A York YK takes the oil named on the label on its oil sump, and York picks that oil by refrigerant and evaporator temperature, not by the YK style. Per York form 50.40-O1, Table 1, an R-134a or R-513A YK running at an evaporator saturation of 57.2°F (14°C) or lower uses York K oil (5 gal: 011-00533-000), an R-1234ze or R-515B unit at 36°F (2.2°C) or lower uses York J oil (5 gal: 011-00558-000), and York F oil (5 gal: 011-00434-000) is listed only for R-22 or R-717. F oil is not listed for R-134a, R-513A, R-1234ze or R-515B, the refrigerants York names for YK Styles G and H.
Which York oil goes with which refrigerant?
Form 50.40-O1 covers YK, YST, YD, CYK, SCYK, YKEP, YKCP and YT centrifugal chillers in one table. The rows below are from Table 1, "Oil application table."
| Refrigerant | Operating mode | York oil | 5 gal P/N | 55 gal P/N | 2.5 gal P/N |
|---|---|---|---|---|---|
| R-134a or R-513A | Evap saturation ≤ 57.2°F (14°C) | K | 011-00533-000 | 011-00534-000 | 011-01046-000 |
| R-134a or R-513A | Evap saturation ≤ 57.2°F (14°C) | SK | 011-01257-000 | 011-01256-000 | 011-01258-000 |
| R-134a or R-513A | Evap saturation 57.2–82.4°F (14–28°C) | H | 011-00549-000 | 011-00550-000 | 011-00993-000 |
| R-134a or R-513A | Evap saturation > 82.4°F (28°C), auxiliary compressor or condenser venting | H | 011-00549-000 | 011-00550-000 | 011-00993-000 |
| R-1234ze or R-515B | Evap saturation ≤ 36°F (2.2°C) | J | 011-00558-000 | 011-00559-000 | See note |
| R-1234ze or R-515B | Evap saturation 36–65°F (2.2–18.3°C) | H | 011-00549-000 | 011-00550-000 | 011-00993-000 |
| R-1234ze or R-515B | Evap saturation 65–88°F (18.3–31.1°C), or > 65°F with auxiliary compressor or condenser venting | AA | 011-01370-000 | 011-01369-000 | 011-01371-000 |
| R-123 | All conditions | C | 011-00312-000 | 011-00313-000 | N/A |
| R-22 or R-717 | Evap saturation > -20°F (-28.9°C) | C | 011-00312-000 | 011-00313-000 | N/A |
| R-22 or R-717 | Evap saturation > -20°F (-28.9°C) | F | 011-00434-000 | 011-00426-000 | N/A |
Note: the 2.5 gal part number in the J row is printed irregularly in the 50.40-O1 (725) table, so confirm it with us before ordering. Table 1 lists the evaporator saturation range, so the same refrigerant can call for a different oil on a heat recovery or high-temperature job. The table also has CYK-only rows and an R-12/R-500 (B oil) row, not shown here.
How do you know which oil your YK has?
Check the sump label first. Form 50.40-O1 says all chillers ship with a label on the oil sump showing the specified oil type, and to use Table 1 only if the label is missing or can't be read. The YK Style G and Style H operation manuals (160.75-O1 and 160.76-O1) add that all York compressors have specific oil requirements based on duty and refrigerant, and that any deviation from the specified oil can lead to premature compressor component failures.
Don't go by the YK style letter alone. York's Style G and Style H manuals cover R-134a, R-513A and R-1234ze units, which can take K, H or J oil depending on refrigerant and operating mode.
Can you mix York K, F and J oil, or switch types?
No mixing. Form 50.40-O1 states: "Never mix different oil types, brands, or additives." It also says: "When changing the lubricant, the entire volume of lubricant must be changed." It adds:"Take adequate measures to ensure that all residual lubricant is removed from the system."
Switching between H, K or SK (R-134a/R-513A units), between H, J or AA (R-1234ze/R-515B units), or between C and F (R-22/R-717 units), calls for the form's draining, flushing and refrigerant handling procedure. One step of that procedure is "Replace the oil filter."
How much oil does a YK hold?
Form 50.40-O1, Table 2 gives the quantity needed to fill the oil sump in an empty oil system:
| Chiller | Compressors | Fill quantity |
|---|---|---|
| YK | Q3 to Q8 | 11.0 gal |
| YK or YST | J1 to J4 and P6 to P9 | 20.0 gal |
| YK or YST | H, P8, K1 to K4 | 17.5 gal |
| YK or YST | K7 | 24.0 gal |
| YD | All | 45.0 gal |
| YKEP or YKCP | All | 45.0 gal |
The table lists P8 in two rows as printed. Check the compressor code on your nameplate and confirm the fill against the sump sight glass when you charge.
When should YK oil be changed?
Form 50.40-O1 says to perform a complete oil analysis on an annual basis, and to change the oil if the results show any parameter outside its testing limits. York's oil analysis kit is 064-54053-000. The Style G and Style H annual inspection lists (160.75-O1 and 160.76-O1) include conducting an oil analysis and draining and replacing the oil in accordance with 50.40-O1.
Selected York K oil limits from 50.40-O1, Table 5 ("YORK K oil analysis parameters"):
| Property | New | Marginal | Unacceptable |
|---|---|---|---|
| Viscosity at 40°C (cSt) | 30–35 | 25–29 and 36–40 | <25 and >40 |
| Acid number (mg KOH/g) | 0.1 | 0.3 | >0.5 |
| Water content (ppm) | <100 | 100–300 | >300 |
| Iron, copper, lead, tin, aluminum (ppm) | 0 | 10 | >10 |
J, H, F and C oils have their own limit tables in 50.40-O1 (Tables 4, 6, 7 and 8). Use the table for the oil in your sump. For the oil pressure side of the system, see York Chiller Oil Low Differential Pressure Shutdown: What to Check.
Parts involved
| Component | Role | Where to find it |
|---|---|---|
| York K oil, 5 gal | R-134a/R-513A, evap sat ≤ 57.2°F | York 011-00533-000 York "K" Compressor Oil, 5 Gallon | OEM Chiller Part |
| York K oil, 2.5 gal | Same duty, smaller container per Table 1 | York 011-01046-000 Oil, Compressor (York "K") | OEM Chiller Part |
| York H oil, 5 gal | Higher evaporator saturation ranges | York 011-00549-000 Oil, Compressor (York "H", 5 Gallon) | OEM Chiller Part |
| York J oil, 5 gal | R-1234ze/R-515B, evap sat ≤ 36°F | York 011-00558-000 Oil, J, 5-GAL | OEM Chiller Part |
| York F oil, 5 gal | R-22 or R-717 row only | York 011-00434-000 Oil, F, 5-GAL | OEM Chiller Part |
| York C oil, 5 gal | R-123 and R-22/R-717 rows | York 011-00312-000 Oil, Compressor (York "C", 5 Gallon) | OEM Chiller Part |
| Oil analysis kit | Annual oil analysis per 50.40-O1 | York 064-54053-000 Oil Analysis Kit | OEM Chiller Part |
| All York oils | Browse | York Chiller Compressor Oil & Chemicals |
Which York units this applies to
- YK Mod G: R-134a, R-513A or R-1234ze per 160.75-O1; oil per the sump label and 50.40-O1.
- YK Mod H: same refrigerants per 160.76-O1.
- YK Mod F: covered by the same 50.40-O1 table.
- YD Mod C: YD is covered by 50.40-O1; fill is 45.0 gal per Table 2.
- CYK: 50.40-O1 has CYK-only rows; check the sump label.
Scope: Oil types, part numbers, quantities and limits come from York form 50.40-O1 (725), which covers YK, YST, YD, CYK, SCYK, YKEP, YKCP and YT centrifugal chillers. Annual inspection items come from 160.75-O1 (YK Style G) and 160.76-O1 (YK Style H). Screw and scroll chillers are not covered.
Before you order
Read the oil type from the sump label and the model and serial number from the nameplate. Tell us the refrigerant too. To confirm the oil and container size, contact us at help@totalhvacparts.com or 610-487-7999.
Frequently Asked Questions
What oil does a York YK chiller use?
The oil on the sump label. Per York form 50.40-O1, an R-134a or R-513A YK at an evaporator saturation of 57.2°F (14°C) or lower uses York K oil, 011-00533-000 in 5 gallons.
Can I mix York K oil and York H oil?
No. York form 50.40-O1 says never to mix oil types, brands or additives, and that changing between H, K or SK requires the draining and flushing procedure.
Which York oil is used with R-1234ze?
York form 50.40-O1 lists J oil (5 gal 011-00558-000) at evaporator saturation of 36°F (2.2°C) or lower, H oil from 36–65°F, and AA oil from 65–88°F.
How often should York YK oil be tested?
York form 50.40-O1 calls for a complete oil analysis every year, and an oil change if any result is outside the testing limits.
Does a York YK take F oil?
Not on the refrigerants York lists for YK Styles G and H. York form 50.40-O1, Table 1 lists F oil (5 gal 011-00434-000) only for R-22 or R-717 at evaporator saturation above -20°F (-28.9°C); R-134a and R-513A units use K, SK or H oil.
How many gallons of oil does a York YK with a Q compressor hold?
York form 50.40-O1, Table 2 gives 11.0 gallons to fill the sump of an empty oil system on a YK with Q3 to Q8 compressors.
Sources
- York form 50.40-O1 (725), YORK Oil Application, Oil Change Interval, and Oil Quality Limits Replacement Recommendations (Tables 1, 2 and 5, oil change and flushing guidance)
- York form 160.75-O1, YK Style G Operation and Maintenance (oil charge, annual inspections)
- York form 160.76-O1, YK Style H Operation and Maintenance (oil charge, annual inspections)
- Live product titles for the parts listed above, as shown on each product page
Compressor oil in a chiller is under refrigerant pressure and may be hot. Service should be performed only by qualified personnel, following York's manual for your unit and your facility's lockout/tagout procedures.