Skip to content

York YR Screw Chiller Oil Filter: Which Kit (364-50438-000) and When to Change It?

On a York YR twin-screw chiller, the oil filter element comes as "Kit, Filter and O-ring". York renewal-parts form 160.81-RP4 (YR Style C) lists it as 364-50438-000 and 364-50438-001, quantity 2, in the T0 to T3 compressor filter tables, and form 160.81-RP1 (YR Style A) lists 364-50438-001. York form 160.81-O1 sets pressure limits rather than a calendar interval: the OptiView shows "Warning – Oil - Dirty Filter" at 18 psid and makes an "Oil - Clogged Filter" shutdown at 25 psid (software C.OPT.05.09.303 and later).

Which oil filter kit does a York YR use?

York's YR parts manuals split the oil filter into single-filter and dual-filter arrangements on the T0 to T3 compressors. Table of contents lines read "T0 THROUGH T3 COMPRESSOR COMPONENTS SINGLE FILTER" and "T0 THROUGH T3 COMPRESSOR COMPONENTS DUAL FILTER".

Item as listed Single filter Dual filter
Bracket, Oil Filter 075-41294-000, qty 1 075-41298-000, qty 1
Housing, Filter Oil 026-37589-000, qty 1 026-37589-000, qty 2
Kit, Filter and O-ring 160.81-RP4 (Style C): 364-50438-000 and 364-50438-001, qty 2. 160.81-RP1 (Style A): 364-50438-001, qty 2, in both tables.
Valve, 3-way Ball — 022-10094-000, qty 1
Tee, Union 3/4" — 023-18913-000, qty 1

Our listing for 364-50438-001 shows it as replaced by 364-50438-000; confirm by model and serial number before ordering. If your unit has two filter housings, it is the dual-filter arrangement; the parts list shows a 3-way ball valve only on that arrangement.

The same filter tables list O-rings 028-12961-006, 028-12961-015 and 028-12961-001, and isolation valves 022-10092-000 and 022-10046-000. Form 160.81-RP4 also lists an O-ring kit, 028-15058-000.

How does the YR control center know the filter is dirty?

York form 160.81-O1 (1020), page 40 (Oil Separator Screen), defines:

Differential Filter Pressure = (Discharge Pressure – Oil Pressure) ± Offset Pressure

Discharge pressure is the pressure at the oil filter inlet, and oil pressure is the pressure at the compressor inlet. The offset is derived during the first 15 seconds of the start sequence. York says this value is "used to check for filter clogging". If either transducer is out of range, the display shows XX.X.

At what pressure drop do you change a York YR oil filter?

Form 160.81-O1 (1020) gives a warning and a shutdown. Both trigger when the oil filter differential pressure exceeds the limit for 8 continuous seconds. The limits depend on the control center software version:

Software version Warning – Oil - Dirty Filter (p. 86) Oil - Clogged Filter shutdown (p. 92)
C.OPT.05.09.303 and later 18 PSID 25 PSID
C.OPT.05.04.303 through C.OPT.05.08.303 28 PSID 32 PSID
C.MLM.05.03.303 and earlier 20 PSID 25 PSID
  • The warning clears automatically when the condition is no longer present.
  • On C.OPT.05.09.303 and later, the clogged-filter check is bypassed for the first 3 minutes of chiller run time.
  • The clogged-filter message is a safety shutdown. Find the cause before restarting.

Our practical advice (not a York interval): treat the dirty-filter warning as the signal to schedule the kit change. Waiting for the clogged-filter shutdown means an unplanned trip.

Parts involved

Component Role Where to find it
Oil filter and O-ring kit "Kit, Filter and O-ring", 160.81-RP4 York 364-50438-000 Oil Filter Element Kit | OEM Chiller Part
Earlier kit number Listed in 160.81-RP1 and 160.81-RP4 York 364-50438-001 Oil Filter Element Kit (Replaced by 364-50438-000)
O-ring Listed in the T0 to T3 filter tables York 028-12961-006 O-Ring, 2.95 x 23.47 mm | OEM Chiller Part
O-ring Listed in the T0 to T3 filter tables York 028-12961-015 O-Ring, 0.739" x 0.070" | OEM Chiller Part
O-ring Listed in the T0 to T3 filter tables York 028-12961-001 O-Ring, 1.83 x 8.92 mm | OEM Chiller Part
Isolation valve "Valve, Stop Ang Vertical", filter tables York 022-10092-000 Valve, Angle (Isolation, 7/16") | OEM Chiller Part
Isolation valve "Valve, Stop Ang Vertical", filter tables York 022-10046-000 Valve, Isolation Angle (SC 1-3/16") | OEM Chiller Part
Other filters and driers Browse by category York Chiller Oil Filters & Filter Driers

Which York units this applies to

Scope: York forms 160.81-RP4 (622), YR Style C, and 160.81-RP1 (622), YR Style A, rotary screw liquid chillers YR TA TA T0 through YR XD XD T3 (200 to 430 tons 60 Hz, 170 to 365 tons 50 Hz, R-134a), and form 160.81-O1 (1020), YR Style A, B and C with OptiView control center. Thresholds apply to the software versions listed. York marks RP manuals as reference only.

Before you order

Read the chiller model and serial number from the nameplate, count the oil filter housings (one or two), and note the control center software version from the OptiView if you are judging the pressure drop. To confirm fit, contact us at help@totalhvacparts.com or 610-487-7999 with the model, serial number and part number. For the YT centrifugal filter, see York YT Oil Filter Element 026-37915-000; for oil pressure trips, see York Chiller Oil Low Differential Pressure Shutdown.

Frequently Asked Questions

What oil filter kit does a York YR Style C use?

York form 160.81-RP4 lists "Kit, Filter and O-ring" 364-50438-000 and 364-50438-001, quantity 2, for the T0 to T3 compressor filter arrangements. Our listing shows -001 replaced by -000.

When should I change the oil filter on a York YR chiller?

York form 160.81-O1 gives pressure limits, not a calendar interval. It shows "Warning – Oil - Dirty Filter" when filter differential pressure exceeds 18 psid for 8 continuous seconds on software C.OPT.05.09.303 and later, which is a practical point to schedule the kit change.

What causes an "Oil - Clogged Filter" shutdown on a York YR?

Form 160.81-O1 says the chiller shuts down when oil filter differential pressure exceeds 25 psid for 8 continuous seconds (32 psid on software C.OPT.05.04.303 through C.OPT.05.08.303).

How is YR oil filter differential pressure calculated?

York form 160.81-O1 defines it as discharge pressure minus oil pressure, plus or minus an offset that the control center derives during the first 15 seconds of the start sequence.

Sources

Form 160.81-O1 labels the pressure at the YR oil filter inlet as discharge pressure, so isolate and relieve the filter housing before opening it. Service should be performed only by qualified personnel, following York's manual for your unit and your facility's lockout/tagout procedures.