-134a |
| Primary Compressor (K7) Components, Pre-Rotational Device, Variable Geometry Diffuser, Gear Set | The main compressor, a K7 |
| Economizer Compressor (Q3) Components, Pre-Rotational Device, Variable Geometry Diffuser, PRV Position Sensor Kit, Gear Set | The second, economizer compressor, a Q3 |
| Oil Pump Housing; Oil Filter Arrangement | Oil pump housing table includes "Cooler Oil Q3" 026-45980-000; the oil filter table shows single and dual filter arrangements for both the Q3 and the K7 |
| Liquid Cooled Solid State Starter | Starter parts, including coolant inhibitor 013-04129-000 |
| Relief Valves (Evaporator), (Condenser) and (Economizer) | A separate relief valve table for the economizer |
Form 160.77-O1 also describes a solid state starter for the economizer compressor motor. Form 160.77-RP1 lists coolant inhibitor 013-04129-000 in its liquid-cooled SSS table, so the YK-EP starter has its own coolant loop to maintain.
Which parts are unique to the YK-EP economizer compressor?
Form 160.77-RP1 (825) lists these Q3 economizer compressor items, among others:
| Table | Item as listed | York part number | Qty |
|---|---|---|---|
| Table 8, Q3 components | 1 Impeller 4.16 Eye Hard Coat Q3 | 364-51661-001 | 1 |
| Table 8, Q3 components | 29 Ring Eye Seal Q3 | 064-51575-000 | 1 |
| Table 8, Q3 components | 107 Wiring PRV Motor Actuator | 375-49340-101 | 2 |
| Table 8, Q3 components | 107A Motor Actuator 150 450 In | 025-17175-002 | 1 |
| Table 8, Q3 components | 193 Device PRV Q3 | 364-51554-003 | 1 |
| Table 8, Q3 components | 302 Device VGD Q3 | 364-51553-001 | 1 |
| Table 9, Q3 pre-rotational device | 11 Housing PRV Q3 | 064-51570-000 | 1 |
| Table 10, Q3 VGD | 1 Ring Diffuser Q3 and Q4 VGD | 064-51565-000 | 1 |
| Table 11, Q3 PRV position sensor kit | 4 Pot 2500 Ohms 2 Watt | 025-32570-000 | 1 |
| Table 11, Q3 PRV position sensor kit | 6 Cable PRV Sensor VSD | 571-02012-005 | 1 |
| Table 3, oil pump housing | 32 Cooler Oil Q3 | 026-45980-000 | 1 |
On the K7 primary compressor, Table 5 lists item 6 "Wiring PRV Motor Actuator" 375-49340-105, quantity 2. That is a different kit from the -101 on the Q3, so check which compressor you are working on.
Which YK-EP parts are also listed for a YK?
Many 160.77-RP1 line items also appear on our YK Mod G parts page. Form 160.77-RP1 lists, for example:
- Filter drier 3/8 ORFS, 026-37563-000, quantity 2 (Table 2, unit piping, item 47).
- O-rings from the 028-12961 family: -015 (0.739 ID x 0.070 thick, qty 10, Table 2), -021 (0.301 ID x 0.064, Table 5), -003 (0.468 ID x 0.078, qty 10, Table 8) and -004 (0.644 ID x 0.087, qty 2, Table 8).
- Coolant inhibitor 013-04129-000 for the liquid-cooled SSS (Table 12).
On our YKEP Mod A page, three O-ring dash numbers appear that are not on any of our YK model pages: 028-12961-019, -020 and -022.
Parts involved
| Component | Role | Where to find it |
|---|---|---|
| Q3 PRV actuator wiring kit | Economizer compressor, Table 8 item 107 | York 375-49340-101 ACTUATOR/WIRING, PRV Kit | OEM Chiller Part |
| K7 PRV actuator wiring | Primary compressor, Table 5 item 6 | York 375-49340-105 Wiring, Actuator | OEM Chiller Part |
| Q3 motor actuator | Table 8 item 107A | York 025-17175-002 Motor, Actuator (150DEG, 450") | OEM Chiller Part |
| PRV position sensor potentiometer | Table 11 item 4 | York 025-32570-000 Potentiometer (2500 Ohms, 2W) | OEM Chiller Part |
| Filter drier | Unit piping, qty 2 | York 026-37563-000 Filter Drier, 3/8" ORFS | OEM Chiller Part |
| SSS coolant | Liquid-cooled SSS, Table 12 | York 013-04129-000 Inhibitor, Corrosion (1 Gallon) | OEM Chiller Part |
| O-ring on YKEP page only | Listed on our YKEP Mod A page | York 028-12961-019 O-Ring, 1.489" x 0.07" | OEM Chiller Part |
| O-ring on YKEP page only | Listed on our YKEP Mod A page | York 028-12961-020 O-Ring, 1.720" x 0.118" | OEM Chiller Part |
| O-ring on YKEP page only | Listed on our YKEP Mod A page | York 028-12961-022 O-Ring, 1.176" x 0.070" | OEM Chiller Part |
| Q3 impeller, PRV and VGD devices, oil cooler | York numbers in the table above | Not listed individually; contact us with the York number |
Which York units this applies to
- York YKEP Mod A parts: the K7 plus Q3 unit covered by 160.77-RP1.
- York YKEP Mod B parts: our page currently lists starter and drive parts only; send your nameplate for compressor parts.
- York YK Mod G parts: the single-compressor YK; K7 (YDHA 119) is one of its compressor codes per 160.75-RP2.
- York YK Mod H parts: also covered by 160.75-RP2 compressor tables.
Scope: York form 160.77-RP1 (825), YKEP Mod A chiller with economizer compressor, 2,700 to 3,200 ton, R-134a, and form 160.77-O1 (425), YK-EP operation and maintenance (Section 1 system description). York marks RP manuals as reference only. Other YK-EP styles may use different compressors and parts.
Before you order
Read the chiller model and serial number from the nameplate, and note whether the part is on the primary (K7) or economizer (Q3) compressor. To confirm fit, contact us at help@totalhvacparts.com or 610-487-7999 with the model, serial number and part number.
Frequently Asked Questions
What is the difference between a York YK and a YK-EP?
York form 160.77-O1 says the YK-EP operates much the same as the YK single-stage chiller, except for a small economizer loop with its own economizer compressor that compresses partially expanded gas to extend capacity and improve efficiency.
Which compressors are in a York YKEP Mod A?
York form 160.77-RP1 lists a K7 primary compressor and a Q3 economizer compressor, each with its own pre-rotation device, variable geometry diffuser and gear set tables.
Where does the York YK-EP economizer compressor discharge?
Per form 160.77-O1, the economizer compressor draws vapor out of the economizer and discharges high pressure vapor to the condenser.
Which PRV actuator wiring kit is on the YK-EP economizer compressor?
Form 160.77-RP1 Table 8 lists 375-49340-101, quantity 2, on the Q3 economizer compressor; the K7 primary lists 375-49340-105.
Sources
- York form 160.77-RP1, YKEP Mod A chiller with economizer compressor renewal parts (cover, table of contents, Tables 2, 3, 5, 8, 9, 10, 11, 12)
- York form 160.77-O1 (425), YK-EP centrifugal chiller operation and maintenance (Section 1, system fundamentals, steps 4 and 5)
- York form 160.75-RP2, YK Style G and H compressors (compressor model and code list)
- Live product titles for the parts listed above, as shown on each product page
A YK-EP has two compressors, two motors and multiple starters or drives, all at line voltage, with refrigerant under pressure. Service should be performed only by qualified personnel, following York's manual for your unit and your facility's lockout/tagout procedures.